1、Designation: D2665 14 An American National StandardStandard Specification forPoly(Vinyl Chloride) (PVC) Plastic Drain, Waste, and VentPipe and Fittings1This standard is issued under the fixed designation D2665; the number immediately following the designation indicates the year oforiginal adoption o
2、r, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the U.S. Department of Defense.1. S
3、cope*1.1 This specification covers requirements and test methodsfor materials, dimensions and tolerances, pipe stiffness, crushresistance, impact resistance, and solvent cement for poly(vinylchloride) plastic drain, waste, and vent pipe and fittings.Aformof marking is also included. Plastic which do
4、es not meet thematerial requirements specified in Section 5 is excluded.Installation procedures are given in the Appendix.1.2 The values stated in inch-pound units are to be regardedas standard. The values given in parentheses are mathematicalconversions to SI units that are provided for information
5、 onlyand are not considered standard.1.3 The text of this specification references notes, footnotes,and appendixes which provide explanatory material. Thesenotes and footnotes (excluding those in tables and figures) shallnot be considered as requirements of the specification.1.4 The following safety
6、 hazards caveat pertains only to thetest methods portion, Section 7, of this specification: Thisstandard does not purport to address all of the safety concerns,if any, associated with its use. It is the responsibility of the userof this standard to establish appropriate safety and healthpractices an
7、d determine the applicability of regulatory limita-tions prior to use.2. Referenced Documents2.1 ASTM Standards:2D618 Practice for Conditioning Plastics for TestingD1600 Terminology forAbbreviated Terms Relating to Plas-ticsD1784 Specification for Rigid Poly(Vinyl Chloride) (PVC)Compounds and Chlori
8、nated Poly(Vinyl Chloride)(CPVC) CompoundsD2122 Test Method for Determining Dimensions of Ther-moplastic Pipe and FittingsD2412 Test Method for Determination of External LoadingCharacteristics of Plastic Pipe by Parallel-Plate LoadingD2444 Test Method for Determination of the Impact Resis-tance of T
9、hermoplastic Pipe and Fittings by Means of aTup (Falling Weight)D2564 Specification for Solvent Cements for Poly(VinylChloride) (PVC) Plastic Piping SystemsD3311 Specification for Drain, Waste, and Vent (DWV)Plastic Fittings PatternsF402 Practice for Safe Handling of Solvent Cements,Primers, and Cle
10、aners Used for Joining ThermoplasticPipe and FittingsF412 Terminology Relating to Plastic Piping SystemsF1498 Specification for Taper Pipe Threads 60 for Thermo-plastic Pipe and FittingsF1866 Specification for Poly (Vinyl Chloride) (PVC) PlasticSchedule 40 Drainage and DWV Fabricated FittingsF2135 S
11、pecification for Molded Drain, Waste, and Vent(DWV) Short-Pattern Plastic Fittings3. Terminology3.1 Definitions are in accordance with Terminology F412,and abbreviations are in accordance with Terminology D1600,unless otherwise specified.4. Significance and Use4.1 The requirements of this specificat
12、ion are intended toprovide pipe and fittings suitable for the drainage and ventingof sewage and certain other liquid wastes.NOTE 1Industrial waste disposal lines should be installed only withthe specific approval of the cognizant building code authority sincechemicals not commonly found in drains an
13、d sewers and temperatures inexcess of 180F (82.2C) may be encountered.NOTE 2This specification does not include requirements for pipe andfittings intended to be used to vent combustion gases.5. Materials5.1 Basic MaterialsThe pipe shall be made of virgin PVCcompounds meeting or exceeding the require
14、ments of Class1This specification is under the jurisdiction of ASTM Committee F17 on PlasticPiping Systems and is the direct responsibility of Subcommittee F17.63 on DWV.Current edition approved May 1, 2014. Published June 2014. Originallyapproved in 1968. Last previous edition approved in 2012 as D
