1、Designation: D4418 00 (Reapproved 2016)Standard Practice forReceipt, Storage, and Handling of Fuels for Gas Turbines1This standard is issued under the fixed designation D4418; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the yea
2、r of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This practice covers the receipt, storage, and handling offuels for gas turbines, except for gas turbines used in
3、 aircraft.It is intended to provide guidance for the control of substancesin a fuel that could cause deterioration of either the fuel system,or the gas turbine, or both.1.2 This practice provides no guidance for either the selec-tion of a grade of fuel, a topic covered by Specification D2880,or for
4、the safety aspects of the fuel and fuel systems. Forexample, this practice does not address the spacings of storagetanks, loading and unloading facilities, etc., and procedures fordealing with the flammability and toxic properties of the fuels.1.3 The values stated in SI units are to be regarded as
5、thestandard. The values given in parentheses are for informationonly.1.4 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the
6、applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2D1500 Test Method for ASTM Color of Petroleum Products(ASTM Color Scale)D1796 Test Method for Water and Sediment in Fuel Oils bythe Centrifuge Method (Laboratory Procedure)D2274 Test Method for Oxidation
7、 Stability of Distillate FuelOil (Accelerated Method)D2276 Test Method for Particulate Contaminant in AviationFuel by Line SamplingD2880 Specification for Gas Turbine Fuel OilsD4057 Practice for Manual Sampling of Petroleum andPetroleum ProductsD6469 Guide for Microbial Contamination in Fuels and Fu
8、elSystems3. Terminology3.1 fuel entering the combustor(s)this term is used todesignate the fuel that is actually burned in the gas turbine.Fuel may actually be sampled at a point upstream from thepoint of entry into the combustor(s), provided the sample isrepresentative of the fuel actually entering
9、 the combustor(s).3.2 fuel contaminantsin principle, are any fuel componentother than hydrocarbon oils. In the present context the con-taminants are foreign materials that make the fuel less suitableor even unsuitable for the intended use. The contaminants ofprimary interest are foreign materials in
10、troduced subsequent tothe manufacture of specification quality fuel. Hence they arematerials introduced in the distribution system (that is storagetanks, pipelines, tank, trucks, barges, etc.), or in the usersstorage and handling systems, or generated within thesesystems (rust generated in steel pip
11、es and tanks by moist fuel,etc.). Contaminants may be soluble or insoluble in the fuel.3.3 dissolved and free waterwater may be present in thefuel as dissolved water or as “free” (undissolved) water, orboth. The free water may be fresh or saline. Fresh water mayenter the fuel from steam coils in sto
12、rage tanks, from conden-sation out of moisture-laden air, or from leaking cooling coils.Saline water can enter the fuel during transportation in bargesor tankers.3.4 particulate solidsmay enter a fuel from the air (sus-pended dirt and aerosols) or from the distribution and storagesystems (rust, corr
13、osion products, gasket debris, and so forth).3.5 metallic compoundsmetals may be present as metalliccompounds in the fuel as a natural result of the composition ofthe crude oil and of the refining process. However, unlessspecial precautions are taken, additional metallic compoundscan be acquired dur
14、ing distribution and storage. A commercialproduct pipeline may contain residues of lead-containinggasoline that would then be dissolved by the gas turbine fuel.Tank trucks, railroad tankcars, barges, and tankers may beinadequately cleaned and contain residues of past cargos.Acidic components in sali
15、ne water salts in the fuel may reactwith distribution and storage equipment.3.6 microbial slimesmay result when conditions are con-ducive to the growth of microorganisms that are always1This practice is under the jurisdiction of ASTM Committee D02 on PetroleumProducts, Liquid Fuels, and Lubricants a
16、nd is the direct responsibility of Subcom-mittee D02.E0 on Burner, Diesel, Non-Aviation Gas Turbine, and Marine Fuels.Current edition approved April 1, 2016. Published May 2016. Originallyapproved in 1984. Last previous edition approved in 2011 as D4418 00(2011).DOI: 10.1520/D4418-00R16.2For referen
17、ced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Co
18、nshohocken, PA 19428-2959. United States1present. The presence of free water is essential to the growth ofmany of these microorganisms that grow in tank water bottomsand feed on nutrients in the water or on the hydrocarbons.4. Summary of Practice4.1 The body of this practice defines the contaminants
