1、Designation: D4263 83 (Reapproved 2018)Standard Test Method forIndicating Moisture in Concrete by the Plastic SheetMethod1This standard is issued under the fixed designation D4263; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, th
2、e year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the U.S. Department of Defense.1. Scope1.1 This test method is us
3、ed to indicate the presence ofcapillary moisture in concrete.1.2 The values stated in inch-pound units are to be regardedas standard. The values given in parentheses are mathematicalconversions to SI units that are provided for information onlyand are not considered standard.1.3 This standard does n
4、ot purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety, health, and environmental practices and deter-mine the applicability of regulatory limitations prior to use.For specific caution st
5、atements, see Section 4.1.4 This international standard was developed in accor-dance with internationally recognized principles on standard-ization established in the Decision on Principles for theDevelopment of International Standards, Guides and Recom-mendations issued by the World Trade Organizat
6、ion TechnicalBarriers to Trade (TBT) Committee.2. Significance and Use2.1 Capillary moisture in the concrete may be detrimental tothe performance of certain coating systems that cannot toleratemoisture on or within the surface boundary.2.2 This test method is used prior to the application ofcoatings
7、 on concrete.3. Materials3.1 Transparent Polyethylene Sheet, commerciallyavailable, approximately 4 mils (0.1 mm) thick.3.2 Adhesive Tape that will adhere to the substrate. (Ducttape 2 in. (50 mm) wide is suggested.)4. Cautions4.1 This test method shall be conducted when the surfacetemperature and a
8、mbient conditions are within the establishedparameters for application of the coating system.4.2 Avoid direct sunlight, direct heat, or damage to theplastic sheet, as such treatment affects the reliability of theresults.5. Procedure5.1 Tape a segment of plastic sheet, approximately 18 by 18in. (457
9、by 457 mm), tightly to the concrete surface makingsure that all edges are sealed.5.2 Allow the plastic sheet to remain in place a minimum of16 h.5.3 After the allowed time has elapsed, remove the plasticsheet and visually inspect the underside of the sheet and theconcrete surface of the patch for th
10、e presence of moisture.5.4 Sampling:5.4.1 FloorsOne test area per 500 ft2(46 m2) or portionthereof, of surface areas unless otherwise specified.5.4.2 Walls and CeilingsOne test area per 500 ft2(46 m2)or portion thereof, of surface area unless otherwise specified.5.4.3 The recommended practice is a m
11、inimum of one testfor each 10 ft (3 m) of vertical rise in all elevation startingwithin 12 in. (300 mm) of the floor.6. Report6.1 Report the presence or absence of moisture.7. Precision and Bias7.1 This test method indicates the presence of capillarymoisture. This method is purely qualitative. No pr
12、ecision orbias has been established for this test method.8. Keywords8.1 concrete; moisture1This test method is under the jurisdiction of ASTM Committee D33 onProtective Coating and Lining Work for Power Generation Facilities and is the directresponsibility of Subcommittee D33.05 on Application and S
13、urface Preparation.Current edition approved Aug. 1, 2018. Published August 2018. Originallyapproved in 1983. Last previous edition approved in 2012 as D4263 83 (2012).DOI: 10.1520/D4263-83R18.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United S
14、tatesThis international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for theDevelopment of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to
15、Trade (TBT) Committee.1ASTM International takes no position respecting the validity of any patent rights asserted in connection with any item mentionedin this standard. Users of this standard are expressly advised that determination of the validity of any such patent rights, and the riskof infringem
16、ent of such rights, are entirely their own responsibility.This standard is subject to revision at any time by the responsible technical committee and must be reviewed every five years andif not revised, either reapproved or withdrawn. Your comments are invited either for revision of this standard or
17、 for additional standardsand should be addressed to ASTM International Headquarters. Your comments will receive careful consideration at a meeting of theresponsible technical committee, which you may attend. If you feel that your comments have not received a fair hearing you shouldmake your views kn
18、own to the ASTM Committee on Standards, at the address shown below.This standard is copyrighted by ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959,United States. Individual reprints (single or multiple copies) of this standard may be obtained by contacting AS
19、TM at the aboveaddress or at 610-832-9585 (phone), 610-832-9555 (fax), or serviceastm.org (e-mail); or through the ASTM website(www.astm.org). Permission rights to photocopy the standard may also be secured from the Copyright Clearance Center, 222Rosewood Drive, Danvers, MA 01923, Tel: (978) 646-2600; http:/ 83 (2018)2
copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
备案/许可证编号:苏ICP备17064731号-1