1、05-03M 21 05 12 - 1 SECTION 21 05 12 MOTOR REQUIREMENTS FOR FIRE-SUPPRESSION EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION: This section specifies the furnishing, installation and connection of motors for fire-suppression equipment. 1.2 RELATED WORK: A. Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INS
2、TALLATIONS: General electrical requirements that are common to more than one Section of Division 26. B. Section 26 29 11, LOW-VOLTAGE MOTOR STARTERS: Starters, control and protection for motors. C. Section 26 24 19, MOTOR-CONTROL CENTERS: Multiple motor control assemblies, which include motor starte
3、rs. D. Other sections specifying motor driven equipment in Division 21. 1.3 SUBMITTALS: A. In accordance with Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS, submit the following: B. Shop Drawings: 1. Sufficient information, clearly presented, shall be included to determine compliance w
4、ith drawings and specifications. 2. Include electrical ratings, dimensions, mounting details, materials, horsepower, RPM, enclosure, starting characteristics, torque characteristics, code letter, full load and locked rotor current, service factor, and lubrication method. C. Manuals: 1. Submit simult
5、aneously with the shop drawings, companion copies of complete maintenance and operating manuals, including technical data sheets and application data. D. Certification: Two weeks prior to final inspection, unless otherwise noted, submit four copies of the following certification to the Resident Engi
6、neer: 1. Certification that the motors have been properly applied, installed, adjusted, lubricated, and tested. 1.4 APPLICABLE PUBLICATIONS: A. Publications listed below (including amendments, addenda, revisions, supplements and errata) form a part of this specification to the extent referenced. Pub
7、lications are referenced in the text by designation only. B. National Electrical Manufacturers Association (NEMA): MG 1-98 Motors and Generators Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-05-03M 21 05 12 - 2 MG 2-01 Safety Standard and Guide for
8、 Selection, Installation and Use of Electric Motors and Generators C. National Fire Protection Association (NFPA): 70-02 National Electrical Code (NEC) PART 2 - PRODUCTS 2.1 MOTORS: A. For alternating current, fractional and integral horsepower motors, NEMA Publications MG 1 and MG 2 shall apply. B.
9、 Voltage ratings shall be as follows: 1. Single phase: a. Motors connected to 120-volt systems: 115 volts. b. Motors connected to 208-volt systems: 200 volts. c. Motors connected to 240 volt or 480 volt systems: 230/460 volts, dual connection. 2. Three phase: a. Motors connected to 208-volt systems:
10、 200 volts. b. Motors, less than 74.6 kW (100 HP), connected to 240 volt or 480 volt systems: 230/460 volts, dual connection. c. Motors, 74.6 kW (100 HP) or larger, connected to 240-volt systems: 230 volts. d. Motors, 74.6 kW (100 HP) or larger, connected to 480-volt systems: 460 volts. e. Motors co
11、nnected to high voltage systems: Shall conform to NEMA Standards for connection to the nominal system voltage shown on the drawings. C. Number of phases shall be as follows: 1. Motors, less than 373 W (1/2 HP): Single phase. 2. Motors, 373 W (1/2 HP) and larger: 3 phase. 3. Exceptions: a. Hermetical
12、ly sealed motors. b. Motors for equipment assemblies, less than 746 W (one HP), may be single phase provided the manufacturer of the proposed assemblies cannot supply the assemblies with three phase motors. D. Horsepower ratings shall be adequate for operating the connected loads continuously in the
