1、 Errata NFPA 409 Standard on Aircraft Hangars 2016 Edition Reference: 7.5.3 Errata No: 409-16-1 The Committee on Airport Facilities notes the following error in the 2016 edition of NFPA 409, Standard on Aircraft Hangars. Note: Prior to the printing of NFPA 409, this error was noted and incorporated
2、into the standard at the time of issuance. 1. Update the reference to a section in NFPA 11 to read as follows: 7.5.3 The discharge rate of the system shall be based on the application rate multiplied by the entire aircraft storage and servicing floor area. The application total discharge rate shall
3、include the sprinkler breakdown factor specified in 2.3.5.2(b) 6.12.8.2.3.2 of NFPA 11. Issue Date: July 14, 2015 (Note: Electronic products and pamphlet reprints may have this errata incorporated. For current information about the NFPA Codes and Standards, including this errata, please see www.nfpa.org/codelist) Copyright 2015 All Rights Reserved NATIONAL FIRE PROTECTION ASSOCIATION