15、2665 12. DOI:10.1520/D2665-14.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.*A Summary of Changes section a
16、ppears at the end of this standardCopyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States112454 as defined in Specification D1784. The fittings shall bemade of virgin PVC compounds meeting or exceeding therequirements of Class 12344 as define
17、d in SpecificationD1784, but with a tensile strength of not less than 6500 psi anda modulus of elasticity for not less than 380,000 psi. Theseplastics contain stabilizers, lubricants, and pigments.5.2 Rework MaterialThe manufacturer shall use only hisown clean pipe or fitting rework material, and th
18、e pipe orfittings produced shall meet all the requirements of thisspecification.5.3 Solvent CementThe solvent cement used to join pipeand fittings made to this specification shall meet the require-ments of Specification D2564.6. Requirements6.1 GeneralThe pipe and fittings shall be homogeneousthroug
19、hout and free of visible cracks, holes, foreign inclusions,or other injurious defects. The pipe shall be as uniform ascommercially practicable in color, opacity, density, and otherphysical properties.6.1.1 The requirements in this section are intended only foruse as quality control tests, not as sim
20、ulated service tests.6.2 Dimensions and Tolerances:6.2.1 MethodAll dimensions shall be determined in accor-dance with Test Method D2122.6.2.2 Dimensions:6.2.2.1 The outside diameter and wall thicknesses of pipeshall meet the requirements of Table 2. The pipe shall be ineither 10 or 20-ft (3.05 or 6.
21、1-m) lengths, unless otherwisespecified, with an allowable tolerance of +12, 0 in. (+13, 0mm).6.2.2.2 The patterns, dimensions, and laying lengths offittings, including adaptors, shall meet the requirements ofSpecification D3311 and Table 1.6.2.2.3 Reducer bushings of sizes 2 by 114 and 4 by 3 shall
22、be permitted to have the socket wall thickness and spigot wallthickness below the minimum requirements defined in Table 1,but not less than 0.098 in. (2.5 mm), provided the inner socketand outer spigot are reinforced by a minimum of four ribs. Thethickness of the supporting ribs shall not be less th
23、an 0.098 in.(2.5 mm).6.2.2.4 The patterns, dimensions, and laying lengths ofShort-Pattern fittings shall meet the requirements of Specifica-tion F2135.6.2.2.5 For all fittings having taper pipe threads, threadsshall conform to Specification F1498 and be gaged in accor-dance with 7.5. Fittings of nom
24、inal sizes not given in Speci-fication F1498 shall not have threads.6.2.2.6 Fabricated DWV fittings shall comply with Specifi-cation F1866.6.3 Pipe Stiffness, Deflection Load and Flattening:6.3.1 PipeThe minimum pipe stiffness at 5 % deflectionshall be in accordance with Table 3. The pipe shall defl
25、ect by60 % of the nominal outside diameter (flattening) withoutcracking, rupture, or other visible evidence of failure whentested in accordance with 7.4.6.3.1.1 Pipe Stiffness (PS)Three specimens shall be tested.If all three meet the PS requirement, the sample meets the PSrequirement. If one or two
26、fail, additional testing shall beconducted in accordance with 6.3.1.2. If all three fail, thesample does not meet the PS requirement.6.3.1.2 Pipe Stiffness and Lower Confidence LimitIn theevent that one or two of the specimens tested in 6.3.1 fail tomeet the minimum PS requirement, the average pipe
27、stiffnessof eleven specimens shall meet or exceed the minimumrequirement given in Table 3. The 99 % lower confidence limit(LCL) shall be within 15 % of the average value. The LCLshall be calculated using the Students “t” distribution, withN-1 degrees of freedom, where N is the number of specimens.Th
28、e critical t value shall be used to at least three significantdigits. Alternatively, if the LCL exceeds the minimum PSrequirement in Table 3, but is not within 15 % of the average,the sample meets the requirements of the pipe stiffness testing.The eleven specimens include the three tested under 6.3.