13、 prevailing ambient temperatures in areas where the motors are installed, without exceeding the NEMA standard temperature rises for the motor insulation. E. Motor designs, as indicated by the NEMA code letters, shall be coordinated with the connected loads to assure adequate starting and running tor
14、que. Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-05-03M 21 05 12 - 3 F. Motor Enclosures: 1. Shall be the NEMA types shown on the drawings for the motors. 2. Where the types of motor enclosures are not shown on the drawings, they shall be the NEM
15、A types, which are most suitable for the environmental conditions where the motors are being installed. 3. Enclosures shall be primed and finish coated at the factory with manufacturers prime coat and standard finish. G. Additional requirements for specific motors, as indicated in other sections, sh
16、all also apply. H. Energy-Efficient Motors (Motor Efficiencies): All permanently wired polyphase motors of 746 Watts or more shall meet the minimum full-load efficiencies as indicated in the following table, and as specified in this specification. Motors of 746 Watts or more with open, drip-proof or
17、 totally enclosed fan-cooled enclosures shall be NEMA premium efficiency type, unless otherwise indicated. Motors provided as an integral part of motor driven equipment are excluded from this requirement if a minimum seasonal or overall efficiency requirement is indicated for that equipment by the p
18、rovisions of another section. Minimum Efficiencies Open Drip-Proof Minimum Efficiencies Totally Enclosed Fan-Cooled Rating kW (HP) 1200 RPM 1800 RPM 3600 RPM Rating kW (HP) 1200 RPM 1800 RPM 3600 RPM 0.746 (1) 82.5% 85.5% 77.0% 0.746 (1) 82.5% 85.5% 77.0% 1.12 (1.5) 86.5% 86.5% 84.0% 1.12 (1.5) 87.5
19、% 86.5% 84.0% 1.49 (2) 87.5% 86.5% 85.5% 1.49 (2) 88.5% 86.5% 85.5% 2.24 (3) 88.5% 89.5% 85.5% 2.24 (3) 89.5% 89.5% 86.5% 3.73 (5) 89.5% 89.5% 86.5% 3.73 (5) 89.5% 89.5% 88.5% 5.60 (7.5) 90.2% 91.0% 88.5% 5.60 (7.5) 91.0% 91.7% 89.5% 7.46 (10) 91.7% 91.7% 89.5% 7.46 (10) 91.0% 91.7% 90.2% 11.2 (15)
20、91.7% 93.0% 90.2% 11.2 (15) 91.7% 92.4% 91.0% 14.9 (20) 92.4% 93.0% 91.0% 14.9 (20) 91.7% 93.0% 91.0% 18.7 (25) 93.0% 93.6% 91.7% 18.7 (25) 93.0% 93.6% 91.7% 22.4 (30) 93.6% 94.1% 91.7% 22.4 (30) 93.0% 93.6% 91.7% 29.8 (40) 94.1% 94.1% 92.4% 29.8 (40) 94.1% 94.1% 92.4% 37.3 (50) 94.1% 94.5% 93.0% 37
21、.3 (50) 94.1% 94.5% 93.0% 44.8 (60) 94.5% 95.0% 93.6% 44.8 (60) 94.5% 95.0% 93.6% 56.9 (75) 94.5% 95.0% 93.6% 56.9 (75) 94.5% 95.4% 93.6% 74.6 (100) 95.0% 95.4% 93.6% 74.6 (100) 95.0% 95.4% 94.1% 93.3 (125) 95.0% 95.4% 94.1% 93.3 (125) 95.0% 95.4% 95.0% 112 (150) 95.4% 95.8% 94.1% 112 (150) 95.8% 95
22、.8% 95.0% Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-05-03M 21 05 12 - 4 149.2 (200) 95.4% 95.8% 95.0% 149.2 (200) 95.8% 96.2% 95.4% I. Minimum Power Factor at Full Load and Rated Voltage: 90 percent at 1200 RPM, 1800 RPM and 3600 RPM. J. Premiu
23、m efficiency motors shall be used where energy cost/kW x (hours use/year) 50. PART 3 - EXECUTION 3.1 INSTALLATION: Install motors in accordance with manufacturers recommendations, the NEC, NEMA, as shown on the drawings and/or as required by other sections of these specifications. 3.2 FIELD TESTS Megger all motors after installation, before start-up. All shall test free from grounds. - - - E N D - - - Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-