1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL UL 1650 Portable Power Cable STANDARD FOR SAFETYUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM ULUL COPYRIGHTED MATERIAL NOT AUTHORIZED
2、FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL UL Standard for Safety for Portable Power Cable, UL 1650 First Edition, Dated January 28, 2015 Summary of Topics This revision to ANSI/UL 1650 corrects tensile strength values for TPE Jacket in Table 8.3. The revised requirements ar
3、e substantially in accordance with Proposal(s) on this subject dated January 29, 2016. Text that has been changed in any manner or impacted by ULs electronic publishing system is marked with a vertical line in the margin. All rights reserved. No part of this publication may be reproduced, stored in
4、a retrieval system, or transmitted in any form by any means, electronic, mechanical photocopying, recording, or otherwise without prior permission of UL. UL provides this Standard as is without warranty of any kind, either expressed or implied, including but not limited to, the implied warranties of
5、 merchantability or tness for any purpose. In no event will UL be liable for any special, incidental, consequential, indirect or similar damages, including loss of prots, lost savings, loss of data, or any other damages arising out of the use of or the inability to use this Standard, even if UL or a
6、n authorized UL representative has been advised of the possibility of such damage. In no event shall ULs liability for any damage ever exceed the price paid for this Standard, regardless of the form of the claim. Users of the electronic versions of ULs Standards for Safety agree to defend, indemnify
7、, and hold UL harmless from and against any loss, expense, liability, damage, claim, or judgment (including reasonable attorneys fees) resulting from any error or deviation introduced while purchaser is storing an electronic Standard on the purchasers computer system. APRIL 1, 2016 UL 1650 tr1UL COP
8、YRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL APRIL 1, 2016 UL 1650 tr2 No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL January 28, 2015 (Title Page Reprinted: April
9、1, 2016) 1 UL 1650 Standard for Portable Power Cable Prior to the rst edition, the requirements for the products covered by this standard were included in the Outline of Investigation for Portable Power Cable, UL 1650. First Edition January 28, 2015 This ANSI/UL Standard for Safety consists of the F
10、irst Edition including revisions through April 1, 2016. The most recent designation of ANSI/UL 1650 as an American National Standard (ANSI) occurred on April 1, 2016. ANSI approval for a standard does not include the Cover Page, Transmittal Pages, or Title Page. Comments or proposals for revisions o
11、n any part of the Standard may be submitted to UL at any time. Proposals should be submitted via a Proposal Request in ULs On-Line Collaborative Standards Development System (CSDS) at http:/. ULs Standards for Safety are copyrighted by UL. Neither a printed nor electronic copy of a Standard should b
12、e altered in any way. All of ULs Standards and all copyrights, ownerships, and rights regarding those Standards shall remain the sole and exclusive property of UL. COPYRIGHT 2016 UNDERWRITERS LABORATORIES INC. ANSI/UL 1650-2016UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRI
13、BUTION WITHOUT PERMISSION FROM UL JANUARY 28, 2015 PORTABLE POWER CABLE - UL 1650 2 No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL CONTENTS INTRODUCTION 1 Scope .5 1.1 General 5 2 Units of Measurement .5 3 Undated Refere
14、nces 5 4 Glossary .5 CONSTRUCTION 5 General 5 6 Conductors 6 6.1 General 6 6.2 Coated copper conductors .6 6.3 Uncoated copper conductors .6 7 Conductor Assembly 7 7.1 General 7 7.2 Strands .7 7.3 Length and direction of lay .7 7.4 Grounding conductor 8 7.5 Insulation .10 7.6 Covering .11 7.7 Overal
15、l assembly 11 7.8 Jacket .11 TEST PROGRAM 8 Performance and Test Requirements .13 8.1 General .13 8.2 Physical properties 14 8.3 Copper corrosion 15 8.4 Cold bend 16 8.5 Jacket resistance 17 8.6 Horizontal ame test FT2 .17 8.7 Vertical ame test FT1 .17 8.8 Flame resistance of electrical cables .17 8
16、.9 Dielectric strength for all nished types .17 8.10 Insulation resistance 18 8.11 Durability of ink printing .19 8.12 Capacitance and relative permittivity 19 8.13 Long-term insulation resistance in water 20 8.14 Weather resistance cables marked sunlight resistant 22 8.15 Swelling and blistering of
17、 thermoset jackets Types W, G, G-GC marked sunlight resistant .22 8.16 Heat-shock resistance 23 8.17 Deformation Type PPE only .25 MANUFACTURING AND PRODUCTION TESTS 9 Spark Test 25 JANUARY 28, 2015 PORTABLE POWER CABLE - UL 1650 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DI
