1、Designation: C578 11b1Standard Specification forRigid, Cellular Polystyrene Thermal Insulation1This standard is issued under the fixed designation C578; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last revision. A n
2、umber in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the Department of Defense.1NOTE8.2.1 was editorially corrected in February 2012.1. Scope1.1 T
3、his specification2covers the types, physical properties,and dimensions of cellular polystyrene boards with or withoutfacings or coatings made by molding (EPS) or extrusion (XPS)of expandable polystyrene. Products manufactured to thisspecification are intended for use as thermal insulation fortempera
4、tures from -65 to +165F (-53.9 to +73.9C). Thisspecification does not apply to laminated products manufac-tured with any type of rigid board facer including fiberboard,perlite board, gypsum board, or oriented strand board.1.1.1 For Type XIII only, this specification covers thephysical properties, an
5、d dimensions of cellular polystyreneintended for use as thermal insulation for temperatures from297 to +165F (183 to +73.9C).1.2 Consult the manufacturer for specific recommendationsand properties in cryogenic conditions.1.2.1 This specification does not cover cryogenic propertiesexcept for the k-fa
6、ctors for Type XIII in Appendix X1. ForType XIII in specific cryogenic applications, the manufacturerand purchaser shall agree upon the actual temperature limitsand physical property requirements in addition to the k-factorsin Appendix X1.1.3 The use of thermal insulation materials covered by thissp
7、ecification may be regulated by building codes that addressfire performance. For some end uses, specifiers should alsoaddress the effect of moisture and wind pressure resistance.Guidelines regarding these end use considerations are includedin Appendix X1.1.4 The values stated in inch-pound units are
8、 to be regardedas standard. The values given in parentheses are mathematicalconversions to SI units that are provided for information onlyand are not considered standard.1.5 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility
9、of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:3C165 Test Method for Measuring Compressive Propertiesof Thermal InsulationsC168 Terminology Relating t
10、o Thermal InsulationC177 Test Method for Steady-State Heat Flux Measure-ments and Thermal Transmission Properties by Means ofthe Guarded-Hot-Plate ApparatusC203 Test Methods for Breaking Load and Flexural Prop-erties of Block-Type Thermal InsulationC272 Test Method for Water Absorption of Core Mater
11、ialsfor Structural Sandwich ConstructionsC303 Test Method for Dimensions and Density of Pre-formed Block and BoardType Thermal InsulationC335 Test Method for Steady-State Heat Transfer Proper-ties of Pipe InsulationC390 Practice for Sampling and Acceptance of ThermalInsulation LotsC518 Test Method f
12、or Steady-State Thermal TransmissionProperties by Means of the Heat Flow Meter ApparatusC550 Test Method for Measuring Trueness and Squarenessof Rigid Block and Board Thermal InsulationC870 Practice for Conditioning of Thermal Insulating Ma-terials1This specification is under the jurisdiction of AST
13、M Committee C16 onThermal Insulation and is the direct responsibility of Subcommittee C16.22 onOrganic and Nonhomogeneous Inorganic Thermal Insulations.Current edition approved Nov. 15, 2011. Published December 2011. Originallyapproved in 1965. Last previous edition approved in 2011 as C578 11a. DOI
14、:10.1520/C0578-11BE01.2This specification is similar to ISO 4898-1984, “Cellular PlasticsSpecificationfor Rigid Cellular Materials Used in the Thermal Insulation of Buildings,” in titleonly. The scope and technical content are significantly different.ISO standards are available from American Nationa
15、l Standards Institute (ANSI),25 W. 43rd St., 4th Floor, New York, NY 10036, http:/www.ansi.org.3For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Documen
16、t Summary page onthe ASTM website.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.C1045 Practice for CalculatingThermalTransmission Prop-erties Under Steady-State ConditionsC1058 Practice for Selecting Temperatures for Evaluatingand
17、Reporting Thermal Properties of Thermal InsulationC1114 Test Method for Steady-State Thermal TransmissionProperties by Means of the Thin-Heater ApparatusC1303 Test Method for Predicting Long-Term ThermalResistance of Closed-Cell Foam InsulationC1363 Test Method for Thermal Performance of BuildingMat
18、erials and Envelope Assemblies by Means of a HotBox ApparatusD1600 Terminology for Abbreviated Terms Relating toPlasticsD1621 Test Method for Compressive Properties of RigidCellular PlasticsD1622 Test Method for Apparent Density of Rigid CellularPlasticsD2126 Test Method for Response of Rigid Cellul