19、frequently found in turbine fuel oils and discusses the sourcesand significance of such contaminants.4.2 Annex A1 is a guide for the receipt, storage, andhandling of distillate gas turbine fuels, Grades 1-GT and 2-GT,in accordance with Specification D2880.4.3 Annex A2 is a guide for the receipt, sto
20、rage, andhandling of gas turbine fuels, Grades 3-GT and 4-GT, thatcontain residual components.4.4 Annex A3 is a guide for the selection and storage offuels intended for long-term storage, when such fuels aredistillate fuels.4.5 Annex A4 is a guide for gas turbine users who areconsidering the use of
21、fuels from alternative non-petroleumsources.5. Significance and Use5.1 This practice provides the user of gas turbine fuel oilsand the designer of gas turbine fuel systems with an apprecia-tion of the effects of fuel contaminants and general methods ofcontrolling such contaminants in gas turbine fue
22、l systems.5.2 This practice is general in nature and should not beconsidered a substitute for any requirement imposed by war-ranty of the gas turbine manufacturer, or by federal, state, orlocal government regulations.5.3 Although it cannot replace a knowledge of local condi-tions or the use of good
23、engineering and scientific judgment,this practice does provide guidance in development of indi-vidual fuel management systems for the gas turbine user.6. Significance of Contaminants6.1 Contamination levels in the fuel entering the combus-tor(s) must be low for improved turbine life. Low contamina-t
24、ion levels in the fuel in the turbines in-plant fuel system arerequired to minimize corrosion and operating problems. Pro-viding fuel of adequate cleanliness to the gas turbine combus-tor(s) may require special actions by the user. These actionsmight include special transportation arrangements with
25、the fuelsupplier, particular care in on-site fuel storage and qualitycontrol procedures, and establishment of on-site cleanup pro-cedures. Each of the four classes of contaminants defined in 3.2has its own significance to system operation.6.1.1 Water will cause corrosion of tanks, piping, flowdivide
26、rs, and pumps. Corrosion or corrosion products inclose-tolerance devices, such as flow dividers, may causeplugging and may stop flow to the turbines. Free water ispotentially corrosive in sulfur-containing fuels, it may beparticularly corrosive. Free water may contain dissolved saltsthat may be corr
27、osive, and may encourage microbiologicalgrowth.6.1.2 Particulate solids may shorten the life of fuel systemcomponents. Life of fuel pumps and of various close-tolerancedevices is a function of particulate levels and size distributionsin the fuel. High levels of particulates can lead to short cycleti
28、mes in the operation of filters, filter/separators, centrifuges,and electrostatic purifiers. Since such separation devices do notremove all the particulates, certain quantities will be present inthe down-stream fuel.6.1.3 Trace metals refer both to those metals present asmetallic compounds in soluti
29、on and to metals present inparticulates like rust. They are dissolved or suspended either inthe fuel hydrocarbons or in free water present in the fuel. Thesignificance of several individual trace metals with respect tohot corrosion is discussed in 6.1.4 through 6.1.5. Althoughlower levels of trace m
30、etals in a fuel will promote longerturbine service from a corrosion standpoint, the specification ofexcessively low levels may limit the availability of the fuel ormaterially increase its cost. Table 1 suggests levels of tracemetals that would probably yield satisfactory service.6.1.4 Ash is the non
31、combustible material in an oil. Ashforming materials may be present in fuel oil in two forms: (1)solid particles, and (2) oil- or water-soluble metallic com-pounds. The solid particles are for the most part the samematerial that is designated as sediment in the water andsediment test. Depending on t
32、heir size, these particles cancontribute to wear in the fuel system and to plugging of the fuelfilter and the fuel nozzle. The soluble metallic compounds havelittle or no effect on wear or plugging, but they can containelements that produce turbine corrosion and deposits as de-scribed in 6.1.5.6.1.5
33、 Vanadium and LeadFuel contaminants might in-clude soluble compounds such as vanadium porphyrins, me-tallic soaps, or tetraethyl lead that cannot be removed from thefuel at the gas-turbine site.6.1.5.1 Vanadium can form low melting compounds such asvanadium pentoxide which melts at 691 C (1275 F), a
34、ndcauses severe corrosive attack on all of the high-temperaturealloys used for gas-turbine blades. If there is sufficient magne-sium in the fuel, it will combine with the vanadium to formcompounds with higher melting points and thus reduce thecorrosion rate to an acceptable level. The resulting ash
