1、 Errata NFPA 99 Health Care Facilities Code2018 Edition Reference: 6.7.5.1.2.2 and 6.7.6.2.1.5(B) Errata No: 99-18-1 The Technical Committee on Electrical Systems and the Correlating Committee on Health Care Facilities notes the following errors in the 2018 edition of NFPA 99, Health Care Facilities
2、 Code. 1. Correct 6.7.5.1.2.2 to read as follows: 6.7.5.1.2.2 The following portions of Article 700 of NFPA 70 shall be amended as follows: (1) 700.4 shall not apply. (2) 700.10 (D)(1) through (3) shall not apply. (3) 700.17 Branch Circuits for Emergency Lighting. Branch circuits that supply emergen
3、cy lighting shall be installed to provide service from a source complying with 700.12 when the normal supply for lighting is interrupted or where single circuits supply luminaires containing secondary batteries. (4) 700.2832 shall not apply. 2. Correct 6.7.6.2.1.5(B) to read as follows: 6.7.6.2.1.5
4、Life Safety Branch. (A) For the purposes of this code, Article 700 of NFPA 70 shall only be applied to the life safety branch. (B) The following portions of Article 700 of NFPA 70 shall be amended as follows: (1) 700.4 shall not apply. (2) 700.10 (D)(1) through (3) shall not apply. (3) 700.17 Branch
5、 Circuits for Emergency Lighting. Branch circuits that supply emergency lighting shall be installed to provide service from a source complying with 700.12 when the normal supply for lighting is interrupted or where single circuits supply luminaires containing secondary batteries. (4) 700.2832 shall
6、not apply. Issue Date: September 22, 2017 (Note: Electronic products and pamphlet reprints may have this errata incorporated. For current information about the NFPA Codes and Standards, including this errata, please see www.nfpa.org/docinfo) Copyright 2017 All Rights Reserved NATIONAL FIRE PROTECTION ASSOCIATION