1、*USACE / NAVFAC / AFCESA / NASA UFGS-33 60 01 (April 2008)-Preparing Activity: USACE SupersedingUFGS-33 60 01 (July 2006)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated March 2008*SECTION TABLE OF CONTENTSDIVISION 33 - UTILITIESSECTION 33 60 01VALVES, PIPING, AND E
2、QUIPMENT IN VALVE MANHOLES04/08PART 1 GENERAL1.1 REFERENCES1.2 SUBMITTALS1.3 QUALITY ASSURANCE1.3.1 Detail Drawings1.3.2 Insulated Sections1.4 DELIVERY, STORAGE, AND HANDLINGPART 2 PRODUCTS2.1 STANDARD PRODUCTS2.2 NAMEPLATES2.3 ASBESTOS PROHIBITION2.4 ELECTRICAL WORK2.5 PIPING AND FITTINGS2.5.1 Gene
3、ral Requirements2.5.2 Steel Pipe2.5.2.1 Nipples2.5.2.2 Pipe Threads2.5.3 Fittings2.5.3.1 Welded Fittings2.5.3.2 Unions2.5.3.3 Ball Valves2.5.4 Insulating Flanges and Dielectric Waterways2.5.4.1 Insulating Flanges2.5.4.2 Dielectric Waterways2.5.4.3 Gaskets Non-Insulating2.6 VALVES2.6.1 Steel Valves2.
4、6.2 Bronze Valves2.6.2.1 Globe, Gate, and Angle Valves2.6.2.2 Check Valves2.6.3 Packing2.7 STEAM TRAPS2.7.1 Bucket TrapsSECTION 33 60 01 Page 1Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-2.7.2 Thermostatic Traps2.8 STRAINERS2.9 PRESSURE GAUGES2.1
5、0 DIAL THERMOMETERS2.11 INSULATION AND JACKETING2.11.1 General Provisions2.11.2 Insulation2.11.3 Aluminum Jackets2.11.4 Bands2.11.5 Insulation for Flanges, Unions, Valves, and Fittings2.11.6 Vapor Barrier Coating2.11.7 Finishing Cement2.11.8 Glass Tape2.11.9 Plain Weave, Untreated2.11.10 Knitted, Un
6、treated2.11.11 Distortion Requirements2.11.12 Open-Weave Tape2.12 SUMP PUMPS AND DRAINERS2.12.1 Sump Pumps2.12.2 Drainers2.13 CONCRETE VALVE MANHOLES AND ACCESSORIES2.13.1 Valve Manhole Construction2.13.2 Ladders2.13.3 Pipe Sleeves2.13.3.1 Pipe Sleeves Through Valve Manhole Cover2.13.3.2 Pipe Sleeve
7、s for Conduit Penetrations2.13.4 Pipe Supports2.14 EXPANSION JOINTS2.14.1 Guided Slip Tube2.14.2 Flexible Ball2.14.3 Bellows-Type2.15 MISCELLANEOUS METALPART 3 EXECUTION3.1 EXAMINATION3.2 SITE WORK3.2.1 Excavation, Trenching, and Backfilling3.2.2 Electric Work3.2.3 Painting3.3 PIPING3.3.1 General3.3
8、.2 Welded Joints3.3.3 Flanged and Threaded Joints3.3.3.1 Flanged Joints3.3.3.2 Threaded Joints3.3.4 Reducing Fittings3.3.5 Branch Connections3.3.6 Pipe Supports in Valve Manholes3.4 WELDING3.5 INSULATION3.5.1 Installation3.5.2 Insulation on Pipes Passing Through Sleeves3.5.3 Covering of Insulation i
9、n Valve Manholes3.5.4 Insulation of Piping Accessories in Valve Manholes3.5.5 Insulation Sealing for Chilled Water Systems3.5.6 Insulation Thickness3.6 VALVE MANHOLES AND ACCESSORIES3.6.1 Piping and Equipment in Valve ManholesSECTION 33 60 01 Page 2Provided by IHSNot for ResaleNo reproduction or net
10、working permitted without license from IHS-,-,-3.6.2 Sump Pumps Installation3.7 TESTS- End of Section Table of Contents -SECTION 33 60 01 Page 3Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-*USACE / NAVFAC / AFCESA / NASA UFGS-33 60 01 (April 2008)
11、-Preparing Activity: USACE SupersedingUFGS-33 60 01 (July 2006)UNIFIED FACILITIES GUIDE SPECIFICATIONSReferences are in agreement with UMRL dated March 2008*SECTION 33 60 01VALVES, PIPING, AND EQUIPMENT IN VALVE MANHOLES04/08*NOTE: This guide specification covers the requirements for valves, piping
