1、Designation: C1534 12Standard Specification forFlexible Polymeric Foam Sheet Insulation Used as aThermal and Sound Absorbing Liner for Duct Systems1This standard is issued under the fixed designation C1534; the number immediately following the designation indicates the year oforiginal adoption or, i
2、n the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This specification covers the composition, dimensions,and physical properties of f
3、lexible unfaced foam sheet, used toinsulate interior surfaces of HVAC ducts, plenums and equip-ment used for the distribution of conditioned air with atemperature of up to 250F (121C).1.2 HVAC ducts, plenums and equipment systems typicallyoperate between a temperature range of 50F to 150F (10C to65C
4、) and are designed to meet building code requirements ofmaximum temperatures of 250F (121C).1.3 The values stated in inch-pound units are to be regardedas standard. The values given in parentheses are mathematicalconversions to SI units that are provided for information onlyand are not considered st
5、andard.1.4 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory requirements prior to use.2. Refe
6、renced Documents2.1 ASTM Standards:2C168 Terminology Relating to Thermal InsulationC177 Test Method for Steady-State Heat Flux Measure-ments and Thermal Transmission Properties by Means ofthe Guarded-Hot-Plate ApparatusC209 Test Methods for Cellulosic Fiber Insulating BoardC390 Practice for Sampling
7、 and Acceptance of ThermalInsulation LotsC411 Test Method for Hot-Surface Performance of High-Temperature Thermal InsulationC423 Test Method for Sound Absorption and Sound Ab-sorption Coefficients by the Reverberation Room MethodC518 Test Method for Steady-State Thermal TransmissionProperties by Mea
8、ns of the Heat Flow Meter ApparatusC634 Terminology Relating to Building and EnvironmentalAcousticsC665 Specification for Mineral-Fiber Blanket Thermal In-sulation for Light Frame Construction and ManufacturedHousingC1045 Practice for Calculating Thermal Transmission Prop-erties Under Steady-State C
9、onditionsC1071 Specification for Fibrous Glass Duct Lining Insula-tion (Thermal and Sound Absorbing Material)C1104/C1104M Test Method for Determining the WaterVapor Sorption of Unfaced Mineral Fiber InsulationC1114 Test Method for Steady-State Thermal TransmissionProperties by Means of the Thin-Heat
10、er ApparatusC1304 Test Method for Assessing the Odor Emission ofThermal Insulation MaterialsC1338 Test Method for Determining Fungi Resistance ofInsulation Materials and FacingsE84 Test Method for Surface Burning Characteristics ofBuilding MaterialsE176 Terminology of Fire StandardsE795 Practices fo
11、r Mounting Test Specimens During SoundAbsorption TestsE2231 Practice for Specimen Preparation and Mounting ofPipe and Duct Insulation Materials to Assess SurfaceBurning CharacteristicsG21 Practice for Determining Resistance of Synthetic Poly-meric Materials to Fungi2.2 Other Standards:CAN/ULC-S102 S
12、tandard Method of Test for SurfaceBurning Characteristics of Building Materials and Assem-blies3. Terminology3.1 The definitions of terms used in this specification shallbe in accordance with Terminologies C168, C634, and E176.Incase of any conflicts, Terminology C168 shall be the authority.3.2 Defi
13、nitions of Terms Specific to This Standard:1This specification is under the jurisdiction of ASTM Committee C16 onThermal Insulation and is the direct responsibility of Subcommittee C16.22 onOrganic and Nonhomogeneous Inorganic Thermal Insulations.Current edition approved Feb. 1, 2012. Published Marc
14、h 2012. Originallyapproved in 2002. Last previous edition approved in 2007 as C1534071. DOI:10.1520/C1534-12.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the sta
15、ndards Document Summary page onthe ASTM website.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.3.2.1 closed cell foama foam comprised of predominatelyindividual non interconnecting cells.3.2.2 flexible cellulara cellular material th
16、at will notrupture within 60 s when a specimen 1 3 1 3 8 in. in length(25 3 25 3 200 mm) is bent around a 1 in. (25 mm) diametermandrel at a uniform rate of one lap in5sintheform of a helixat a temperature between 65 and 85F (18 and 29C).3.2.3 open cell foama foam made porous by interconnect-ing cel
17、ls.4. Classification4.1 The flexible polymeric insulations of this specificationare classified into Types I and II. Type I is a closed flexiblefoam. Type II is an open cell flexible foam.NOTE 1The primary difference between Type I and Type II materialsare: Type I materials exhibit lower water absorp
18、tion properties and TypeII materials have greater acoustical properties as noted in Tables 1 and 2.5. Materials5.1 These products shall be made of a homogeneous blendof natural or synthetic polymeric materials. Modifications withvarious thermoplastic or thermosetting resins, plasticizers,modifiers,