18、STRIBUTION WITHOUT PERMISSION FROM UL 10 Dielectric Withstand .26 10.1 General .26 10.2 Insulation resistance 26 MARKINGS 11 Surface Markings .27 12 Package Markings 27 JANUARY 28, 2015 PORTABLE POWER CABLE - UL 1650 4UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WI
19、THOUT PERMISSION FROM UL INTRODUCTION 1 Scope 1.1 General 1.1.1 This Standard species the requirements for Portable Power Cables for use in accordance with the National Electrical Code, NFPA 70. 1.1.2 Any references to UL 2556, refer to the Standard for Wire and Cable Test Methods, UL 2556. 2 Units
20、of Measurement 2.1 The values stated without parentheses are the requirements. Values in parentheses are explanatory or approximate information. 3 Undated References 3.1 Any undated reference to a code or standard appearing in the requirements of this standard shall be interpreted as referring to th
21、e latest edition of that code or standard. 4 Glossary 4.1 For the purpose of this standard the following denitions apply: 4.2 GROUND-CHECK CONDUCTOR A conductor used in cables to monitor the continuity of the grounding circuit, so that a discontinuity or open in the grounding circuit causes the powe
22、r conductors to be de-energized. 4.3 PORTABLE POWER CABLE Cable used to supply power to mobile equipment and machinery. 4.4 XL A thermoset compound whose characteristic constituent is cross-linked polyethylene (XLPE), cross-linked polyvinyl chloride (XLPVC), cross-linked ethylene vinyl acetate (XLEV
23、A), or blends thereof. CONSTRUCTION 5 General 5.1 Portable power cables consist of either a single insulated conductor or two or more insulated circuit conductors with or without grounding conductors with an overall reinforced jacket. They employ exible stranded copper conductors in a size range of
24、12 AWG to 500 kcmil (3.31 253 mm 2 ), except for single conductor Type W that employs exible stranded copper conductors in sizes 12 AWG to 1000 kcmil (3.31 507 mm 2 ). This cable is rated 2000 V, 75C (167F) or 90C (194F) dry, and 60C (140F) or 75C (167F) where exposed to oil. For cable so marked, ra
25、tings of 60C (140F), 75C (167F), or 90C (194F) wet are also assigned. The term wet indicates that the cable is acceptable for immersion in water. Wet rated cable that has been additionally investigated for use where exposed to the direct rays of the sun is marked Sunlight Resistant or Sun Res. JANUA
26、RY 28, 2015 PORTABLE POWER CABLE - UL 1650 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL 5.2 Portable power cables shall consist of the following circuit, grounding and ground-check conductors: a) Type G Contains two to six circuit conduc
27、tors and a grounding conductor. The grounding conductor is either bare or covered with a green-colored braid or tape or extruded layer, and may either be a single conductor or be sectioned into two or more parts. b) Type G-GC Same as Type G except that the cable also contains one 12 AWG (3.31 mm 2 )
28、 or larger, yellow insulated conductor which is used as a ground check. c) Type W Contains one to six circuit conductors and may or may not contain a grounding conductor in cables with three or more conductors. If included, the grounding conductor is fully insulated and colored green. d) Type PPE Co
29、ntains one to six circuit conductors and may or may not contain a grounding conductor in cables with three or more conductors. If included, the grounding conductor is fully insulated and colored green. 6 Conductors 6.1 General 6.1.1 The circuit conductors shall be annealed, stranded copper, bare, or
30、 tin-coated. 6.2 Coated copper conductors 6.2.1 Each tin-coated conductor shall comply with the requirements of the Standard Specication for Tin-Coated Soft or Annealed Copper Wire for Electrical Purposes, ASTM B33. 6.2.2 A tin coating is appropriate for use on individual wires (strands) or selected
31、 wires, such as the outer layer of wires of a stranded conductor. The tin coating shall comply with 6.2.1. 6.3 Uncoated copper conductors 6.3.1 Each wire in an uncoated copper conductor shall comply with the requirements of Standard Specication for Soft or Annealed Copper Wire, ASTM B3. JANUARY 28,
32、2015 PORTABLE POWER CABLE - UL 1650 6UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL 7 Conductor Assembly 7.1 General 7.1.1 Conductors shall be of an assembly indicated in Table 7.1. Table 7.1 Conductor Assembly Conductor size range Assembly
33、 AWG or kcmil (mm 2 ) 12 1000 (3.31 507) Concentric rope lay and rope lay 12 9 (3.31 6.63) Combination unilay 12 3 (3.31 26.7) Concentric, compressed, bunched 7.2 Strands 7.2.1 Copper strands smaller than 36 AWG (0.0127 mm 2 ) shall not be used. Circuit and grounding conductors 12 9 AWG (3.31 6.63 m
34、m 2 ) shall contain a minimum of 19 strands;83A W G(8.37 26.7 mm 2 ) circuit conductors shall contain a minimum of 49 strands; 2 AWG 2/0 (33.6 67.4 mm 2 ) shall contain a minimum of 133 strands; and 3/0 1000 kcmil (85 507 mm 2 ) shall contain a minimum 259 strands. 7.3 Length and direction of lay 7.
