1、Designation: C1015 06 (Reapproved 2011)1Standard Practice forInstallation of Cellulosic and Mineral Fiber Loose-FillThermal Insulation1This standard is issued under the fixed designation C1015; the number immediately following the designation indicates the year oforiginal adoption or, in the case of
2、 revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the Department of Defense.1NOTENote 1 was editoriall
3、y revised in December 2011.1. Scope1.1 This practice covers procedures for the installation ofcellulosic and mineral fiber loose-fill insulation in ceilings,attics, and floor and wall cavities of new or existing housingand other framed buildings.1.2 This practice applies only to the installation of
4、dryloose-fill thermal insulation consisting of cellulosic materialsor mineral fiber by pneumatic or pouring application.1.3 This practice covers the installation process from pre-installation inspection through post-installation procedure. Itdoes not cover the production of the insulation materials.
5、1.4 This practice is not intended to replace the manufactur-ers installation instructions, but shall be used in conjunctionwith such instructions. This practice is not intended to super-sede local, state, or federal codes.1.5 This practice assumes that the installer possesses a goodworking knowledge
6、 of the applicable codes and regulations,safety practices, tools, equipment, and methods necessary forthe installation of thermal insulation materials. It also assumesthat the installer understands the fundamentals of residentialconstruction that affect the installation of insulation.1.6 The values
7、stated in inch-pound units are to be regardedas standard. The values given in parentheses are mathematicalconversions to SI units that are provided for information onlyand are not considered standard.1.7 This standard does not purport to address all of thesafety concerns, if any, associated with its
8、 use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use. For specificprecautionary statements, see Section 5.2. Referenced Documents2.1 ASTM Standards:2C168 Terminology Re
9、lating to Thermal InsulationC739 Specification for Cellulosic Fiber Loose-Fill ThermalInsulationC755 Practice for Selection of Water Vapor Retarders forThermal InsulationC764 Specification for Mineral Fiber Loose-Fill ThermalInsulation2.2 NFPA Standards:3NFPA 31 Standard for the Installation of Oil
10、BurningEquipmentNFPA 54 National Fuel Gas CodeNFPA 70 National Electrical CodeNFPA 211 Standard for Chimneys, Fireplaces, Vents andSolid-Fuel Burning Appliances2.3 ICC Document:4International Residential Code 20032.4 Federal Standard:5FTC Trade Regulation Rule 16 CRF 460, Labeling andAdvertising of
11、Home Insulation3. Terminology3.1 DefinitionsFor definitions of terms used in this prac-tice, see Terminology C168.3.2 Definitions of Terms Specific to This Standard:1This practice is under the jurisdiction of ASTM Committee C16 on ThermalInsulation and is the direct responsibility of Subcommittee C1
12、6.23 on Blanket andLoose Fill Insulation.Current edition approved Sept. 1, 2011. Published December 2011. Originallyapproved in 1984. Last previous edition approved in 2006 as C1015 06. DOI:10.1520/C1015-06R11.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Custo
13、mer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Available from National Fire Protection Association (NFPA), 1 BatterymarchPark, Quincy, MA 02169-7471, http:/www.nfpa.org.4Available from Internationa
14、l Code Council (ICC), 500 New Jersey Ave., NW,6th Floor, Washington, DC 20001, http:/www.iccsafe.org.5Federal Register Vol 70, No 103, May 31, 2005. Available from NationalArchives and Records Administration, 8601 Adelphi Road, College Park Maryland,207406001.1Copyright ASTM International, 100 Barr
15、Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.3.2.1 installerthe person or persons who apply thermalinsulation materials in residential buildings whether or not suchperson or persons have contracted with the owner to performthe work.3.2.2 cellulosic loose-fill thermal in
16、sulating materialsthose materials that meet the minimum requirements specifiedin Specification C739.3.2.3 conditioned spacea space in a residential buildingthat is served by a heating or cooling system.3.2.4 mineral fiber loose-fill thermal insulating materialsthose materials that meet the minimum r
17、equirements specifiedin Specification C764.3.2.5 ownerthe person, partnership, corporation, agency,or other entity who owns the residential building to beinsulated whether such ownership is by virtue of deed, con-tract, or any other instrument for acquiring legal title under thelaws of the state in