19、antioxidants, curatives, blowing agents and otheradditives are allowed. These products do not melt whenexposed to heat and are considered to be thermoset materials.5.2 Flexible, polymeric cellular thermal insulations shall beof uniform core density. These insulation materials are avail-able with a s
20、mooth skin surface or coating on one or both sides,and they are to be considered homogeneous for the purposes ofdetermining thermal performance.6. Ordering Information6.1 Specific installation, insulation type, thickness, length,and width suited for the intended use shall be agreed upon bythe purcha
21、ser and supplier.7. Physical PropertiesSee Tables 1 and 2 for Summaryof Requirements7.1 Apparent Thermal ConductivityThe material shall betested for apparent thermal conductivity at 75F (24C) meantemperature in accordance with 12.1. The thermal conductivityfor the average of any four randomly select
22、ed samples, shallnot be more than 0.30 Btu-in./h-sq ftF (0.043 W/m-K) whentested in accordance with 12.1. See Table 1.NOTE 2Consult the local or state building codes for the minimuminstalled thermal resistance, R-value, required to be installed.7.2 Surface Burning CharacteristicsShall be in accor-da
23、nce with 12.2. See Table 1 for requirements.7.3 Hot Surface PerformanceThe insulation shall have noevidence of flaming, glowing, smoldering, visible smoke,delamination, cracking, warpage, melting, dripping or reduc-tion in thickness when tested in accordance with 12.3 at thetemperature specified in
24、Table 1.NOTE 3Hot Surface Performance Characteristics for Type 1MaterialWhen this type of material is used on hot applications, thematerials characteristics will change and should be considered whenselecting the material for an application. Heat will cause the elastomericinsulation to harden. As the
25、 temperature approaches the stated hightemperature limit, the process occurs faster. This hardening will notnegatively effect the thermal performance or water vapor transmissionproperties of the product. The hardening will be most noticeable closer tothe heat source. This effect is based on time and
26、 temperature.7.4 Water Vapor SorptionShall be tested in accordancewith 12.4. See Table 1.7.5 Water AbsorptionShall be tested in accordance with12.5. See Table 1.7.6 Dimensional StabilityShall be tested in accordancewith 12.6.7.7 Odor EmissionThere shall be no detectable odor ofobjectionable nature w
27、hen tested in accordance with 12.7.7.8 CorrosivenessNo corrosion shall be noted whentested in accordance with 12.8.7.9 Fungi ResistanceWhen tested in accordance with12.9, the test specimens shall show no fungal growth.7.10 Erosion ResistanceThe product shall show no evi-dence of delamination or cont
28、inued erosion when air is passedthrough typical duct sections when tested in accordance with12.10.7.11 Sound Absorption CoeffcientWhen tested in accor-dance with Test Method C423 using an “A” mounting inTABLE 1 Physical PropertiesType I Type IIMaximum Apparent Thermal Conductivity Btu-in./h-ft2F) ma
29、x.(W/m-K) max.0.30(0.043)0.30(0.043)Surface Burning Characteristics ( at maximum total installedthickness):(SeeA) (SeeA)Flame Spread Index, (max) # 25 15Smoke Developed Index, (max) # 50 15Water Vapor Sorption wt % gain by vol. (max.) 0.00 0.1Water Absorption, wt % gain by vol. (max.) 0.2 4.0Dimensi
30、onal Stability % change (max.) length, width or thickness 7.0 1.0Odor Emission Pass PassCorrosiveness Pass PassFungi Resistance No Growth No GrowthErosion Resistance Pass PassHot Surface Performance at not less than 250F (125C)(See 7.3 for requirements)Pass PassBAConsult manufacturer regarding maxim
31、um thickness approved for surface burning characteristics Type 1 is typically tested at 1 in. thickness. Type 2 is typically testedat 2 in. thickness. Product should be tested at the thickness to be used in the application.BActual product properties may exceed requirements listed in Table 1, consult
32、 manufacturers for specific applications.C1534 122accordance with Practice E795, the insulation shall have soundabsorption coefficient and NRC not less than that indicated inTable 2.8. Qualification and Inspection Requirements8.1 Qualification RequirementsThe following require-ments shall be used fo
33、r purposes of initial material qualifica-tion:8.1.1 Apparent thermal conductivity,8.1.2 Surface burning characteristics,8.1.3 Hot surface performance,8.1.4 Water vapor sorption,8.1.5 Water absorption,8.1.6 Odor emission,8.1.7 Corrosiveness,8.1.8 Fungi resistance,8.1.9 Erosion resistance, and8.1.10 S
34、ound absorption coefficient.8.2 InspectionThe following requirements shall be usedfor purposes of acceptance sampling of lots or shipments ofqualified thermal insulation:8.2.1 Dimensional tolerances, and8.2.2 Workmanship.9. Dimensional Tolerances9.1 After conditioning for a minimum of 24 h at 70 6 3