12、and equipment in valve manholes that form a part of an underground heat distribution system.Edit this guide specification for project specific requirements by adding, deleting, or revising text. For bracketed items, choose applicable items(s) or insert appropriate information.Remove information and
13、requirements not required in respective project, whether or not brackets are present.Comments and suggestions on this guide specification are welcome and should be directed to the technical proponent of the specification. A listing of technical proponents, including their organization designation an
14、d telephone number, is on the Internet.Recommended changes to a UFGS should be submitted as a Criteria Change Request (CCR).*PART 1 GENERAL*NOTE: Design manual UFC 3-430-1 HEATING AND COOLING DISTRIBUTION SYSTEMS contains information that will assist the designer. Do not allow chilled water lines or
15、 other plastic piping to be routed through manholes where high temperature piping systems (above 110 degrees C (230 degrees F) are installed.Provide the following information on the contract drawings: (1) valve manhole dimensions, (2) location of all valve manholes, (3) sizes of the pipe in the valv
16、e manholes, (4) location of all valves in the valve manholes, (5) thickness of the insulation on the pipe, (6) valve manhole details, SECTION 33 60 01 Page 4Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-(7) final elevations of the valve manholes, (
17、8) valve manhole cover details including manway access details, (9) how valve manholes are drained and vented, (10) sump pump piping details, (11) valve manhole equipment dimensions and details, (12) sump pump capacity, (13) electrical wiring details for the equipment (dedicated service for sump pum
18、p), (14) steam drip trap locations with access and capacities, (15) steam main drip leg sizes.This guide specification is to be included as a part of a contract which includes Sections 33 61 00 PREFABRICATED UNDERGROUND HEATING/COOLING DISTRIBUTION SYSTEM or 33 52 13 EXTERIOR FUEL DISTRIBUTION; 33 6
19、1 13 PRE-ENGINEERED UNDERGROUND HEAT DISTRIBUTION SYSTEM or 33 63 16 EXTERIOR SHALLOW TRENCH STEAM DISTRIBUTION; 33 61 15 HEAT DISTRIBUTION SYSTEMS IN CONCRETE TRENCHES or 33 63 13EXTERIOR UNDERGROUND STEAM DISTRIBUTION SYSTEM. Include the following Sections as part of this contract: 31 00 00 EARTHW
20、ORK; 33 71 01 OVERHEAD TRANSMISSION AND DISTRIBUTION or 33 71 01 OVERHEAD TRANSMISSION AND DISTRIBUTION; 33 70 02.00 10 ELECTRICAL DISTRIBUTION SYSTEM, UNDERGROUND or 33 71 02.00 20 UNDERGROUND TRANSMISSION AND DISTRIBUTION; 03 15 13.00 10 EXPANSION JOINTS, CONTRACTION JOINTS, AND WATERSTOPS; Sectio
21、n 03 31 00.00 10 CAST-IN-PLACE STRUCTURAL CONCRETE03 30 00 CAST-IN-PLACE CONCRETE; 05 05 23.00 10 WELDING, STRUCTURAL; 05 50 00 METAL: MISCELLANEOUS AND FABRICATIONS; 07 13 53 ELASTOMERIC SHEET WATERPROOFING; 09 90 00 PAINTS AND COATINGS; 43 02 00or 40 17 26.00 20 WELDING PRESSURE PIPING; 26 20 00 I
22、NTERIOR DISTRIBUTION SYSTEM or 26 51 00 INTERIOR LIGHTING; and others as applicable to the project.*1.1 REFERENCES*NOTE: This paragraph is used to list the publications cited in the text of the guide specification. The publications are referred to in the text by basic designation only and listed in
23、this paragraph by organization, designation, date, and title.Use the Reference Wizards Check Reference feature when you add a RID outside of the Sections Reference Article to automatically place the reference in the Reference Article. Also use the Reference Wizards Check Reference feature to update
24、the issue dates.References not used in the text will automatically be deleted from this section of the project specification when you choose to reconcile references in the publish print process.*SECTION 33 60 01 Page 5Provided by IHSNot for ResaleNo reproduction or networking permitted without licen
25、se from IHS-,-,-The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.ALUMINUM ASSOCIATION (AA)AA H35.1/35.1M (2007) Alloy and Temper Designation Systems for AluminumASME INTERNATIONAL
26、(ASME)ASME B1.20.1 (1983; R 2006) Pipe Threads, General Purpose (Inch)ASME B16.11 (2005) Forged Fittings, Socket-Welding and ThreadedASME B16.20 (1998; Addenda A 2000; R 2004) Metallic Gaskets for Pipe Flanges - Ring-Joint, Spiral Wound, and JacketedASME B16.21 (2005) Nonmetallic Flat Gaskets for Pi
27、pe FlangesASME B16.3 (2006) Malleable Iron Threaded Fittings, Classes 150 and 300ASME B16.34 (2004) Valves - Flanged, Threaded and Welding EndASME B16.5 (2003) Standard for Pipe Flanges and Flanged Fittings: NPS 1/2 Through NPS 24ASME B16.9 (2003) Standard for Factory-Made Wrought Steel Buttwelding
28、FittingsASME B31.1 (2007) Power PipingASME B40.100 (2006) Pressure Gauges and Gauge AttachmentsASME BPVC SEC IX (2007) Boiler and Pressure Vessel Code; Section IX, Welding and Brazing QualificationsASTM INTERNATIONAL (ASTM)ASTM A 106/A 106M (2006a) Standard Specification for Seamless Carbon Steel Pi
29、pe for High-Temperature ServiceASTM A 123/A 123M (2002) Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel ProductsASTM A 193/A 193M (2007) Standard Specification for Alloy-Steel and Stainless Steel Bolting Materials for High-Temperature ServiceSECTION 33 60 01 Page 6Pro
30、vided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-ASTM A 194/A 194M (2007) Standard Specification for Carbon and Alloy Steel Nuts for Bolts for High-Pressure or High-Temperature Service, or BothASTM A 234/A 234M (2007) Standard Specification for Piping Fi
31、ttings of Wrought Carbon Steel and Alloy Steel for Moderate and High Temperature ServiceASTM A 53/A 53M (2007) Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and SeamlessASTM A 733 (2003) Standard Specification for Welded and Seamless Carbon Steel and Austenitic St
32、ainless Steel Pipe NipplesASTM B 209 (2007) Standard Specification for Aluminum and Aluminum-Alloy Sheet and PlateASTM B 209M (2007) Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate (Metric)ASTM C 449/C 449M (2007) Standard Specification for Mineral Fiber Hydraulic-Setting Ther
33、mal Insulating and Finishing CementASTM C 533 (2007) Standard Specification for Calcium Silicate Block and Pipe Thermal InsulationASTM C 547 (2007) Standard Specification for Mineral Fiber Pipe InsulationASTM C 552 (2007) Standard Specification for Cellular Glass Thermal InsulationASTM C 647 (1995;
34、R 2000) Properties and Tests of Mastics and Coating Finishes for Thermal InsulationASTM D 2822 (2005) Asphalt Roof CementASTM D 3278 (1996; R 2004e1) Flash Point of Liquids by Small Scale Closed-Cup ApparatusASTM E 84 (2007b) Standard Test Method for Surface Burning Characteristics of Building Mater