18、which the building is located.3.2.6 residential buildinga building used for residentialoccupancy and that has a mechanical or electrical system forheating or for cooling, or for both.3.2.7 vapor retardera material (membrane or paint) thathas a water vapor permeance rating of 1 perm (5.7 310-8/Pasm2)
19、 or less. See Practice C755 for more information onvapor retarders.4. Significance and Use4.1 This practice recognizes that effectiveness, safety, anddurability of insulation depend not only on the quality of theinsulating materials, but also on their proper installation.4.2 Improper installation of
20、 insulation can reduce its ther-mal effectiveness, cause fire risks and other unsafe conditions,and promote deterioration for the structure in which it isinstalled. Specific hazards that can result from improperinstallation include fires caused by (1) heat build-up in recessedlighting fixtures; (2)
21、deterioration or failure of electrical wiringcomponents; (3) heat build-up resulting from overcurrentprotection devices incorrectly matched to wiring; or (4) dete-rioration in wood structures and paint failure due to moistureaccumulation.4.3 This practice provides general procedures that will helpen
22、sure the installation of insulation in a safe and effectivemanner. It must be noted that actual conditions in existingbuildings vary greatly, and in some cases substantial additionalcare and precaution must be taken to ensure effective and safeinstallation.5. Safety Precautions5.1 All pneumatic equi
23、pment shall be operated in accor-dance with the recommended operating and safety proceduresof the equipment manufacturer and the insulation manufac-turer.5.2 The installer shall wear proper clothing and equipmentas recommended by the insulation manufacturer. If in doubt ofthe effects of the insulati
24、on, wear protective clothing, gloves,eye and breathing protection.NOTE 1For breathing protection use a NIOSH approved N95 orhigher disposable or reusable particulate respirator.5.3 In areas where insulation will be installed, componentsof the electrical system shall be in good condition. If theelect
25、rical system is faulty, proper inspection and repair must benone.NOTE 2The Consumer Product Safety Commission6has identified thefollowing signs of potential electrical deficiencies: Lights dimming, fusesblowing, circuit breakers tripping frequently, electrical sparks and glowingfrom receptacles, lig
26、hts flickering, and coverplates on switches and outletsthat are warm or hot to the touch.6. Pre-Installation Preparation6.1 In the areas where insulation will be installed, theinstaller shall locate and plan for subsequent blocking aroundrecessed lighting fixtures, motors, fans, blowers, heaters, fl
27、ues,chimneys, and other heat-producing electrical or mechanicaldevices.6.1.1 Install blocking, such as wood, metal, or unfacedmineral wool batts, securely fastened in place around allheat-producing devices to exclude loose fill insulation andpermanently maintain the clearances specified in 6.1.2 and
28、6.1.3, or the exception in 6.1.4. Install all required blocking atleast as high as the height of the finished insulation and in amanner that ensures that all devices that require maintenance orservicing remain accessible after the insulation is installed.6.1.2 Install blocking to provide a 3-in. (75
29、-mm) minimumclearance around all sides of recessed lighting fixtures, unlesssuch fixtures are approved for installation in direct contact withinsulation (IC rated), including fixture wiring compartmentsand ballasts, and other heat-producing devices not covered in6.1.3. The open area above these devi
30、ces must not be covered,in order to allow free air circulation unless they are specificallyapproved devices for operation when covered with thermalinsulation (see 410-66, NFPA 70, National Electric Code).6.1.3 Do not place insulation in air spaces surroundingmetal flues, chimneys or fireplaces. Prov
31、ide the minimumclearances specified in NFPA 31, NFPA 54 or NFPA 211 or asrequired by local building codes.6.1.4 Inspect the roof, walls, ceilings, and attic floors toidentify areas where previous or existing moisture problem hascaused paint peeling, warpage, stain, visible fungus growth,rotting, or
32、other structural damage. Notify the owner to correctthese conditions before installing insulation.6.1.5 The installer shall block all openings in ceilings,floors, and sidewalls through which it is possible for theinsulating material to escape. Block all wall cavities that openinto a basement or craw