35、3.1 Every stranded conductor or a bunch-stranded conductor twisted as a single bunch, shall comply with the following: a) Rope-lay conductors in a 12 AWG 1000 kcmil (3.31 507 mm 2 ) conductor with bunch- stranded or concentric-stranded members shall be either unidirectional or reversed. All unidirec
36、tional lays and the outer layer of reversed lays shall be in the left-hand direction. b) For a bunch-stranded member of a rope-lay-stranded conductor in which the members are formed into rope-stranded components that are then cabled into the nal conductor, the length of lay of the individual members
37、 within each component shall not be more than 30 times the outside diameter of one of those members. c) For a concentric-stranded member of a rope-lay-stranded conductor, the length of lay of the individual strands in a member shall be81 6times the outside diameter of the member. The direction of la
38、y of the strands in each member shall be reversed in successive layers of the member. d) The length of lay of the strands in both layers of a 19-wire combination round-wire unilay- stranded copper conductor shall be81 6times the outside diameter of the completed conductor. Otherwise, the length of l
39、ay of the strands in every layer of a concentric-lay-stranded conductor consisting of fewer than 37 strands shall be81 6times the outside diameter of the conductor. e) The length of lay of the strands in the outer two layers of a concentric-lay-stranded conductor consisting of 37 or more strands sha
40、ll be81 6times the outside diameter of the conductor. JANUARY 28, 2015 PORTABLE POWER CABLE - UL 1650 7UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL f) The length of lay of the outer layer of a rope-lay-stranded conductor shall be81 6times
41、 the outside diameter of that layer. 7.3.2 For bunch-stranded conductors, simple bunching (untwisted strands) shall not be used. The length of lay of the strands in a bunch-stranded conductor twisted as a single bunch shall not be greater than indicated in Table 7.2. The direction of lay of the stra
42、nds in a bunch-stranded conductor shall be left-hand. Table 7.2 Length of Lay of Strands in a Bunch-Stranded Conductor Twisted as a Single Bunch a Size of conductor Maximum acceptable length of lay AWG (mm 2 ) inches (mm) 2.08 (14) 1.75 (44) 3.31 (12) 2.00 (51) 5.26 (10) 2.50 (64) 8.37 (8) 2.75 (70)
43、 13.3 (6) 3.38 (86) Larger than 13.3 (6) 16 times the conductor diameter 7.4 Grounding conductor 7.4.1 The grounding conductor where used, may be a single conductor or may be sectioned into two or more equal parts. The grounding conductor for Types W and PPE shall be the same size as the circuit con
44、ductors. The grounding conductor for Types G and G-GC shall be sized in accordance with Tables 7.3 7.6. If standard AWG sizes are not used for the grounding conductor, the grounding conductor shall be at least 60 percent of the size of the largest circuit conductor. The total circular mil area of a
45、sectioned grounding conductor shall be equal to or greater than that of the corresponding size of a single conductor. Table 7.3 Grounding conductors for Type G, round construction 2 conductor 3 conductor 4 conductor 5 conductor 6 conductor Circuit conductor size, AWG (mm 2 ) or kcmil Size of section
46、ed grounding conductors, AWG (mm 2 ) Size of sectioned grounding conductors, AWG (mm 2 ) Size of sectioned grounding conductors, AWG (mm 2 ) Size of central grounding conductor, AWG (mm 2 ) Size of central grounding conductor, AWG (mm 2 ) 12 (3.31) 14 (2.08) 14 (2.08) 14 (2.08) 12 (3.31) 12 (3.31) 1
47、0 (5.26) 12 (3.31) 12 (3.31) 12 (3.31) 10 (5.26) 10 (5.26) 8 (8.37) 10 (5.26) 10 (5.26) 12 (3.31) 8 (8.37) 8 (8.37) 6 (13.3) 10 (5.26) 10 (5.26) 12 (3.31) 7 (10.6) 7 (10.6) 4 (21.2) 8 (8.37) 8 (8.37) 10 (5.26) 6 (13.3) 6 (13.3) 3 (26.7) 6 (13.3) 8 (8.37) 10 (5.26) 5 (16.8) 5 (16.8) 2 (33.6) 6 (13.3)
48、 8 (8.37) 9 (6.63) 4 (21.2) 4 (21.2) 1 (42.4) 5 (16.8) 7 (10.6) 8 (8.37) 3 (26.7) 3 (26.7) 1/0 (53.5) 4 (21.2) 6 (13.3) 7 (10.6) 2 (33.6) 2 (33.6) 2/0 (67.4) 3 (26.7) 5 (16.8) 6 (13.3) 1 (42.4) 1 (42.4) 3/0 (85.0) 2 (33.6) 4 (21.2) 5 (16.8) 1/0 (53.5) 1/0 (53.5) 4/0 (107.2) 1 (42.4) 3 (26.7) 4 (21.2
49、) 2/0 (67.4) 2/0 (67.4) 250 (127) 1/0 (53.5) 2 (33.6) 3 (26.7) 3/0 (85.0) 3/0 (85.0) 300 (152) 1/0 (53.5) 1 (42.4) 3 (26.7) 4/0 (107.2) 4/0 (107.2) 350 (177) 2/0 (67.4) 1 (42.4) 2 (33.6) 250 (127) 250 (127) 400 (203) 3/0 (85.0) 1/0 (53.5) 1 (42.4) 250 (127) 250 (127) JANUARY 28, 2015 PORTABLE POWER CABLE - UL 1650 8 Table 7.3 Continued on Next PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT