1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL UL 183 Manufactured Wiring Systems STANDARD FOR SAFETYUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM ULUL COPYRIGHTED MATERIAL NOT AUTHO
2、RIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL UL Standard for Safety for Manufactured Wiring Systems, UL 183 Fourth Edition, Dated September 22, 2009 Summary of Topics This revision to ANSI/UL 183 is being issued for the following requirements: Changes in requirements for
3、 MC-PCS cables with non Class 2 power conductors The revised requirements are substantially in accordance with Proposal(s) on this subject dated March 4, 2016. Text that has been changed in any manner or impacted by ULs electronic publishing system is marked with a vertical line in the margin. All r
4、ights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form by any means, electronic, mechanical photocopying, recording, or otherwise without prior permission of UL. UL provides this Standard as is without warranty of any kind, either expr
5、essed or implied, including but not limited to, the implied warranties of merchantability or tness for any purpose. In no event will UL be liable for any special, incidental, consequential, indirect or similar damages, including loss of prots, lost savings, loss of data, or any other damages arising
6、 out of the use of or the inability to use this Standard, even if UL or an authorized UL representative has been advised of the possibility of such damage. In no event shall ULs liability for any damage ever exceed the price paid for this Standard, regardless of the form of the claim. Users of the e
7、lectronic versions of ULs Standards for Safety agree to defend, indemnify, and hold UL harmless from and against any loss, expense, liability, damage, claim, or judgment (including reasonable attorneys fees) resulting from any error or deviation introduced while purchaser is storing an electronic St
8、andard on the purchasers computer system. MAY 6, 2016 UL 183 tr1UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL MAY 6, 2016 UL 183 tr2 No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOU
9、T PERMISSION FROM UL SEPTEMBER 22, 2009 (Title Page Reprinted: May 6, 2016) 1 UL 183 Standard for Manufactured Wiring Systems First Edition October, 1984 Second Edition August, 1993 Third Edition October, 2003 Fourth Edition September 22, 2009 This ANSI/UL Standard for Safety consists of the Fourth
10、Edition including revisions through May 6, 2016. The most recent designation of ANSI/UL 183 as an American National Standard (ANSI) occurred on May 6, 2016. ANSI approval for a standard does not include the Cover Page, Transmittal Pages, Title Page, or effective date information. Comments or proposa
11、ls for revisions on any part of the Standard may be submitted to UL at any time. Proposals should be submitted via a Proposal Request in ULs On-Line Collaborative Standards Development System (CSDS) at http:/. ULs Standards for Safety are copyrighted by UL. Neither a printed nor electronic copy of a
12、 Standard should be altered in any way. All of ULs Standards and all copyrights, ownerships, and rights regarding those Standards shall remain the sole and exclusive property of UL. COPYRIGHT 2016 UNDERWRITERS LABORATORIES INC. ANSI/UL 183-2016UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRO
13、DUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL MAY 6, 2016 MANUFACTURED WIRING SYSTEMS - UL 183 2 No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL CONTENTS INTRODUCTION 1 Scope .5 2 Glossary .5 3 Components 6A 4 Units
14、of Measurement 6B 5 Undated References .6B CONSTRUCTION 6 General 6B 7 Connecting Cable and Flexible Metal Conduit .6B 8 Continuous Plug-in Busway 9 9 Knockouts 9 10 Connecting Flexible Cord .9 11 Mechanical Assembly and Enclosure 11 12 Enclosures of Polymeric Material 12B 13 Protection Against Corr
15、osion 12B 14 Field Wiring .12B 15 Internal Wiring 15 15A Low Voltage Charging Circuits 16 16 Receptacle Wiring 16 16A Conductor Fill Requirements 16A 17 Control Circuits 16B 17A Supplementary Protectors .16B 18 Laser Devices 16C 19 Splices and Connections .16D 20 Grounding 16D 21 Bonding .17 22 Mati
16、ng Connectors 18 22A Mating Connectors 18 22A.1 General 18 22A.2 Flammability 18 22A.3 Electrical properties .19 22A.4 Thermal properties 19 22A.5 Mating connector physical requirements .20 22A.6 Mating connectors for use in environmental air handling spaces (plenums) 21 23 Strain Relief 21 24 Flexi
17、ble Cord Strain Relief .21 25 Spacings 22 25A Spacings .22 26 Accessibility to Uninsulated Live Parts .22A PERFORMANCE 27 Temperature Test .22A 27A Temperature Cycling Test 23 28 Aging/Creep Test .24 29 Aging/Penetration Test 25 30 Vibration Test 26 MAY 6, 2016 MANUFACTURED WIRING SYSTEMS - UL 183 3
