1、UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL UL 2515A Supplemental Requirements for Extra Heavy Wall Reinforced Thermosetting Resin Conduit (RTRC) and Fittings STANDARD FOR SAFETYUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUC
2、TION OR DISTRIBUTION WITHOUT PERMISSION FROM ULUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL UL Standard for Safety for Supplemental Requirements for Extra Heavy Wall Reinforced Thermosetting Resin Conduit (RTRC) and Fittings, UL 2515A Fir
3、st Edition, Dated November 21, 2011 Summary of Topics The following revisions to the Standard for Supplemental Requirements for Extra Heavy Wall Reinforced Thermosetting Resin Conduit (RTRC) and Fittings, UL 2515A, are being issued: 1. New Test Method to Determine if Extra Heavy Wall Aboveground RTR
4、C is Suitable for Use at Extended Support Distances as Permitted by the NEC Text that has been changed in any manner or impacted by ULs electronic publishing system is marked with a vertical line in the margin. The new and revised requirements are substantially in accordance with Proposal(s) on this
5、 subject dated December 4, 2015. All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted in any form by any means, electronic, mechanical photocopying, recording, or otherwise without prior permission of UL. UL provides this Standard as is wit
6、hout warranty of any kind, either expressed or implied, including but not limited to, the implied warranties of merchantability or tness for any purpose. In no event will UL be liable for any special, incidental, consequential, indirect or similar damages, including loss of prots, lost savings, loss
7、 of data, or any other damages arising out of the use of or the inability to use this Standard, even if UL or an authorized UL representative has been advised of the possibility of such damage. In no event shall ULs liability for any damage ever exceed the price paid for this Standard, regardless of
8、 the form of the claim. Users of the electronic versions of ULs Standards for Safety agree to defend, indemnify, and hold UL harmless from and against any loss, expense, liability, damage, claim, or judgment (including reasonable attorneys fees) resulting from any error or deviation introduced while
9、 purchaser is storing an electronic Standard on the purchasers computer system. The requirements in this Standard are now in effect, except for those paragraphs, sections, tables, gures, and/or other elements of the Standard having future effective dates as indicated in the note following the affect
10、ed item. The prior text for requirements that have been revised and that have a future effective date are located after the Standard, and are preceded by a SUPERSEDED REQUIREMENTS notice. APRIL 26, 2016 UL 2515A tr1UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHO
11、UT PERMISSION FROM UL APRIL 26, 2016 UL 2515A tr2 No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL NOVEMBER 21, 2011 (Title Page Reprinted: April 26, 2016) 1 UL 2515A Standard for Supplemental Requirements for Extra Heavy
12、Wall Reinforced Thermosetting Resin Conduit (RTRC) and Fittings The requirements for products covered by this standard were previously published in the rst edition of the Standard for Supplemental Requirements for Extra Heavy Wall Reinforced Thermosetting Resin Conduit (RTRC) and Fittings, UL 1684A,
13、 which has now been renumbered as UL 2515A. First Edition November 21, 2011 This ANSI/UL Standard for Safety consists of the First Edition including revisions through April 26, 2016. The most recent designation of ANSI/UL 2515A as an American National Standard (ANSI) occurred on April 26, 2016. ANSI
14、 approval for a standard does not include the Cover Page, Transmittal Pages, Title Page, or effective date information. Comments or proposals for revisions on any part of the Standard may be submitted to UL at any time. Proposals should be submitted via a Proposal Request in ULs On-Line Collaborativ
15、e Standards Development System (CSDS) at http:/. ULs Standards for Safety are copyrighted by UL. Neither a printed nor electronic copy of a Standard should be altered in any way. All of ULs Standards and all copyrights, ownerships, and rights regarding those Standards shall remain the sole and exclu
