1、 TIA-526-14-C April 2015Optical Power Loss Measurement of Installed Multimode Fiber Cable Plant; Modification of IEC 61280-4-1 edition 2, Fiber-Optic Communications Subsystem Test Procedures- Part 4-1: Installed Cable Plant- Multimode Attenuation Measurement ANSI/TIA-526-14-C-2015 APPROVED: FEBRUARY
2、 26, 2015 NOTICE TIA Engineering Standards and Publications are designed to serve the public interest through eliminating misunderstandings between manufacturers and purchasers, facilitating interchangeability and improvement of products, and assisting the purchaser in selecting and obtaining with m
3、inimum delay the proper product for their particular need. The existence of such Standards and Publications shall not in any respect preclude any member or non-member of TIA from manufacturing or selling products not conforming to such Standards and Publications. Neither shall the existence of such
4、Standards and Publications preclude their voluntary use by Non-TIA members, either domestically or internationally. Standards and Publications are adopted by TIA in accordance with the American National Standards Institute (ANSI) patent policy. By such action, TIA does not assume any liability to an
5、y patent owner, nor does it assume any obligation whatever to parties adopting the Standard or Publication. This Standard does not purport to address all safety problems associated with its use or all applicable regulatory requirements. It is the responsibility of the user of this Standard to establ
6、ish appropriate safety and health practices and to determine the applicability of regulatory limitations before its use. Any use of trademarks in this document are for information purposes and do not constitute an endorsement by TIA or this committee of the products or services of the company. (From
7、 Project No. ANSI/TIA-PN-526.14-C-R1, formulated under the cognizance of the TIA TR-42 Telecommunications Cabling Systems, TR-42.11 Subcommittee on Optical Systems (568). Published by TELECOMMUNICATIONS INDUSTRY ASSOCIATION Technology and Standards Department 1320 N. Courthouse Road, Suite 200 Arlin
8、gton, VA 22201 U.S.A. PRICE: Please refer to current Catalog of TIA TELECOMMUNICATIONS INDUSTRY ASSOCIATION STANDARDS AND ENGINEERING PUBLICATIONS or call IHS, USA and Canada (1-877-413-5187) International (303-397-2896) or search online at http:/www.tiaonline.org/standards/catalog/ All rights reser
9、ved Printed in U.S.A. NOTICE OF COPYRIGHT This document is copyrighted by the TIA. Reproduction of these documents either in hard copy or soft copy (including posting on the web) is prohibited without copyright permission. For copyright permission to reproduce portions of this document, please conta
10、ct the TIA Standards Department or go to the TIA website (www.tiaonline.org) for details on how to request permission. Details are located at: http:/www.tiaonline.org/standards/catalog/info.cfm#copyright or Telecommunications Industry Association Technology (b) there is no assurance that the Documen
11、t will be approved by any Committee of TIA or any other body in its present or any other form; (c) the Document may be amended, modified or changed in the standards development or any editing process. The use or practice of contents of this Document may involve the use of intellectual property right
12、s (“IPR”), including pending or issued patents, or copyrights, owned by one or more parties. TIA makes no search or investigation for IPR. When IPR consisting of patents and published pending patent applications are claimed and called to TIAs attention, a statement from the holder thereof is request
13、ed, all in accordance with the Manual. TIA takes no position with reference to, and disclaims any obligation to investigate or inquire into, the scope or validity of any claims of IPR. TIA will neither be a party to discussions of any licensing terms or conditions, which are instead left to the part
14、ies involved, nor will TIA opine or judge whether proposed licensing terms or conditions are reasonable or non-discriminatory. TIA does not warrant or represent that procedures or practices suggested or provided in the Manual have been complied with as respects the Document or its contents. If the D
15、ocument contains one or more Normative References to a document published by another organization (“other SSO”) engaged in the formulation, development or publication of standards (whether designated as a standard, specification, recommendation or otherwise), whether such reference consists of manda
16、tory, alternate or optional elements (as defined in the TIA Procedures for American National Standards) then (i) TIA disclaims any duty or obligation to search or investigate the records of any other SSO for IPR or letters of assurance relating to any such Normative Reference; (ii) TIAs policy of en
17、couragement of voluntary disclosure (see TIA Procedures for American National Standards Annex C.1.2.3) of Essential Patent(s) and published pending patent applications shall apply; and (iii) Information as to claims of IPR in the records or publications of the other SSO shall not constitute identifi
