1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL UL 758 Appliance Wiring MaterialUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM ULUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPR
2、ODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL UL Standard for Safety for Appliance Wiring Material, UL 758 Third Edition, Dated May 2, 2014 Summary of Topics This revision to ANSI/UL 758 has been made to 2.3.2 and Table 7.1 to include additional physical properties. Text that has been changed
3、in any manner or impacted by ULs electronic publishing system is marked with a vertical line in the margin. The new and revised requirements are substantially in accordance with Proposal(s) on this subject dated February 6, 2015. All rights reserved. No part of this publication may be reproduced, st
4、ored in a retrieval system, or transmitted in any form by any means, electronic, mechanical photocopying, recording, or otherwise without prior permission of UL. UL provides this Standard as is without warranty of any kind, either expressed or implied, including but not limited to, the implied warra
5、nties of merchantability or tness for any purpose. In no event will UL be liable for any special, incidental, consequential, indirect or similar damages, including loss of prots, lost savings, loss of data, or any other damages arising out of the use of or the inability to use this Standard, even if
6、 UL or an authorized UL representative has been advised of the possibility of such damage. In no event shall ULs liability for any damage ever exceed the price paid for this Standard, regardless of the form of the claim. Users of the electronic versions of ULs Standards for Safety agree to defend, i
7、ndemnify, and hold UL harmless from and against any loss, expense, liability, damage, claim, or judgment (including reasonable attorneys fees) resulting from any error or deviation introduced while purchaser is storing an electronic Standard on the purchasers computer system. The requirements in thi
8、s Standard are now in effect, except for those paragraphs, sections, tables, gures, and/or other elements of the Standard having future effective dates as indicated in the note following the affected item. The prior text for requirements that have been revised and that have a future effective date a
9、re located after the Standard, and are preceded by a SUPERSEDED REQUIREMENTS notice. AUGUST 7, 2015 UL 758 tr1UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL AUGUST 7, 2015 UL 758 tr2 No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZE
10、D FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL MAY 2, 2014 (Title Page Reprinted: August 7, 2015) 1 UL 758 Standard for Appliance Wiring Material First Edition July, 2000 Second Edition April, 2006 Third Edition May 2, 2014 This ANSI/UL Standard for Safety consists of the Thir
11、d Edition including revisions through including revisions through August 7, 2015. The most recent designation of ANSI/UL 758 as an American National Standard (ANSI) occurred on August 7, 2015. ANSI approval for a standard does not include the Cover Page, Transmittal Pages, Title Page, or effective d
12、ate information. Comments or proposals for revisions on any part of the Standard may be submitted to UL at any time. Proposals should be submitted via a Proposal Request in ULs On-Line Collaborative Standards Development System (CSDS) at http:/. ULs Standards for Safety are copyrighted by UL. Neithe
13、r a printed nor electronic copy of a Standard should be altered in any way. All of ULs Standards and all copyrights, ownerships, and rights regarding those Standards shall remain the sole and exclusive property of UL. COPYRIGHT 2015 UNDERWRITERS LABORATORIES INC. ANSI/UL 758-2015UL COPYRIGHTED MATER
14、IAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL MAY 5, 2014 APPLIANCE WIRING MATERIAL - UL 758 2 No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL CONTENTS INTRODUCTION 1 Scope .5 2 Ge
15、neral 6 2.1 Components .6 2.2 Units of measurement .7 2.3 Undated references .7 CONSTRUCTION 3 General 7 4 Materials 13 5 Conductor .13 5.1 General 13 5.2 Metal 17 5.3 Size and cross-sectional area .23 5.4 Metal coating .25 5.5 Joints 25 5.6 Resistance .25 5.7 Stranding .26 5.8 Separator 29 5.9 Semi
16、-conductive polymeric layer 29 6 Optical Fiber Member(s) 29 6.1 General 29 6.2 Cable composed of both current-carrying conductors and optical-ber members 30 6.3 Cable composed entirely of optical-ber members .30 7 Insulation .30 7.1 General 30 7.2 Materials .31 7.3 Thickness 35 8 Coverings .38 9 Fil
17、lers 39 10 Binders 39 11 Shield(s) .40 12 Cable Assembly 41 13 Overall Jacket .42 13.1 General .42 13.2 Materials 43 13.3 Thickness .43 PERFORMANCE TESTS FOR THERMAL AND CHEMICAL PROPERTIES 14 Physical Properties, Unaged and Air Oven Aged .49 15 Physical Properties, Oil Immersion Aging 51 16 Physica