18、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL 31 Push-Back Relief Test .26 32 Pull-Out Test 27 33 Strain Relief Test 27 34 Overload Test 28 35 Fault Current Test .29 36 Internal Conductor Overcurrent Test .30 37 Conductor-Secureness Test 3
19、1 38 Grounding Impedance Test .31 38.1 General .31 38.2 Grounding or bonding ttings 32 39 Dielectric Voltage-Withstand Test .33 40 Outdoor Use Performance 33 41 Knockout Test 34 42 Cap Separation Test .34 MANUFACTURING AND PRODUCTION TESTS 43 Grounding-Continuity Test .34 44 Dielectric Voltage-Withs
20、tand Test 35 44.1 General .35 44.2 Test equipment 35 MARKING 45 Details .36 INSTRUCTIONS 46 Installation and Operating Instructions .39 SUPPLEMENT SA - MANUFACTURED WIRING SYSTEMS FOR USE IN PATIENT CARE AREAS SA1 Scope SA1 SA2 Construction .SA1 SA3 Performance .SA2 SA4 Markings .SA3 SA5 Installatio
21、n Instructions SA3 APPENDIX A Standards for ComponentsA1 MARCH 27, 2015 MANUFACTURED WIRING SYSTEMS - UL 183 4UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL INTRODUCTION 1 Scope 1.1 These requirements cover wiring systems for use in outdoor
22、 locations, eld-installed wiring assemblies using off-site manufactured subassemblies for branch circuits, remote-control circuits, signaling circuits, and communication circuits in accessible areas. The products covered under this standard are to be installed in accordance with Article 604 of the N
23、ational Electrical Code, ANSI/NFPA 70. 2 Glossary 2.1 For the purposes of this standard the following denitions apply. 2.2 ACCESSIBLE PART A part that is: a) Located so that it can be contacted by a person; or b) Not recessed the required distance behind an opening. 2.3 BRANCH CIRCUIT The circuit co
24、nductors between the nal over-current device protecting the circuit and the outlet(s). 2.4 BRANCH CIRCUIT, MULTIWIRE A branch circuit that consists of two or more ungrounded conductors that have a voltage between them, and a grounded conductor that has equal voltage between it and each ungrounded co
25、nductor of the circuit, and that is connected to the neutral or grounded conductor of the system. 2.5 CLASS 2 CIRCUIT An isolated secondary circuit involving a potential of not more than 30-volt rms maximum 42.4 volts peak open circuit secondary potential under any condition of loading or open circu
26、it by: a) An inherently-limited Class 2 transformer; b) A combination of an isolated transformer secondary winding and a xed impedance or regulating network that together comply with the performance requirements for an inherently- limited Class 2 transformer; c) A dry-cell battery having output char
27、acteristics not greater than those of an inherently-limited Class 2 transformer; d) Any combination of (a), (b), and (c) that together comply with the performance requirements for an inherently-limited Class 2 transformer; or e) One or more combinations of a Class 2 transformer and an overcurrent pr
28、otective device that together comply with the performance requirements for a noninherently-limited Class 2 transformer. A circuit derived from a line-connected circuit by connecting impedance in series with the supply circuit as a means of limiting the voltage and current is not considered to be a C
29、lass 2 circuit. SEPTEMBER 22, 2009 MANUFACTURED WIRING SYSTEMS - UL 183 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL 2.6 CONTINUOUS PLUG-IN BUSWAY A continuous plug-in busway is rated at 600V, 40 Amperes or less, has no exposed bus bars,
30、 and is intended for general use, including installation within the reach of persons. 2.7 ENCLOSURE A housing which provides a degree of protection against contacting live parts (i.e., connector, conductors, and contacts). The enclosures are constructed of metal, polymeric material, or hybrid (combi
31、nation of metal and polymer). 2.8 ENCLOSURE, ENVIRONMENTAL The portion or portions of a device intended to provide a degree of protection to the contacts, blades, terminals, conductors, and other live parts of the device and of any adjoining devices or components comprising a complete protective sys
32、tem against outdoor conditions, both when the device is unmated and when it is fully connected to its intended mating device. 2.9 FITTING A means of securing conduit, cable, or raceway to an enclosure or box. 2.10 INSULATION, BASIC The insulation necessary for the intended functioning of the product
33、 and for basic protection against the risk of electric shock. 2.11 INSULATION, SUPPLEMENTARY An independent insulation provided in addition to the basic insulation to reduce the risk of electric shock in case of breakdown of the basic insulation. 2.12 LIMITED POWER SOURCE (LPS) A limited power sourc
34、e is as specied in the Standard for Information Technology Equipment Safety Part 1: General Requirements, UL 60950-1, and shall comply with the requirements of UL 60950-1. 2.13 LOW-VOLTAGE CIRCUIT A circuit involving a potential of not more than 30 volts dc or ac rms (42.4 volts ac peak). 2.14 MANUF