16、sive property of UL. COPYRIGHT 2016 UNDERWRITERS LABORATORIES INC. ANSI/UL 2515A-2016UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL APRIL 26, 2016 UL 2515A 2 No Text on This PageUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTIO
17、N OR DISTRIBUTION WITHOUT PERMISSION FROM UL CONTENTS 1 Scope .4 2 General 4 2.1 Units of measurement .4 2.2 Undated references .4 3 Construction 4 4 Performance .6 4.1 Compression Test (for Type XW conduit) .6 4.2 Impact Resistance (for Type XW conduit) .7 4.3 Extended support distance test (option
18、al) 8 5 Markings .8C APRIL 26, 2016 UL 2515A 3UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL 1 Scope 1.1 These requirements are supplementary to the applicable requirements in the Standard for Aboveground Reinforced Thermosetting Resin Cond
19、uit (RTRC) and Fittings, UL 2515. Products covered by these requirements are for use in the United States only. References to requirements in UL 2515 are in italics for easy identication. 1.2 This standard covers aboveground (AG) extra heavy wall conduit, Type XW (dimensions based on wall thicknesse
20、s). Trade sizes (metric designators) are 1/2 (16), 3/4 (21), 1 (27), 1-1/4 (35), 1-1/2 (41), 2 (53), 2-1/2 (63), 3 (78), 3-1/2 (91), 4 (103), 4-1/2 (116), 5 (129), and 6 (155). Note: The values in parenthesis are metric size designations of conduit and ttings and do not necessarily reect metric trad
21、e sizes. 1.3 AG Type XW is suitable for concealed or exposed work where subject to physical damage. 2 General 2.1 Units of measurement 2.1.1 Values stated without parentheses are the requirement. Values in parentheses are explanatory or approximate information. 2.2 Undated references 2.2.1 Any undat
22、ed reference to a code or standard appearing in the requirements of this standard shall be interpreted as referring to the latest edition of that code or standard. 3 Construction 3.1 Only materials that are acceptable for the particular use shall be employed. 3.2 Conduit with an integral belled end
23、The dimensions of conduit with an integral coupling on one end shall be in accordance with the values specied in Table 3.1. They shall also meet the requirements of Clause 5.7 of the Standard for Aboveground Reinforced Thermosetting Resin Conduit (RTRC) and Fittings, UL 2515. 3.2 revised October 3,
24、2014 OCTOBER 3, 2014 UL 2515A 4UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL Table 3.1 Conduit dimensions Type XW Table 3.1 revised October 3, 2014 Inside diameter minimum Wall thickness Outside diameter a Minimum Maximum Nominal Maximum T
25、rade size (metric designator) (millimeters) Type XW-IPS 3/4 21 22.61 5.59 6.73 35.31 36.58 1 27 29.34 5.59 6.73 42.04 43.31 1-1/4 35 38.10 5.59 6.73 50.80 52.07 1-1/2 41 44.20 5.59 6.73 56.90 58.17 Trade size (metric designator) (inches) 3/4 21 0.890 0.220 0.265 1.390 1.440 1 27 1.155 0.220 0.265 1.
26、655 1.705 1-1/4 35 1.500 0.220 0.265 2.000 2.050 1-1/2 41 1.740 0.220 0.265 2.240 2.290 Type XW-ID Trade size (metric designator) (millimeters) 2 53 50.29 5.59 6.73 62.99 64.26 2-1/2 63 63.00 5.59 6.73 75.69 76.96 3 78 75.69 5.59 6.73 88.39 89.66 3-1/2 91 88.39 5.59 6.73 101.10 102.36 4 103 101.09 5
27、.59 6.73 113.79 115.06 5 129 126.24 5.59 6.73 138.94 140.46 6 155 151.64 5.59 6.73 164.34 165.86 Trade size (metric designator) (inches) 2 53 1.980 0.220 0.265 2.480 2.530 2-1/2 63 2.480 0.220 0.265 2.980 3.030 3 78 2.980 0.220 0.265 3.480 3.530 3-1/2 91 3.480 0.220 0.265 3.980 4.030 4 103 3.980 0.2
28、20 0.265 4.480 4.530 5 129 4.970 0.220 0.265 5.470 5.530 6 155 5.970 0.220 0.265 6.470 6.530 a Measured circumferentially. 3.3 Couplings Couplings shall be straight with belled ends, or 5 degree angle couplings. Dimensions of couplings are shown in Table 3.2. Couplings shall also meet the requiremen
29、ts of Clause 5.7 of the Standard for Aboveground Reinforced Thermosetting Resin Conduit (RTRC) and Fittings, UL 2515. OCTOBER 3, 2014 UL 2515A 5UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL Table 3.2 Dimensions for integral couplings Type
30、XW Socket depth Inside diameter of socket Socket wall thickness minimum minimum minimum Trade size (metric designator) mm (in) mm (in) mm (in) 3/4 21 50.80 2.00 35.69 1.405 5.59 0.220 1 27 50.80 2.00 42.42 1.670 5.59 0.220 1-1/4 35 50.80 2.00 51.18 2.015 5.59 0.220 1-1/2 41 50.80 2.00 57.28 2.255 5.