19、ar Plasticsto Thermal and Humid AgingD2863 Test Method for Measuring the Minimum OxygenConcentration to Support Candle-Like Combustion ofPlastics (Oxygen Index)E84 Test Method for Surface Burning Characteristics ofBuilding MaterialsE96/E96M Test Methods for Water Vapor Transmission ofMaterialsE176 T
20、erminology of Fire Standards3. Terminology3.1 Definitions:3.1.1 Terms used in this specification are defined in Termi-nology C168.3.1.2 Terms used in this specification that relate to firestandards are defined in Terminology E176.3.2 Definitions of Terms Specific to This Standard:3.2.1 EPSletter des
21、ignation for the molded expandedpolystyrene thermal insulation classified by this specification.It is defined as cellular plastic product manufactured frompre-expanded polystyrene beads subsequently molded intodesired shapes and sizes resulting in a product which is rigidwith closed cellular structu
22、re.3.2.2 RCPSletter designations for the rigid cellular poly-styrene thermal insulation classified by this specification thatidentifies the product as rigid cellular polystyrene.3.2.3 PSused in this specification to represent polystyrenein accordance with Terminology D1600.3.2.4 XPSletter designatio
23、n for the extruded expandedpolystyrene thermal insulation classified by this specification.It is defined as cellular plastic product manufactured in a onestage process by extrusion and expansion of the base polymerin the presence of blowing agent(s) resulting in a productwhich is rigid with closed c
24、ellular structure.4. Classification4.1 This specification covers types of RCPS thermal insu-lations currently commercially available as described by thephysical property requirements in Table 1.5. Ordering Information5.1 Acquisition documents shall specify the following:5.1.1 Title, number, and year
25、 of this specification,5.1.2 Type (see Table 1),5.1.3 R-value or thickness required (see Tables 1 and 2),5.1.3.1 Thermal Resistance/Thickness RelationshipThethermal resistance (R-value) and the thermal resistivity (R-value/inch) of RCPS thermal insulation may vary with thick-ness. Therefore, when or
26、dering, specify the R-value or thethickness, or both. For additional information, see PracticeC1045.5.1.4 Density, if other than specified in Table 1,5.1.5 Tolerance, if other than specified (see 8.2),5.1.6 Length and width required (see Table 2 and 8.1),5.1.7 If other than straight edges are requir
27、ed (see 8.3),5.1.8 If either ship-lap or tongue-and-groove edges arerequired (see 8.6),5.1.9 Tapered Insulationspecial ordering information. Inaddition to other applicable requirements in Section 5 (Note 1),acquisition documents for tapered RCPS thermal insulationshall specify the following:5.1.9.1
28、Minimum starting thickness,5.1.9.2 Slope, in./ft (mm/m),5.1.9.3 Average R-value,5.1.9.4 Minimum thickness,5.1.9.5 Shop DrawingsThe tapered insulation suppliershall provide shop drawings to illustrate installation patternsand dimensions for each tapered module,5.1.10 Sampling, if different (see 10.1)
29、,5.1.11 If a certificate of compliance is required (see 14.1),and5.1.12 If marking is other than specified (see 15.1).NOTE 1Physical properties of tapered insulation should be deter-mined on blocks of RCPS thermal insulation before the insulation istapered.5.1.13 Type XIIISpecial ordering informatio
30、n. In additionto other applicable requirements in Section 5, acquisitiondocuments for Type XIII thermal insulation shall specify ifpresence of surface skins is required.6. Materials and Manufacture6.1 RCPS thermal insulation shall be formed by the expan-sion of polystyrene resin beads or granules in
31、 a closed mold, orby the expansion of polystyrene base resin in an extrusionprocess. RCPS thermal insulation shall be of uniform densityand have essentially closed cells. All RCPS thermal insulationshall contain sufficient flame retardants to meet the oxygenindex requirements of Table 1.7. Physical
32、Requirements7.1 Inspection Requirements:7.1.1 The physical requirements listed in this section aredefined as inspection requirements (refer to Practice C390).7.1.2 All dimensional requirements are described in Section8.7.1.3 All workmanship, finish, and appearance requirementsare described in Sectio
33、n 9.7.1.4 Density shall be in accordance with Table 1.C578 11b12NOTE 2For lots of 150 units or less, the tightened inspection samplingplan in Practice C390 will be followed.7.2 Qualification Requirements:7.2.1 The physical properties listed in this section of thespecification are defined as qualific
34、ation requirements (refer toPractice C390). Thermal resistance, compressive resistance,flexural strength, water vapor permeance, water absorption,dimensional stability, and oxygen index shall be in accordancewith Table 1. The average test value based upon testing thenumber of test specimens required