35、willform deposits in the turbine and will require appropriatecleaning procedures.6.1.5.2 When vanadium is present in more than traceamounts either in excess of 0.5 ppm or a level recommendedby the turbine manufacturer, it is necessary to maintain aweight ratio of magnesium to vanadium in the fuel of
36、 not lessthan 3.0 in order to control corrosion.6.1.5.3 An upper limit of 3.5 is suggested since larger ratioswill lead to unnecessarily high rates of ash deposition. In mostTABLE 1 Trace Metal Limits of Fuel Entering TurbineCombustor(s)DesignationTrace Metal Limits by Weight, max, ppmVanadiumSodium
37、 plusPotassiumCalcium LeadNo. 0-GT 0.5 0.5 0.5 0.5No. 1-GT 0.5 0.5 0.5 0.5No. 2-GT 0.5 0.5 0.5 0.5No. 3-GT 0.5 0.5 0.5 0.5No. 4-GT (Consult turbine manufacturers)D4418 00 (2016)2cases, the required magnesium-to-vanadium ratio will beobtained by additions of magnesium-containing compounds tothe fuel
38、oil. The special requirements covering the addition andtype of magnesium-containing additive, or equivalent, shall bespecified by mutual agreement between the various interestedparties. The additive will vary depending on the application,but it is always essential that there is a fine and uniformdis
39、persion of the additive in the fuel at the point of combustion.6.1.5.4 For gas turbines operating at turbine-inlet gas tem-peratures below 650 C (1200 F), the corrosion of the high-temperature alloys is of minor importance, and the use of asilicon-base additive will further reduce the corrosion rate
40、 byabsorption and dilution of the vanadium compounds.6.1.5.5 Lead can cause corrosion, and in addition it can spoilthe beneficial inhibiting effect of magnesium additives onvanadium corrosion. Since lead is only rarely found in signifi-cant quantities in crude oils, its appearance in the fuel oil is
41、primarily the result of contamination during processing ortransportation.6.1.6 Sodium, Potassium, and CalciumFuel contaminantsmight also include fuel-insoluble materials such as water, salt,or dirt, potential sources of sodium, potassium, and calcium.These are normally removed at the gas-turbine sit
42、e, unless suchcontaminants are extremely finely divided.6.1.6.1 Sodium and Potassium can combine with vanadiumto form eutectics that melt at temperatures as low as 566 C(1050 F) and can combine with sulfur in the fuel to yieldsulfates with melting points in the operating range of the gasturbine. The
43、se compounds produce severe corrosion, and forturbines operating at gas inlet temperatures above 650 C(1200 F), additives are not yet in general use that control suchcorrosion.6.1.6.2 Accordingly, the sodium-plus-potassium level mustbe limited, but each element is measured separately. Some gasturbin
44、e installations incorporate systems for washing oil withwater to reduce the sodium-plus-potassium level. In installa-tions where the fuel is moved by sea transport, the sodium-plus-potassium level should be checked prior to use to ensurethat the oil has not become contaminated with sea salt. For gas
45、turbines operating at turbine inlet gas temperatures below650 C (1200 F), the corrosion due to sodium compounds is ofminor importance and can be further reduced by silicon-baseadditives. A high sodium content is even beneficial in theseturbines because it increases the water-solubility of the depos-
46、its and thereby increases the ease with which gas turbines canbe water-washed to obtain recovery of the operating perfor-mance.6.1.6.3 CalciumCalcium is not harmful from a corrosionstandpoint: in fact, it serves to inhibit the corrosive action ofvanadium. However, calcium can lead to hard-bonded dep
47、ositsthat are not self-spalling when the gas turbine is shut down, andare not readily removed by water washing of the turbine. Thefuel-washing systems, used at some gas turbine installations toreduce the sodium and potassium level, will also significantlylower the calcium content of fuel oil.6.1.7 M
48、icrobial SlimesMicrobial slimes caused by micro-organisms can plug filters and other close-tolerance openings.Some organisms can cause corrosion as well as produce slimes.Under anaerobic conditions, hydrogen sulfide, which maycause corrosion, can be generated by biological action. Bio-cides are avai
49、lable for controlling the growth ofmicroorganisms, but their effect on trace metal levels and otherfuel properties should be considered. Since water is requiredfor the growth of the microorganisms, one way of controllingtheir growth is to eliminate the presence of water throughtank-stripping operations or other separation techniques. Referto Guide D6469 for a more complete discussion.7. Keywords7.1 contaminants; fuel handling; fuel storage; gas turbinefuelsANNEXES(Mandatory Information)A1. PRACTICE FOR THE RECEIPT, STORAGE, AND HANDLING OF DISTILLATE TURBINE FU