33、l space before wall insulation isinstalled.6.1.6 Proper attic ventilation and the use of vapor retardersshall be provided before installation in accordance with build-ing requirements or practices, local building codes and theInternational Residence Code.NOTE 3The International Residence Code, Secti
34、on R806.2 states thefollowing attic ventilation requirements: The total net free ventilating areashall not be less than 1 to 150 of the area of the space ventilated except6CPSC Product Safety Fact Sheet No. 518, “Guide to Home Electric Wiring,”available from the Consumer Product Safety Commission, 4
35、330 East West HighwayBethesda, MD 20814.C1015 06 (2011)12that the total area is permitted to be reduced to 1 300, provided at least 50% and not more than 80% of the required ventilating area is provided byventilators located in the upper portion of the space to be ventilated at least3 ft. (914 mm) a
36、bove the eave or cornice vents with the balance of therequired ventilation provided by eave or cornice vents. As an alternative,the net free cross-ventalation area may be reduced to 1 to 300 when avapor barrier having a transmission rate not exceeding 1 perm (57.4 mg/sm2Pa is installed on the warm s
37、ide of the ceiling.When the attic has soffit vents at the eaves, install rigidblocking to restrain loose-fill insulation from clogging thevents, thus restricting attic ventilation. Blocking shall beinstalled to ensure free movement of air through soffit ventsinto the attic.7. Procedure7.1 Installati
38、on:7.1.1 The insulation material shall be handled in accordancewith manufacturers instructions and should be kept free ofextraneous materials. Keep the materials dry and do not placein contact with the ground or other sources of water.7.1.2 Apply the insulation uniformly covering all areas. Toattain
39、 the required R-value, install at least the minimumthickness and minimum square-foot weight in acordance withthe coverage chart supplied by the manufacturer.7.1.3 Fill enclosed cavities to rejection of the material toensure that cavity is free of voids and that the proper amountis installed in accor
40、dance with the manufacturers coveragechart.7.1.4 For pneumatic installation, use only equipment com-patible with the insulation material, and operate the equipmentin accordance with the manufacturers instructions.7.1.5 In pouring applications, install insulation in accor-dance with the manufacturers
41、 recommended coverage.7.2 Post-Installation:7.2.1 Inspect the coverage and depth of the insulation. Fillall pockets and voids in the insulation. Level insulation in amanner that will not damage wiring or any other items. Turnoff the electric power and clear all electric wall outlet boxesand switch b
42、oxes of any insulation material. Check all bafflesand vents for insulation accumulation. Remove all temporaryblockings that were installed over vent openings in attics.7.2.2 The installer must provide a signed and dated state-ment describing the insulation installed, stating thickness,coverage area,
43、 R-value, and number of bags used or poundsinstalled per FTC Rule 16 CFR 460.8. Keywords8.1 cellulose; installation; light frame construction; loosefill; mineral fiberASTM International takes no position respecting the validity of any patent rights asserted in connection with any item mentionedin th
44、is standard. Users of this standard are expressly advised that determination of the validity of any such patent rights, and the riskof infringement of such rights, are entirely their own responsibility.This standard is subject to revision at any time by the responsible technical committee and must b
45、e reviewed every five years andif not revised, either reapproved or withdrawn. Your comments are invited either for revision of this standard or for additional standardsand should be addressed to ASTM International Headquarters. Your comments will receive careful consideration at a meeting of theres
46、ponsible technical committee, which you may attend. If you feel that your comments have not received a fair hearing you shouldmake your views known to the ASTM Committee on Standards, at the address shown below.This standard is copyrighted by ASTM International, 100 Barr Harbor Drive, PO Box C700, W
47、est Conshohocken, PA 19428-2959,United States. Individual reprints (single or multiple copies) of this standard may be obtained by contacting ASTM at the aboveaddress or at 610-832-9585 (phone), 610-832-9555 (fax), or serviceastm.org (e-mail); or through the ASTM website(www.astm.org). Permission rights to photocopy the standard may also be secured from the ASTM website (www.astm.org/COPYRIGHT/).C1015 06 (2011)13
copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
备案/许可证编号:苏ICP备17064731号-1