29、1, andan additional eight with rotation by 35, as specified in TestMethod D2412, continuing throughout the remaining speci-mens.6.3.1.3 The LCL based on testing eleven specimens iscalculated as follows:LCL 5 avg PS! 2 $2.76std. dev.!/=N!% (1)where:avg PS! 5 (PSi!#/ (2)std. dev.! 5 F(PS22 (PS!2/NN 2
30、1G1/2N=116.3.1.4 The 15 % requirement is calculated as follows:Avg 2 LCL!/Avg! 3100#15% (3)NOTE 3The 5 % deflection criterion, which was arbitrarily selectedfor testing convenience, should not be considered as a limitation withrespect to in-use deflection. The engineer is responsible for establishin
31、gthe acceptable deflection.6.3.2 FittingsIndividual fittings unassembled shall with-stand a minimum load of 750 lbf/ft (11 kN/m) of centerlinelength without cracking or other visible evidence of failurewhen tested in accordance with 7.4.6.4 Impact ResistanceThe minimum impact resistance ofpipe and f
32、ittings, when tested at the time of manufacture, shallcomply with Table 4. Test in accordance with Test MethodD2444 using Tup C and Holder A for pipe and Tup A andHolder B for fittings. Use a 12-lb (5-kg) tup for testing pipesizes 4 in. and smaller and a 20-lb (10-kg) tup for pipe largerthan 4 in. T
33、est fittings with a 12-lb (5-kg) Tup. Test couplingscemented to short pieces of pipe and allowed to dry for 24 h.For fittings larger than 4-in, a symmetric section cut from thehub or body with a minimum centerline length of 2 in. shall bepermitted to be used rather than the entire fitting.D2665 1426
34、.4.1 Test 10 specimens. When 9 or 10 specimens pass,accept the lot. When 2 or more specimens fail, test 10additional specimens. When 17 of 20 specimens tested pass,accept the lot. When 4 or more of 20 specimens tested fail, test20 additional specimens. When 32 of 40 specimens pass,accept the lot. Wh
35、en 9 or more of 40 specimens fail, the lotdoes not meet the requirements of this specification.6.4.2 Failure in the test specimens shall be shattering or anycrack or break extending entirely through the pipe wall andvisible to the unaided eye.TABLE 1 Dimensions and Tolerances for Fitting Sockets for
36、 PVC Schedule 40 Drain, Waste and Vent Pipe FittingsNominalPipeSizeABCEMSocket Entrance Diameter Socket Bottom DiameterSocketDepth,minWallthicknessmin.AInternal ThreadsAverage Toleranceon Avg.Out-of-RoundnessAverage Toleranceon Avg.Out-ofRoundnessOutsideDiameter ofHub, M. min.Threadlengthmin.in. (mm
37、)114 1.675(42.54)+0.010/-0.005(+0.25/-0.13)0.024(0.61)1.655(42.04)0.005(0.13)0.024(0.61)0.687(17.44)0.156(3.96)1.871(47.52)0.687(17.44)112 1.915(48.64)+0.010/-0.005(+0.25/-0.13)0.024(0.61)1.894(48.11)0.006(0.15)0.024(0.61)0.687(17.44)0.156(3.96)2.127(54.03)0.687(17.44)2 2.390(60.71)+0.010/-0.005(+0.
38、25/-0.13)0.024(0.61)2.369(60.17)0.006(0.15)0.024(0.61)0.750(19.05)0.156(3.96)2.634(66.90)0.750(19.05)3 3.520(89.41)+0.010/-0.005(+0.25/-0.13)0.030(0.76)3.492(88.70)0.008(0.20)0.030(0.76)1.500(38.10)0.219(5.56)3.841(97.56)1.187(30.15)4 4.520(114.8)+0.010/-0.005(+0.25/-0.13)0.030(0.76)4.491(114.1)0.00
39、9(0.23)0.030(0.76)1.750(44.45)0.250(6.35)4.907(124.6)1.28(32.54)6 6.647(168.8)+0.015/-0.010(+0.38/-0.25)0.060(1.52)6.614(168.0)0.011(0.28)0.060(1.52)3.000(76.200.281(7.14)7.203(183.0)1.500(38.10)8 8.655(219.8)+0.030/-0.000(+0.76/-0.00)0.090(2.29)8.610(218.7)0.015(0.38)0.090(2.29)4.000(101.6)0.328(8.