18、cation to TIA of a claim of Essential Patent(s) or published pending patent applications. TIA does not enforce or monitor compliance with the contents of the Document. TIA does not certify, inspect, test or otherwise investigate products, designs or services or any claims of compliance with the cont
19、ents of the Document. ALL WARRANTIES, EXPRESS OR IMPLIED, ARE DISCLAIMED, INCLUDING WITHOUT LIMITATION, ANY AND ALL WARRANTIES CONCERNING THE ACCURACY OF THE CONTENTS, ITS FITNESS OR APPROPRIATENESS FOR A PARTICULAR PURPOSE OR USE, ITS MERCHANTABILITY AND ITS NONINFRINGEMENT OF ANY THIRD PARTYS INTE
20、LLECTUAL PROPERTY RIGHTS. TIA EXPRESSLY DISCLAIMS ANY AND ALL RESPONSIBILITIES FOR THE ACCURACY OF THE CONTENTS AND MAKES NO REPRESENTATIONS OR WARRANTIES REGARDING THE CONTENTS COMPLIANCE WITH ANY APPLICABLE STATUTE, RULE OR REGULATION, OR THE SAFETY OR HEALTH EFFECTS OF THE CONTENTS OR ANY PRODUCT
21、 OR SERVICE REFERRED TO IN THE DOCUMENT OR PRODUCED OR RENDERED TO COMPLY WITH THE CONTENTS. TIA SHALL NOT BE LIABLE FOR ANY AND ALL DAMAGES, DIRECT OR INDIRECT, ARISING FROM OR RELATING TO ANY USE OF THE CONTENTS CONTAINED HEREIN, INCLUDING WITHOUT LIMITATION ANY AND ALL INDIRECT, SPECIAL, INCIDENT
22、AL OR CONSEQUENTIAL DAMAGES (INCLUDING DAMAGES FOR LOSS OF BUSINESS, LOSS OF PROFITS, LITIGATION, OR THE LIKE), WHETHER BASED UPON BREACH OF CONTRACT, BREACH OF WARRANTY, TORT (INCLUDING NEGLIGENCE), PRODUCT LIABILITY OR OTHERWISE, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. THE FOREGOING NE
23、GATION OF DAMAGES IS A FUNDAMENTAL ELEMENT OF THE USE OF THE CONTENTS HEREOF, AND THESE CONTENTS WOULD NOT BE PUBLISHED BY TIA WITHOUT SUCH LIMITATIONS. i ANSI/TIA Foreword International Standard IEC 61280-4-1 Ed. 2.0 has been prepared by subcommittee 86C: Fibre optic systems and active devices, of
24、IEC technical committee 86: Fibre optics. TIA previously adopted the IEC document as ANSI/TIA-526-14-B (a.k.a. OFSTP-14-B) and in so doing added a foreword. That foreword included clarification on major changes between earlier versions of the TIA document and this version including the nomenclature
25、for the three reference methods and text to describe additional encircled flux launch condition uncertainty not previously considered in the IEC document. This document, ANSI/TIA-526-14-C, changes the nature of the document from an adoption to an adaption because it includes variances from the IEC s
26、tandard. Material within the previous foreword is retained and augmented with new material that defines the variances. The variances are modifications of the requirements on the encircled flux launch condition with regard to its normative usage for measuring the attenuation of installed multimode fi
27、ber cabling. The new material can be found in the last section of this ANSI/TIA Foreword under the heading “Variance from IEC standard”. Reference methods nomenclature The different ways in which reference measurements can be made of the power input to the cabling under test are explicitly referred
28、to in the IEC document by the number of test cords that are used in the reference configuration. In the TIA document these were often referenced as configuration A, B or C. A cross reference of these test methods is shown in Table Foreword.1. Table Foreword.1 Measurement method cross reference IEC 6
29、1280-4-1 Ed. 2.0 OFSTP-14-A Name Location Name One-cord reference method Annex A Method B Three-cord reference method Annex B Method C Two-cord reference method Annex C Method A OTDR testing OTDR testing was not in the original OFSTP-14-A. The use of the OTDR for measuring attenuation is described i
30、n Annex D for total attenuation with additional guidance in Annex G including measuring individual component losses. Inspecting and cleaning connectors The IEC document highlights the importance of, and gives guidance on, good measurement practices including inspection and cleaning of connector end
31、faces. Clean connector end faces are required prior to mating connectors. End-face inspection can be used to verify cleanliness as well as for troubleshooting. Test cord insertion loss verification Annex H describes procedures for checking the insertion loss of test cords that should be performed be
32、fore undertaking cable plant measurements, as poorly performing test cords invalidate measurements made with them. The procedures are delineated by the reference measurement method and by the type of connector system. Reference grade connectors This document recommends the use of reference grade con
33、nections on test cords to reduce measurement uncertainty. This means that there is now a difference between the test result acceptance criteria and the expected link or channel insertion loss in its final configuration. The insertion loss acceptance criteria should be tightened up accordingly. Encir