35、ialsASTM E 96/E 96M (2005) Standard Test Methods for Water Vapor Transmission of MaterialsASTM F 1139 (1988; R 2004) Steam Traps and DrainsSECTION 33 60 01 Page 7Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-MANUFACTURERS STANDARDIZATION SOCIETY OF
36、 THE VALVE AND FITTINGS INDUSTRY (MSS)MSS SP-110 (1996) Ball Valves Threaded, Socket-Welding, Solder Joint, Grooved and Flared EndsMSS SP-25 (1998) Standard Marking System for Valves, Fittings, Flanges and UnionsMSS SP-45 (2003) Bypass and Drain ConnectionsMSS SP-58 (2002) Standard for Pipe Hangers
37、and Supports - Materials, Design and ManufactureMSS SP-69 (2003; R 2004) Standard for Pipe Hangers and Supports - Selection and ApplicationMSS SP-72 (1999) Standard for Ball Valves with Flanged or Butt-Welding Ends for General ServiceMSS SP-80 (2003) Bronze Gate, Globe, Angle and Check ValvesMSS SP-
38、83 (2006) Standard for Class 3000 Steel Pipe Unions Socket Welding and ThreadedNATIONAL FIRE PROTECTION ASSOCIATION (NFPA)NFPA 70 (2007) National Electrical Code - 2008 EditionNFPA 90A (2002; Errata 2003; Errata 2005) Standard for the Installation of Air Conditioning and Ventilating SystemsTHE SOCIE
39、TY FOR PROTECTIVE COATINGS (SSPC)SSPC Paint 16 (2006) Paint Specification No. 16 Coal Tar Epoxy-Polyamide Black (or Dark Red) PaintSSPC SP 10 (2007) Near-White Blast CleaningUNDERWRITERS LABORATORIES (UL)UL 723 (2003; Rev thru May 2005) Standard for Test for Surface Burning Characteristics of Buildi
40、ng Materials1.2 SUBMITTALS*NOTE: Review submittal description (SD) definitions in Section 01 33 00 SUBMITTAL PROCEDURES and edit the following list to reflect only the submittals required for the project. Submittals should be kept to the minimum required for adequate quality control.SECTION 33 60 01
41、 Page 8Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-A “G” following a submittal item indicates that the submittal requires Government approval. Some submittals are already marked with a “G”. Only delete an existing “G” if the submittal item is not
42、 complex and can be reviewed through the Contractors Quality Control system. Only add a “G” if the submittal is sufficiently important or complex in context of the project.For submittals requiring Government approval on Army projects, a code of up to three characters within the submittal tags may be
43、 used following the “G“ designation to indicate the approving authority. Codes for Army projects using the Resident Management System (RMS) are: “AE“ for Architect-Engineer; “DO“ for District Office (Engineering Division or other organization in the District Office); “AO“ for Area Office; “RO“ for R
44、esident Office; and “PO“ for Project Office. Codes following the “G“ typically are not used for Navy, Air Force, and NASA projects.Choose the first bracketed item for Navy, Air Force and NASA projects, or choose the second bracketed item for Army projects.*Government approval is required for submitt
45、als with a “G“ designation; submittals not having a “G“ designation are for Contractor Quality Control approval.information only. When used, a designation following the “G“ designation identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:SD-02 Shop DrawingsDetail Drawings; G; G, _Detail drawings, as specified, _ days after notice to proceed.SD-03 Product DataPiping and FittingsVa
copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
备案/许可证编号:苏ICP备17064731号-1