35、ACTURED WIRING SYSTEM CONNECTOR A device consisting of an electrical and mechanical enclosure, multi-pole electrical contacts and provided in either a male or female locking conguration for connection to a like congured connector. 2.15 MULTI-POLE SPLICING WIRE CONNECTOR An insulated multi-pole matin
36、g or non-mating connector intended for factory wiring or eld wiring contained in an outlet box, junction box, or within an equipment enclosure. Used to connect two or more branch-circuit conductors. 2.16 RACEWAY A completely enclosed channel intended specically for holding and routing wiring and pro
37、viding separation of: a) Power and lighting circuits; and b) Power-limited or communication circuits. 2.17 RISK OF ELECTRIC SHOCK A risk of electric shock is considered to exist in any accessible connective part of a system if a potential greater than 42.4 volts peak (30 volts rms) exists, and the a
38、vailable current is more than 5 milliamperes (7.07 mA peak) through a 1500-ohm resistor connected between: a) The part and other accessible connective parts; or b) Between the part and ground. MAY 6, 2016 MANUFACTURED WIRING SYSTEMS - UL 183 6UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPROD
39、UCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL 2.18 RISK OF FIRE A risk of re is considered to exist in any branch-circuit-connected component part or assembly. In addition, risk of a re is considered to exist in a component part or assembly if the power supply for such a part or assembly is capa
40、ble of delivering more than 15 watts into an external resistor connected between the point in question and any return to the supply. A power supply not capable of delivering more than 15 watts as previously mentioned, is considered to be energy limited. 2.19 SECONDARY CIRCUIT A circuit that is suppl
41、ied by an induced voltage from a primary, where a primary circuit is that supplied by a branch circuit. 2.20 SUPPLEMENTARY PROTECTOR A manually resettable device designed to open the circuit automatically on a predetermined value of time versus current or voltage. 3 Components 3.1 A component of a p
42、roduct covered by this standard shall comply with the requirements for that component, and shall be used in accordance with its recognized rating and other limitations of use. See Appendix A for a list of standards covering components used in the products covered by this standard. 3.2 Component rece
43、ptacles shall be used with conductors or leads in accordance with their recognized rating and other limitations of use in accordance with the Standard for Attachment Plugs and Receptacles, UL 498. 3.3 A component is not required to comply with a specic requirement that: a) Involves a feature or char
44、acteristic not required in the application of the component in the product covered by this standard, or b) Is superseded by a requirement in this standard. 3.4 A component shall be used in accordance with its rating established for the intended conditions of use. 3.5 Specic components are incomplete
45、 in construction features or restricted in performance capabilities. Such components are intended for use only under limited conditions, such as certain temperatures not exceeding specied limits, and shall be used only under those specic conditions. 3.6 Prefabricated oor boxes shall comply with the
46、Standard for Metallic Outlet Boxes, UL 514A, when used as a component of a manufactured wiring system. 3.7 Receptacle congurations constructed in accordance with Wiring Devices Dimensional Specications, ANSI/NEMA WD6 shall comply with the Standard for Attachment Plugs and Receptacles, UL 498. 3.7.1
47、Hospital grade convenience receptacles shall comply with the requirements for Hospital Grade Receptacles in the Standard for Attachment Plugs and Receptacles, UL 498. MAY 6, 2016 MANUFACTURED WIRING SYSTEMS - UL 183 6AUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WI
48、THOUT PERMISSION FROM UL 3.7.2 When hospital grade convenience receptacles are utilized in a manufactured wiring system that has not been evaluated for use in patient care areas in accordance with Supplement SA, the manufactured wiring system shall be provided with installation instructions and a ma
49、rking that specify that the manufactured wiring system is not intended for installation in patient care areas. Refer to 45.20 and 46.7. 3.8 Insulated multi-pole splicing wire connectors shall comply with the Standard for Insulated Multi-Pole Splicing Wire Connectors, UL 2459. 4 Units of Measurement 4.1 Values stated without parentheses are the requirement. Values in parentheses are explanatory or approximate information. 5 Undated References 5.1 Any undated reference to a