35、F(21 6 1.6C) and 50 6 5 % relative humidity, the insulationshall conform to the dimensional tolerances listed in Table 3.All dimensions shall be measured at the conditioning tempera-ture.10. Workmanship and Finish10.1 The insulation shall indicate good workmanship infabrication and shall not have vi
36、sible defects that adverselyeffect service performance.11. Sampling11.1 Sampling of the insulation shall be in accordance withPractice C390. Specific provisions for sampling shall be agreedupon between the purchaser and the supplier.12. Test Methods12.1 Apparent Thermal ConductivityTest in accordanc
37、ewith Test Method C177 or Test Method C518 or Test MethodC1114 at 75F (24C) mean temperature (see also PracticeC1045).12.2 Surface Burning CharacteristicsDetermine the sur-face burning characteristic for the material in accordance withTest Method E84. In Canada use Test Method CAN/ULC-S102. The resu
38、lts shall be reported. See Section 1 of TestMethod E84 for information regarding the applicability of thistest method for use with cellular plastics and Practice E2231for specimen mounting methods.12.3 Hot Service PerformanceThe maximum hot surfacetemperature of the material shall be tested in accor
39、dance withTest Method C411.12.4 Water Vapor SorptionTest the water sorption of thematerial in accordance with the Test Method C1104/C1104M.12.5 Water AbsorptionDetermine the amount of waterabsorption of the test specimen in accordance with TestMethod C209 (24 h immersion time).12.6 Dimensional Stabi
40、lityDetermine length, width andthickness change when tested in accordance with C356 afteraging 24 h at a minimum of 250F (125C) or the maximumuse temperature whichever is higher.12.7 Odor EmissionDetermine the odor emission in ac-cordance with Test Method C1304 except test at 200F (92C).12.8 Corrosi
41、venessThe corrosiveness of the material shallbe determined in accordance with the corrosiveness testmethod defined in Specification C665.12.9 Fungi/ResistanceThe fungi resistance of the materialshall be determined in accordance with Practice G21 and TestMethod C1338.12.10 Erosion ResistanceThe air e
42、rosion properties of thematerial shall be as determined in accordance with the erosionresistance test methods and requirements defined in Specifica-tion C1071. The air velocity for the test is dependent upon theuse of the product. The air velocity for the test shall be 2.5times the maximum rated vel
43、ocity of the product.12.11 Sound Absorption CoeffcientTest in accordancewith Test Method C423 using an “A” mounting in accordancewith Practice E795.13. Inspection13.1 Inspection of the insulation shall be as agreed upon bythe purchaser and the manufacturer as part of the purchaseagreement.TABLE 2 So
44、und Absorption Coefficients (min) Using Test Method C423 Type “A” MountingAPractice E795.Frequency, Hz 125 250 500 1000 2000 4000 NRCAType I12 in. (13 mm) 0.03 0.04 0.06 0.20 0.40 0.15 0.201 in. (25 mm) 0.15 0.10 0.30 0.30 0.20 0.20 0.25Type II12 in. (13 mm) 0.07 0.10 0.25 0.60 0.98 0.85 0.501 in. (
45、25 mm) 0.14 0.20 0.45 0.80 0.98 0.85 0.602 in. (50 mm) 0.25 0.58 1.00 0.98 1.00 0.90 0.90ANRC-Noise Reduction CoefficientTABLE 3 Dimensional Tolerance, in. (mm)Dimension ToleranceWidth +0.250 in./-0 in. (+6 mm/-0 mm)Length -0/excess permittedThickness 610 %C1534 12314. Rejection14.1 Material that fa
46、ils to conform to the requirementsagreed upon in the purchasing agreement is subject to rejec-tion. Rejection shall be reported to the producer or supplierpromptly and in writing.15. Certification15.1 When specified in the purchase order or contract, aproducers, suppliers, or independent third party
47、s certificationshall be furnished to the purchaser indicating that the materialwas manufactured, sampled, tested, and inspected in accor-dance with this specification and has been found to meet therequirements. When specified in the purchase order or contract,a report of test results shall be furnis
48、hed.16. Product Marking16.1 The air stream surface of the liner shall be markedaccording to the purchasers requirements, for example: prod-uct name, thickness, manufacturer, surface burning character-istics and nominal R-value.17. Packaging and Package Marking17.1 PackagingUnless otherwise specified
49、, the insulationshall be packaged in the manufacturers standard containers.17.2 Package MarkingThe markings shall be clear andlegible. The package shall be marked with the manufacturersname, address, product name, lot number, material width,length, thickness, and nominal R-value.18. Keywords18.1 closed cell; ducts; flexible; foam; HVAC; insulation;open cell; sound absorbing; thermal insulationASTM International takes no position respecting the validity of any patent rights asserted in connection with any item me
copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
备案/许可证编号:苏ICP备17064731号-1