31、59 0.220 2 53 50.80 2.00 63.37 2.495 5.59 0.220 2-1/2 63 50.80 2.00 76.07 2.995 5.59 0.220 3 78 50.80 2.00 88.77 3.495 5.59 0.220 3-1/2 91 50.80 2.00 101.47 3.995 5.59 0.220 4 103 57.15 2.25 114.17 4.495 5.59 0.220 5 129 74.68 2.94 139.57 5.495 5.59 0.220 6 155 74.68 2.94 164.97 6.495 5.59 0.220 4 P
32、erformance 4.1 Compression Test (for Type XW conduit) 4.1.1 The internal diameter of conduit shall not decrease by more than 25 percent during application of an 8900 N (2000 lb) force when tested in accordance with 4.1.2 4.1.4. The conduit shall show no evidence of cracking or buckling after removal
33、 from the compression machine. 4.1.2 The apparatus for this test shall consist of: a) An inside micrometer or telescopic gauge and a micrometer caliper; b) A compression machine having 2 steel platens at least 150 mm (6.0 in) long and 10 mm (0.4 in) thick and capable of running at a speed within the
34、 range of 10 15 mm/min (0.4 0.6 in/min). 4.1.3 The specimens shall consist of three 150 3 mm (6.0 0.125 in) lengths of conduit. 4.1.4 The inside diameter of the specimen shall be measured and recorded. The specimen shall be placed between the plates of the compression machine such that the measured
35、inside diameter is perpendicular to the platens. The machine shall be set in motion until the force specied in 4.1.1 has been applied to the specimen. The machine shall be stopped and the inside diameter remeasured. The percent decrease in the internal diameter shall be calculated and recorded. NOVE
36、MBER 21, 2011 UL 2515A 6UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL 4.2 Impact Resistance (for Type XW conduit) 4.2.1 When tested in accordance with 4.2.2 and 4.2.3 there shall not be any fracture or break in the laminate surface of seve
37、n out of ten 200 mm (8.0 in) specimens of the nished conduit. A fracture or break is considered to have occurred where a broken section of the laminate forms a protrusion within the inside diameter or extends beyond the outside diameter of the conduit. The portions of the conduit within 50 mm (2.0 i
38、n) from the cut ends of the specimen shall not be examined. 4.2.2 The specimens are to be cut from nished lengths of each trade size of conduit. Each specimen is to be tested separately while resting on a solid, at, steel plate that is at least 13 mm (1/2 in) thick and is rmly anchored with its uppe
39、r surface horizontal. A protective cage is to surround the plates and the specimen to reduce the likelihood of injury. 4.2.3 The impact energy is to be provided by a weight of 34.1 kg (75 lbs) in the form of a 150 mm (6.0 in) solid right-circular steel cylinder with a at impact face having rounded e
40、dges, as shown in Figure 4.1, falling freely through a vertical guide and supplying the impact force specied in Table 4.1. The at face of the weight is to strike the center of the specimen. Provision is to be made for keeping the weight from striking the specimen more than once. This is generated te
41、xt for gtxt. Figure 4.1 Impact resistance for Type XW tup geometry NOVEMBER 21, 2011 UL 2515A 7UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL Table 4.1 Impact resistance Type XW Force Trade size (metric designator) j (ft.lbs) 1/2 16 127 94
42、3/4 21 127 94 1 27 203 150 1-1/4 35 229 169 1-1/2 41 255 188 2 53 407 300 2-1/2 63 509 375 3 78 712 525 3-1/2 91 712 525 4 103 712 525 4-1/2 116 712 525 5 129 712 525 6 155 712 525 4.3 Extended support distance test (optional) 4.3.1 General 4.3.1.1 Conduit intended to be marked in accordance with 5.
43、2(h), for use at support distances greater than those in the National Electrical Code, ANSI/NFPA 70, shall have a Maximum Deection not greater than 15.9 mm (5/8 inch) after 7 days when tested in accordance with 4.3.2 4.3.5. The conduit under test shall have a center point load as shown in 4.3.2. Rep
44、resentative sample sizes shall be selected. Table 4.2 Wire ll loading for extended support distances Trade size Metric designator Wire ll 40% maximum ll kg/m lbs/ft 3/4 X21 0.707 0.475 1 X27 1.506 1.012 1-1/4 X35 2.463 1.655 1-1/2 X41 3.494 2.348 2 X53 4.274 2.872 2-1/2 X63 7.388 4.965 3 X78 9.925 6
45、.670 3-1/2 X91 13.98 9.392 4 X103 17.86 12.00 5 X129 29.55 19.86 6 X155 41.87 28.14 APRIL 26, 2016 UL 2515A 8UL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL 4.3.2 Center point load 4.3.2.1 The center point load shall be calculated by multipl
46、ying the wire ll from Table 4.2 as follows: L C = (W x D)/2 where: L C = the center point load; W = wire ll as noted above; D = the extended support distance. 4.3.3 Specimen preparation 4.3.3.1 Two specimens for each conduit size and type shall be tested. Suitable lengths are joined at 1/4 of the ex
47、tended support spacing distance using the manufacturers recommended straight section connection method. Total length, including the connection joint, shall allow the joint to be placed at 1/4 of the extended support spacing with a minimum 600-mm (24-in) overhang at each end. 4.3.3.2 All specimens sh
48、all be pre-conditioned for at least 24 hours in still air at a temperature of 10C to 40C (50F to 104F). Ambient temperature shall be in the range of 10C to 40C (50F to 104F). 4.3.4 Test xture 4.3.4.1 The test apparatus shown in Figures 4.2 and 4.3 shall be used for testing. This is generated text fo
49、r gtxt. APRIL 26, 2016 UL 2515A 8AUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL Figure 4.2 Test xture setup for extended support distance test Figure 4.3 Center load application for extended support distance test APRIL 26, 2016 UL 2515A 8BUL COPYRIGHTED MATERIAL NOT AUTHORIZED FOR FURTHER REPRODUCTION OR DISTRIBUTION WITHOUT PERMISSION FROM UL 4.3.4.2 The test xture shall have rigid bases, located at the correct e
copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
备案/许可证编号:苏ICP备17064731号-1