40、33)BB10 10.780(273.8)+0.025/-0.020(+0.64/-0.51)0.120(3.05)10.737(272.7)0.015(0.38)0.120(3.04)5.000(127.0)0.365(9.28)BB12 12.780(324.6)+0.030/-0.025(+0.76/-0.64)0.150(3.81)12.736(323.5)0.015(0.38)0.150(3.81)6.000(152.4)0.406(10.3)BBAThe value for wall thickness shown in Table 1 is an averaged minimum
41、. An averaged minimum is derived by adding two wall thicknesses that are directly opposite eachother and dividing the result by 2. The reason for an averaged minimum wall thickness is due to core shift which is a normal occurrence found in fittings that are injectionmolded. When core shift occurs, t
42、he result is a pair of high and low wall thickness readings. The average of the high and the low wall thickness readings must equal orexceed the averaged minimum value shown in Table 1. The low wall thickness reading shall not be more than 10% below the averaged minimum value shown in Table1. This a
43、pplies to any point on the fitting (hub, body, or spigot). In cases where there is no opposite side (as in the case of a portion of the branch of a wye fitting) thenthe single wall thickness reading shall not be more than 10% below the averaged minimum value shown in Table 1.BNot applicable for thes
44、e nominal sizes.D2665 1436.4.3 Bushings increasers and closet flanges are exemptfrom this requirement.7. Test Methods7.1 SamplingAsample of the pipe and fittings sufficient todetermine conformance with this specification shall be taken atrandom from each lot or shipment. About 40 ft (12 m) of pipear
45、e required to make the tests prescribed. The number offittings required varies depending on the size and type offitting.7.1.1 Test SpecimensNot less than 50 % of the test speci-mens required for any pressure test shall have at least a part ofthe marking in their central sections. The central section
46、 is thatportion of pipe which is at least one pipe diameter away froman end closure.7.2 Conditioning:7.2.1 For referee purposes, condition the specimens prior totest at 73.4 6 3.6F (23 6 2C) and 50 6 5 % relativehumidity in accordance with Practice D618, Procedure A.7.2.2 For routine quality control
47、 testing, condition the speci-mens at the temperature and humidity of the manufacturerstesting facility for not less than1horuntil the specimens areat the room temperature.7.3 Test Conditions:7.3.1 For referee purposes, conduct tests in the standardlaboratory atmosphere of 73.4 6 3.6F (23 6 2C) and
48、50 65 % relative humidity.7.3.2 For routine control testing, conduct tests at the roomtemperature and humidity of the manufacturers testing area.TABLE 2 Dimensions and Tolerances for Outside Diameters and Thicknesses of PVC Plastic Drain, Waste, and Vent PipeNominal Pipe SizeOutside Diameter Wall Th
49、icknessAverageTolerance onAverageOut-of-Roundness(maximum minus minimum)MinimumTolerancein. (mm)114 1.660 (42.16) 0.005 (0.13) 0.024 (0.61) 0.140 (3.56) +0.020 (0.51)0.000112 1.900 (48.26) 0.006 (0.15) 0.024 (0.61) 0.145 (3.68) +0.020 (0.51)0.0002 2.375 (60.33) 0.006 (0.15) 0.024 (0.61) 0.154 (3.91) +0.020 (0.51)0.0003 3.500 (88.90) 0.008 (0.20) 0.030 (0.76) 0.216 (5.49) +0.026 (0.66)0.0004 4.500 (114.30) 0.009 (0.23) 0.100(2.54) 0.237 (6.02) +0.028 (0.71)0.0006 6.625 (168.28) 0.011 (0.28) 0.100 (2.54) 0.280 (