18、l Properties, Gasoline Conditioning .52 17 Physical Properties, Sunlight Resistance 53 18 Conductor Corrosion Test 53 19 Deformation Test (Thermoplastics and Class XL Only) 54 MAY 5, 2014 APPLIANCE WIRING MATERIAL - UL 758 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUT
19、ION WITHOUT PERMISSION FROM UL 20 Flexibility Test of Nylon Covering .56 21 Flexibility Test 56 22 Heat Shock Test (Thermoplastic Materials Only) 57 23 Cold Bend Test 58 24 Delamination Test 59 25 Shrinkback Test Special Rating TV Wires Only .59 26 Ozone Resistance Test Special Rating TV Use Wires O
20、nly 60 27 Durability of Ink-Print Test .61 TESTS FOR MECHANICAL PROPERTIES 28 Crush Resistance Test 62 TESTS FOR ELECTRICAL PROPERTIES 29 Dielectric Test, Method I .63 30 Dielectric Test, Method II 65 31 Dielectric Test, Method III 66 32 High-Voltage DC Wire Dielectric Voltage-Withstand Test, Method
21、 I .67 33 High-Voltage DC Wire Dielectric Voltage-Withstand Test, Method II .68 34 High-Voltage Cut-Through Test, Special Rated TV Wire Only 69 35 Short Term Insulation-Resistance Test in Water at Room Temperature (Wet Rated AWM) . .71 36 Long Term Insulation-Resistance Test in Water at Elevated Tem
22、perature (Wet Rated AWM) .71 37 Temperature Correction Factor (Wet Rated AWM) 75 38 Capacitance and Relative Permittivity Tests (Wet Rated AWM) .77 39 Stability Factor (Wet Rated AWM) 78 TESTS FOR FLAME PROPERTIES 40 Horizontal Flame Test for Internal Wiring 78 41 Cable Flame Test .78 42 VW-1 Flame
23、Test .78 43 FT-1 Flame Test 79 44 FT-2 Flame Test 79 45 IEC 60332-1 Flame Test .79 46 IEC 60332-2 Flame Test .79 MANUFACTURING AND PRODUCTION TESTS 47 Test for Continuity of Conductors .80 48 Spark Test .81 48.1 Appliance wiring material constructed of insulating materials other than laminated lms a
24、nd laminated constructions without uninsulated intervals .81 48.2 Appliance wiring material constructed of laminated lm insulating material with uninsulated intervals 82 48A Cut-Piece Dielectric Voltage Withstand Test .82A 49 Production-Line Dielectric Test 82B MARKINGS 50 Surface Marking of AWM .82
25、C 51 Markings on Tag, Reel, or Carton .83 52 Multiple Markings .85 DECEMBER 8, 2014 APPLIANCE WIRING MATERIAL - UL 758 4UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL INTRODUCTION 1 Scope 1.1 These requirements cover Appliance Wiring Materi
26、al (AWM) in the form of single insulated conductors, multi-conductor cables, optical bers, individual insulated conductors, and ber optic members for use as components in multi-conductor cables. 1.2 The appliance wiring material covered by the requirements of this Standard are solely for use as fact
27、ory-installed wiring either within the overall enclosure of appliances and other equipment (internal wiring) or as external interconnecting cable for appliances (external wiring), or for further processing as components in multi-conductor cables. 1.3 These requirements do not cover any wire, cable,
28、or cord types that are presently covered in the National Electrical Code (NEC), NFPA 70, and are not intended for installation in buildings or structures in accordance with the NEC except within the scope of the installation instructions of the end-product for which their use is intended. 1.4 These
29、requirements cover appliance wiring material with operating temperatures from a minimum 60C (140F) dry temperature rating and voltage ratings from a minimum 30-volt rating. Conductor size ranges from 50 AWG to 2000 kcmil. Appliance wiring material (AWM) composed entirely of optical ber members or el
30、ectrical conductors in combination with optical ber members are also covered by these requirements. 1.5 These requirements do not cover the optical performance of any optical-ber member or group of such members. 1.6 These requirements do not cover constructions which utilize at, insulated conductors
31、 that are not laid parallel. The requirements for these products are found in the Standard for Flexible Materials Interconnect Constructions, UL 796F. 1.7 The evaluation of the performance of the semi-conductive polymeric layer described in 5.9 is not covered by this Standard. 1.7 effective Septembe
32、r 3, 2014 1.8 In addition to these constructions, this Standard establishes guidelines for the evaluation of special constructions that, due to their specic end product use, are not required to meet all of the requirements for general construction AWM. 1.9 The nal acceptance of AWM is dependent upon
33、 its use in complete equipment that conforms with the standards applicable to such equipment. MAY 5, 2014 APPLIANCE WIRING MATERIAL - UL 758 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL 2 General 2.1 Components 2.1.1 Except as indicated
