1、 Tentative Interim Amendment NFPA30B Code for the Manufacture and Storage of Aerosol Products 2015 Edition Reference: 7.2.1, 7.2.2, 7.2.2.1, 7.2.2.1.1(new), 7.2.2.2 and Table 7.2.3.1 TIA 15-3 (SC 16-4-2 / TIA Log #1198R) Pursuant to Section 5 of the NFPA Regulations Governing the Development of NFPA
2、 Standards, the National Fire Protection Association has issued the following Tentative Interim Amendment to NFPA 30B, Code for the Manufacture and Storage of Aerosol Products, 2015 edition. The TIA was processed by the Technical Committee on Aerosol Products, and was issued by the Standards Council
3、 on April 6, 2016, with an effective date of April 26, 2016. A Tentative Interim Amendment is tentative because it has not been processed through the entire standards-making procedures. It is interim because it is effective only between editions of the standard. A TIA automatically becomes a public
4、input of the proponent for the next edition of the standard; as such, it then is subject to all of the procedures of the standards-making process. 1. Revise sections 7.2.1, 7.2.2, 7.2.2.1, 7.2.2.1.1(new) and 7.2.2.2 to read as follows: 7.2 Sales Display Areas Aerosol Storage Not Exceeding 2.4 m (8 f
5、t) High. 7.2.1 Level 1 aerosol products and plastic aerosol 1 products in sales display areas shall not be limited in quantity. 7.2.2 When located in sales display areas, aerosol cooking spray products and Level 2 and Level 3 aerosol products shall be removed from combustible cartons or the combusti
6、ble cartons shall be display-cut, except as provided for in 7.2.2.1 and 7.2.2.2, respectively. 7.2.2.1 Cartoned aerosol cooking spray products shall be permitted in the sales display area, provided the area is protected in accordance with one of the following: (1) Table 6.3.2.3(a) or Table 6.3.2.3(b
7、), or (2) Paragraph 7.2.3.1. 7.2.2.1.1 Protection in accordance with Table 6.4.2.7(a) through Table 6.4.2.7(l) shall also be permitted for aerosol cooking spray products. 7.2.2.2 Cartoned Level 2 and Level 3 aerosol products shall be permitted in the sales display area, provided the area is protecte
8、d in accordance with one of the following: (1) Table 6.4.2.7(a) through Table 6.4.2.7(l), or (2) Paragraph 7.2.3.1. 2. Revise the title of Table 7.2.3.1 to read as follows: Table 7.2.3.1 Maximum Quantity per Floor of Aerosol Cooking Spray Products, and of Level 2 and Level 3 Aerosol Products Issue Date: April 6, 2016 Effective Date: April 26, 2016 (Note: For further information on NFPA Codes and Standards, please see www.nfpa.org/codelist) Copyright 2016 All Rights Reserve NATIONAL FIRE PROTECTION ASSOCIATION