35、 by the specified test methodfor each physical property or Section 11 of this specificationshall be used to determine compliance.7.2.2 The mean thermal resistance of the material testedshall not be less than the minimum value identified in Table 1.The thermal resistances of individual specimens test
36、ed shallnot be less than 90 % of the minimum value identified in Table1.7.2.2.1 If one inch thickness product is not produced thenext available commercially manufactured product thicknessgreater than one inch thickness shall be tested and reported.7.2.3 Compliance with qualification requirements sha
37、ll bein accordance with Practice C390.7.3 Table 1 describes types of RCPS thermal insulation.However, it does not cover all available products on themarket. The values stated in Table 1 are not intended to be usedas design values. It is the buyers responsibility to specifydesign requirements and obt
38、ain supporting documentationfrom the material supplier.7.4 Combustibility CharacteristicsRCPS thermal insula-tion is an organic material and is, therefore, combustible. Itshall not be exposed to flames or other ignition sources. Thevalues obtained by the oxygen index test (see Table 1 and11.10) do n
39、ot necessarily indicate or describe the fire risk of thematerials and are used in this specification primarily toTABLE 1 Physical Property Requirements of RCPS Thermal InsulationNOTE 1The values for properties listed in this table may be affected by the presence of a surface skin which is a result o
40、f the manufacturing process.The values for Type XIII properties listed in this table must be generated on material with the surface skin removed. Where products are tested withskins-in-place, this condition shall be noted in the test report.NOTE 2Type III has been deleted because it is no longer ava
41、ilable.NOTE 3In addition to the thermal resistance values in Table 1, values at mean temperatures of 25 6 2F (-4 6 1C), 40 6 2F (4 6 1C), and 1106 2F (43 6 1C) are provided in X1.8 for information purposes.NOTE 4For Type XIII, in addition to the Thermal resistance property requirements shown in Tabl
42、e 1, there are Apparent Thermal Conductivityproperty values shown for informational purposes in Table X1.2 of Appendix X1.NOTE 5Values quoted are maximum values for 1.00 in. (25.4 mm) thick samples with natural skins intact. Lower values will result for thickermaterials. Where water vapor permeance
43、is a design issue, consult manufacturer.NOTE 6Types XI, I, VIII, II, IX, XIV and XV are typically EPS insulation. Types XII, X, XIII, IV, VI, VII and V are typically XPS insulation.Classification TypeXITypeITypeVIIITypeIITypeIXTypeXIVTypeXVTypeXIITypeXTypeXIIITypeIVTypeVITypeVIITypeVCompressive resi
44、stance atyield or 10 % deformation,whichever occurs first(with skins intact), min, psi(kPa)5.0(35)10.0(69)13.0(90)15.0(104)25.0(173)40.0(276)60.0(414)15.0(104)15.0(104)20.0(138)25.0(173)40.0(276)60.0(414)100.0(690)Thermal resistance of 1.00-in.(25.4-mm) thickness, min,Fft2h/Btu (Km2/W)3.1(0.55)3.6(0
45、.63)3.8(0.67)4.0(0.70)4.2(0.74)4.2(0.74)4.3(0.76)4.6(0.81)5.0(0.88)3.9(0.68)5.0(0.88)5.0(0.88)5.0(0.88)5.0(0.88)Mean temperature:75 6 2F (24 6 1C)Flexural strength, min, psi (kPa) 10.0(70)25.0(173)30.0(208)35.0(240)50.0(345)60.0(414)75.0(517)40.0(276)40.0(276)45.0(310)50.0(345)60.0(414)75.0(517)100.
46、0(690)Water vapor permeance of1.00-in. (25.4-mm) thickness(See Note 5.), max, perm(ng/Pasm2)5.0(287)5.0(287)3.5(201)3.5(201)2.5(143)2.5(143)2.5(143)1.5(86)1.5(86)1.5(86)1.5(86)1.1(63)1.1(63)1.1(63)Water absorption by totalimmersion, max, volume %4.0 4.0 3.0 3.0 2.0 2.0 2.0 0.3 0.3 1.0 0.3 0.3 0.3 0.
47、3Dimensional stability (changein dimensions), max,%2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0Oxygen index, min, volume % 24.0 24.0 24.0 24.0 24.0 24.0 24.0 24.0 24.0 24.0 24.0 24.0 24.0 24.0Density, min, lb/ft3(kg/m3) 0.70(12)0.90(15)1.15(18)1.35(22)1.80(29)2.40(38)2.85(46)1.20(19)1.30(
48、21)1.60(26)1.55(25)1.80(29)2.20(35)3.00(48)TABLE 2 Common Dimensions of RCPS Thermal InsulationType XI, I, VIII, II, IX, XIV, XV X, IV, XII VI, VII V XIIIWidth, in. (mm) 12 to 48 (305 to 1219) 16, 24, 48 (406, 610, 1219) 24 (610) 16 (406) 14 to 20 (356 to508)Length, in. (mm) 48 to 192 (1219 to 4877)
49、 48, 96 108 (1219, 2438, 2743) 48, 96, (1219, 2438) 96 (2438) 36 to 112 (914 to2845)Thickness, in. (mm)38 to 24 (9.5 to 610)12 to 4 (13 to 102) 1 to 4 (25 to 102) 1 to 4 (25 to 102) 7 to 10 (178 to254)C578 11b13distinguish between insulations formulated with flame retar-dants and those not so formulated.8. Dimensions and Permissible Variations8.1 The materials covered by this specification are com-monly available in the sizes shown in Table 2. Other sizes shallbe agreed upon between the supplier and the user.8.2 Dimensional Tolerances