34、cled flux The requirement for the modal launch conditions for the sources used to measure multimode fibers is changed from one based on coupled power ratio (CPR) and mandrel requirements to one based on measurements of the near field at the output of the launching test cord. The launch condition mus
35、t now meet the requirements of the specified encircled flux template. Compliance provides significant improvement in measurement repeatability. For information on implementation of encircled flux launch conditions for field measurements refer to TIA TSB-4979. Within TSB-4979 the term used for device
36、s that create an EF launch condition is controller (universal or matched). IEC 61280-4-1 calls these devices conditioners. Note that the encircled flux template example of Figure E.1 unintentionally shows incomplete Target and OFL lines. The red Target line should run continuously thru the center of
37、 the shaded Template region, and the blue OFL line should be continuous thru the region from 11 to 15 m radius. ii Encircled flux uncertainty For field test equipment using a single optical port that launches two wavelengths, a test cord that is conditioned by a mandrel may not allow an alignment on
38、 the target for both wavelengths simultaneously. Should this be the case, the use of the same mandrel for both wavelengths will reduce the margin for compliance within the templates and add uncertainty. Due to the effect of variations in source wavelength, mode controller, temperature changes, other
39、 physical variations, and the measurement equipment itself, launch conditions at the time of factory calibration will not be identical in the field should any variable change. The use of attenuation artifacts described in IEC 61280-4-1 can help ensure that the equipment produces a launch condition t
40、hat performs acceptably. Alignment of encircled flux targets to eliminate wavelength bias Efforts were taken to harmonize the expected component losses at 850 nm and 1300 nm wavelengths for a given fiber core diameter. This was accomplished by adjustment of the 850 nm and 1300 nm EF targets to produ
41、ce comparable extrinsic component losses. An example of matching the attenuation characteristics at the two wavelengths is illustrated in Figure Foreword.1. This elimination of bias provides an opportunity to ensure dual wavelength compliance of a passive component or a short cable plant link using
42、a single source. This alignment is true for traditional multimode fiber. It is not known to apply to macrobend-loss-reduced (a.k.a. “bend insensitive” ) multimode fiber. Figure Foreword.1 Calculated Wavelength Comparison Other references The following references document the foundational work underl
43、ying the development of the encircled flux launch condition specifications and can be obtained at the following internet location: http:/ftp.tiaonline.org/TR-42/TR-42.11/Public/TSB-178ReferenceRepository 1) T. Hanson, “Considerations on multimode link loss”, December 13, 2005 2) T. Hanson, “Consider
44、ations regarding the target RPD, coupled power, and steady state”, July 13, 2006 3) R. Conte, “Mode Scattering and Steady State Distributions”, August 18, 2006 4) R. Conte, “A Template Based Approach to Source Qualification”, August 18, 2006 5) T. Hanson and J. Luther, “Multimode source boundary exp
45、eriment”, October, 2006 6) R. Conte, “CPR, MPD, and EF”, December 5, 2006 iii Variance from IEC standard Annex E of IEC 61280-4-1 Ed. 2.0 normatively defines encircled flux launch conditions for four cases: 1. measurements of installed 50 m core fiber cabling at 850 nm, 2. measurements of installed
46、50 m core fiber cabling at 1300 nm, 3. measurements of installed 62.5 m core fiber cabling at 850 nm, 4. measurements of installed 62.5 m core fiber cabling at 1300 nm. ANSI/TIA-526-14-C applies only case 1 normatively. For the other three cases the encircled flux launch conditions are informative.
47、However the use of encircled flux launch conditions for cases 2, 3 and 4 is recommended, especially for applications providing channel loss budgets less than 3 dB1. For cases 2, 3 and 4, when the launch condition is not known to be encircled flux compliant, the source shall be qualified using the fo
48、llowing High Order Mode Loss (HOML) test. This test can be readily created in the field to gauge and adjust launch conditions through a reference-grade launch cord, but attenuation measurements from sources qualified by the HOML test will have greater uncertainty due to launch variation than attenua
49、tion measurements made with encircled flux launch conditions. HOML qualified launch conditions are not a substitute for encircled flux compliant launch conditions. The HOML qualification of the source and launch cord combination involves the use of a launch cord with and without applied mandrel wrap prescriptions. The launch cord shall be 2 m to 5 m in length and shall contain fiber of the same nominal core diameter and numerical aperture as the cable plant to be measured. The fiber within the launch cord shall not provide macrobend-loss-reduced properties (a.k.a. “ben