1、Designation: F 1826 00 (Reapproved 2006)Standard Specification forLive Line and Measuring Telescoping Tools1This standard is issued under the fixed designation F 1826; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of las
2、t revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope1.1 This specification covers mechanical and electrical test-ing and acceptance criteria for telescoping live line tools.1.1
3、.1 A tool designed only for use as a measuring deviceneed not comply with mechanical strength requirements of thisspecification.1.2 The use and maintenance of this equipment is beyondthe scope of this specification.1.3 This specification does not cover multiple section orextendable section clampstic
4、ks.1.4 The values stated in SI units are to be regarded as thestandard. The inch-pound units given in parentheses areprovided for information only.1.5 The following safety hazards caveat pertains to Section9 only. This standard does not purport to address all of thesafety concerns, if any, associate
5、d with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2D 149 Test Method for Dielectric Breakdown Voltage andDielectr
6、ic Strength of Solid Electrical Insulating Materialsat Commercial Power FrequenciesF 819 Terminology Relating to Electrical Protective Equip-ment for Workers3. Terminology3.1 Definitions Terminology used in this specification isin accordance with Definitions F 819.3.2 Definitions of Terms Specific t
7、o This Standard:3.2.1 acceptance test, none made at the option of thepurchaser to verify that a product meets design criteria.3.2.2 design test, none made on a sample treated asrepresentative of an industrial product. These tests generallywill not be repeated in quantity production.3.2.3 dimensional
8、 check, nmeasurements made to verifythat a product complies with the dimension stated by themanufacturer.3.2.4 hydrophobic, adjlacking affinity for water.3.2.5 routine test, na type of test made regularly onproduction material.3.2.6 telescoping live line tool, nan extendable multiplesection FRP tool
9、 designed to carry an attachment to performmechanical tasks.3.2.7 telescoping measuring tool, nan extendable mul-tiple section FRP tool designed only to measure verticalheights.3.2.8 visual inspection, na visual check made to detectmanufacturing defects.4. Significance and Use4.1 This specification
10、shall be used for design, routine, andacceptance testing of live line and measuring telescoping tools.5. Ordering Information5.1 Include the following information when ordering tele-scoping live line or measuring tools, or both:5.1.1 Quantity.5.1.2 Catalog number.NOTE 1Live line tools may also be de
11、signed as a measuring tool.5.1.3 Tested to meet ASTM Specification F 1826 designtests.6. Workmanship, Finish, and Appearance6.1 The external and internal surfaces shall have hydropho-bic abilities.6.2 The external and internal surfaces shall be free of anyabrasions, scratches, blemishes and surface
12、defects that maycapture an impurity and impair the dielectric integrity of theproduct.1This specification is under the jurisdiction of ASTM Committee F18 onElectrical Protective Equipment for Workers and is the direct responsibility ofSubcommittee F18.35 on Tools telescoping measuring toolsFIG. 11 T
13、ypical Test Arrangement for Electrical Withstand Acceptance TestTABLE 1 Telescoping Live Line Tool Horizontal BendingDeflection Test Acceptable Values of Deflection Versus ExtendedLengthExtended Length No Weight Added 2.27 kg (5 lb) Added2.4m(8ft) 1.3cm(12 in.) 9.2 cm (358 in.)3.7m(12ft) 9cm(334 in.
14、) 0.4m(1ft358 in.)4.9 m (16 ft) 26.7 cm (1012 in.) 0.9m(2ft1114 in.)6.0m(20ft) 0.53m(1ft9in.) 1.7m(5ft612 in.)7.6m(25ft) 0.95m(3ft112 in.) 2.4 m (8 ft 0 in.)9.1 m (30 ft) 1.5 m (5 ft 1 in.) 3.1 m (10 ft 1058 in.)10.7m(35ft) 2.3m(7ft7in.) 4.4m(14ft4in.)12.2 m (40 ft) 3.15 m (10 ft 4 in.) 5.6 m (18 ft
15、 4 in.)TABLE 2 Telescoping Live Line Tool Vertical Deflection Test (NoWeight Added)Extended Length No Weight Added2.4m(8ft) 0.53m(1ft9in.)3.7m(12ft) 0.83m(2ft812 in.)4.9m(16ft) 1.1m(3ft812 in.)6.1m(20ft) 1.6m(5ft412 in.)7.6m(25ft) 2.0m(6ft8in.)9.1m(30ft) 2.5m(8ft2in.)10.7 m (35 ft) 3.1 m (10 ft 112
16、in.)12.2 m (40 ft) 3.7 m (12 ft 3 in.)TABLE 3 Moisture Conditioning ValuesTime: 168 hTemperature: 23 6 2CRelative humidity: 93 % or greaterTABLE 4 Leakage Current l1AType Outside Diameter Leakage Current l1mm in. ATube B025.4 01 525.431.8 1114 6 31.8 38.1 114 112 8 38.1 44.5 112 134 9 44.5 50.8 134
17、2 1050.863.5 2212 12 63.5 76.2 212 3 14AValues listed for maximum l1are based on pole constructed of a relatively thinwall and filled internally with foam or hollow tube. Some special applicationsrequire a thicker wall, denser foam, or different materials, which could change thedielectric constant o
18、f the test setup and consequently l1. Tubes, such as these, willstill meet the requirements of this specification if the dry leakage is less than twicethe listed maximum value of l1in the table.B = one set not two.F 1826 00 (2006)5APPENDIX(Nonmandatory Information)X1. Alternative Electrical Withstan
19、d TestX1.1 The test apparatus shall be designed to provide theoperator full protection in the performance of duties andprovide reliable means of de-energizing and grounding thehigh voltage circuit.X1.2 The typical test set-up is shown in Fig. X1.1 and Fig.X1.2. The necessary equipment should be shie
20、lded adequatelyto provide accurate readings. The test fixture should beenclosed for worker protection and equipped with an exhaustfan to provide a stable atmosphere. A drive mechanism shouldbe utilized to ensure a uniform rate of feed. The feed rate shallbe proportional to the response time of the m
21、etering circuit,that is, it should be run slow enough that maximum readingsare obtained. At no time should this rate of feed exceed 12.2m/min (40 ft/min).X1.3 With 150 mm (6 in.) electrode spacing, the appliedvoltage will be 50 kV. The equipment shall be designed suchthat at flashover, excessive lea
22、kage current will disable thedrive mechanism so that intentional action on the part of theoperator is required to reset the equipment.X1.4 Acceptable values of leakage current shall be a riseabove ambient of less than l1as listed in Table 4.ASTM International takes no position respecting the validit
23、y of any patent rights asserted in connection with any item mentionedin this standard. Users of this standard are expressly advised that determination of the validity of any such patent rights, and the riskof infringement of such rights, are entirely their own responsibility.This standard is subject
24、 to revision at any time by the responsible technical committee and must be reviewed every five years andif not revised, either reapproved or withdrawn. Your comments are invited either for revision of this standard or for additional standardsand should be addressed to ASTM International Headquarter
25、s. Your comments will receive careful consideration at a meeting of theresponsible technical committee, which you may attend. If you feel that your comments have not received a fair hearing you shouldmake your views known to the ASTM Committee on Standards, at the address shown below.This standard i
26、s copyrighted by ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959,United States. Individual reprints (single or multiple copies) of this standard may be obtained by contacting ASTM at the aboveaddress or at 610-832-9585 (phone), 610-832-9555 (fax), or serviceastm.org (e-mail); or through the ASTM website(www.astm.org).FIG. X1.1 Alternative Electrical Test Set-UpFIG. X1.2 Alternative Electrical Test Set-UpF 1826 00 (2006)6