34、in 2.1.2, a component of a product covered by this Standard shall comply with the requirements for that component. 2.1.2 A component is not required to comply with a specic requirement that: a) Involves a feature or characteristic not required in the application of the component in the product cover
35、ed by this standard, or b) Is superseded by a requirement in this standard. 2.1.3 A component shall be used in accordance with its rating established for the intended conditions of use. 2.1.4 Specic components are incomplete in construction features or restricted in performance capabilities. Such co
36、mponents are intended for use only under limited conditions, such as certain temperatures not exceeding specied limits, and shall be used only under those specic conditions. 2.1.5 Polymeric materials evaluated for its intended use, are not prohibited from being used in the insulation and jacket appl
37、ications indicated in Table 2.1. Table 2.1 Polymeric materials for use in wire and cable and associated AWM ratings Table 2.1 revised December 8, 2014 Minimum average thickness, AWM rating Component inch (mm) Compounds use or rating Sunlight resistant Insulation 0.030 0.76 Outer PVC or TPE insulatio
38、n rated for 720 hours sunlight resistance Sunlight resistant Jacket 0.030 0.76 Outer PVC or TPE jacket rated for 720 hours sunlight resistance 60C Wet Insulation 0.030 0.76 PVC insulation rated for use in Type TW thermoplastic-insulated wire 60C or 75C Wet Insulation 0.030 0.76 PVC insulation rated
39、for use in Types THW or THHW thermoplastic-insulated wire 60C or 75C Wet Insulation 0.015 0.38 PVC insulation rated for use in Type THWN thermoplastic- insulated wire 60C, 75C, or 90C Wet Insulation 0.015 0.38 PVC insulation rated for use in Type THWN-2 thermoplastic- insulated wire DECEMBER 8, 2014
40、 APPLIANCE WIRING MATERIAL - UL 758 6UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL 2.2 Units of measurement 2.2.1 Values stated without parentheses are the requirement. Values in parentheses are explanatory or approximate information. 2.2.
41、2 Unless otherwise indicated, all voltage values mentioned in this Standard are root-mean-square (rms). 2.2.3 Equipment calibrated in metric units is to be used when a requirement is applied in metric terms. 2.3 Undated references 2.3.1 Any undated reference to a code or standard appearing in the re
42、quirements of this standard shall be interpreted as referring to the latest edition of that code or standard. 2.3.2 Wherever the designation UL 1581 is used in this Standard, reference is to be made to the designated part(s) of the Reference Standard for Electrical Wires, Cables, and Flexible Cords,
43、 UL 1581. Wherever the designation UL 62 is used in this Standard, reference is to be made to the designated part(s) of the Standard for Flexible Cords and Cables, UL 62. CONSTRUCTION 3 General 3.1 The acceptability of an AWM for use in a specic end-product is based on the construction and ame ratin
44、g of each individual construction. 3.2 Tables 3.1 3.9 serve as indices to requirements for construction details and basic test methods for typical AWM constructions. 3.3 Coiled cables shall comply with the requirements specied in this Standard. All tests and measurements shall be conducted on specim
45、ens obtained from the straight ends at each end of the coiled portion of the cable. The straight ends shall have been subjected to the same heat conditioning as the coiled portion during the coiling process. In addition, the minimum average thickness and minimum thickness at any point of insulation
46、and jacket shall be made on the coiled portion and shall meet the requirements specied for an uncoiled construction. 3.4 Wires or cables which have a restricted use are those installed where not subject to movement or mechanical abuse, or where totally enclosed. 3.5 A wire or cable for Class 2 use s
47、hall have a voltage rating less than or equal to 150 V AC or DC. 3.5 effective September 3, 2014 3.6 The high voltage DC wire described in Table 3.6 shall have a minimum voltage rating of 3 kV DC. Wires with DC voltage rating less than 3 kV DC shall be evaluated in accordance with Table 3.1. AUGUST
48、7, 2015 APPLIANCE WIRING MATERIAL - UL 758 7UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL Table 3.1 Single or multiple conductor with extruded insulation Conductors: Material See Conductor, Section 5 Size See Conductor, Section 5 Insulatio
49、n: Material See Insulation, Section 7 Thickness See Insulation, Section 7 Covering: Material See Coverings, Section 8 Markings: See Surface Marking of AWM, Section 50, and Markings on Tag, Reel or Carton, Section 51 Basic tests: Physical Properties Unaged and Air Oven Aged, Section 14. Conductor Corrosion Test, Section 18 Deformation Test (Thermoplastics and Class XL Only), Section 19. Flexibility Test, Section. 21. Heat Shock Test (Thermoplastic Materials Only), Section 22. Cold Bend Test
copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
备案/许可证编号:苏ICP备17064731号-1