1、DRAFT FOR DEVELOPMENTDD CEN/TS 15447:2006Mounting and fixing in reaction to fire tests under the Construction Products DirectiveICS 13.220.50g49g50g3g38g50g51g60g44g49g42g3g58g44g55g43g50g56g55g3g37g54g44g3g51g40g53g48g44g54g54g44g50g49g3g40g59g38g40g51g55g3g36g54g3g51g40g53g48g44g55g55g40g39g3g37g6
2、0g3g38g50g51g60g53g44g42g43g55g3g47g36g58Licensed Copy: Wang Bin, na, Thu Apr 19 08:04:59 GMT+00:00 2007, Uncontrolled Copy, (c) BSIDD CEN/TS 15447:2006This Draft for Development was published under the authority of the Standards Policy and Strategy Committee on 30 March 2007 BSI 2007ISBN 978 0 580
3、50357 3National forewordThis Draft for Development was published by BSI. It is the UK implementation of CEN/TS 15447:2006. This publication is not to be regarded as a British Standard.It is being issued in the Draft for Development series of publications and is of a provisional nature. It should be
4、applied on this provisional basis, so that information and experience of its practical application can be obtained.Comments arising from the use of this Draft for Development are requested so that UK experience can be reported to the European organization responsible for its conversion to a European
5、 standard. A review of this publication will be initiated not later than 3 years after its publication by the European organization so that a decision can be taken on its status. Notification of the start of the review period will be made in an announcement in the appropriate issue of Update Standar
6、ds.According to the replies received by the end of the review period, the responsible BSI Committee will decide whether to support the conversion into a European Standard, to extend the life of the Technical Specification or to withdraw it. Comments should be sent to the Secretary of the responsible
7、 BSI Technical Committee at British Standards House, 389 Chiswick High Road, London W4 4AL.The UK participation in its preparation was entrusted to Technical Committee FSH/21, Reaction to fire tests.A list of organizations represented on FSH/21 can be obtained on request to its secretary.This public
8、ation does not purport to include all the necessary provisions of a contract. Users are responsible for its correct application.Amendments issued since publicationAmd. No. Date CommentsLicensed Copy: Wang Bin, na, Thu Apr 19 08:04:59 GMT+00:00 2007, Uncontrolled Copy, (c) BSITECHNICAL SPECIFICATIONS
9、PCIFICATION TECHNIQUETECHNISCHE SPEZIFIKATIONCEN/TS 15447July 2006ICS 13.220.50English VersionMounting and fixing in reaction to fire tests under theConstruction Products DirectiveMontage et fixation en raction des essais au feu dans lecadre de la DPCEinbau und Besfestigung bei Prfungen zumBrandverh
10、alten von Bauprodukten, die unter dieBauproduktenrichtlinie fallenThis Technical Specification (CEN/TS) was approved by CEN on 20 May 2006 for provisional application.The period of validity of this CEN/TS is limited initially to three years. After two years the members of CEN will be requested to su
11、bmit theircomments, particularly on the question whether the CEN/TS can be converted into a European Standard.CEN members are required to announce the existence of this CEN/TS in the same way as for an EN and to make the CEN/TS availablepromptly at national level in an appropriate form. It is permis
12、sible to keep conflicting national standards in force (in parallel to the CEN/TS)until the final decision about the possible conversion of the CEN/TS into an EN is reached.CEN members are the national standards bodies of Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France,Ger
13、many, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania,Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.EUROPEAN COMMITTEE FOR STANDARDIZATIONCOMIT EUROPEN DE NORMALISATIONEUROPISCHES KOMITEE FR NORMUNGMan
14、agement Centre: rue de Stassart, 36 B-1050 Brussels 2006 CEN All rights of exploitation in any form and by any means reservedworldwide for CEN national Members.Ref. No. CEN/TS 15447:2006: ELicensed Copy: Wang Bin, na, Thu Apr 19 08:04:59 GMT+00:00 2007, Uncontrolled Copy, (c) BSI2 Contents Page Fore
15、word. 3 Introduction 4 1 Scope 5 2 Normative references . 5 3 Terms and definitions or descriptions 5 4 General approach 8 4.1 Mounting and fixing of products in tests representing the end-use applications. 8 4.2 Classification not representative of performance in end-use application 9 4.3 Other way
16、s of classifications 9 4.4 Product parameters and end-use application parameters . 9 5 Testing to EN 13823 10 5.1 Test specimen and mounting 10 5.2 Fixings/attachments and supports . 11 5.3 Substrates 13 5.4 Air-gaps/cavities . 16 5.5 Edges 17 5.6 Joints 18 5.7 Product orientation. 20 5.8 Exposure t
17、o thermal attack 21 5.9 Mounting and fixing for specific products and/or end use applications 22 6 Testing to EN ISO 11925-2 . 22 6.1 Test specimen and mounting 22 6.2 Fixings/attachments and supports . 23 6.3 Substrates 24 6.4 Air-gaps/cavities . 27 6.5 Edges 28 6.6 Joints 28 6.7 Product orientatio
18、n. 29 6.8 Exposure to thermal attack 30 6.9 Mounting and fixing for specific products and/or end use applications 30 7 Testing to EN ISO 9239-1 . 31 7.1 Test specimen and mounting 31 7.2 Fixings/attachments and supports . 31 7.3 Substrates 32 7.4 Air-gaps/cavities . 34 7.5 Edges 34 7.6 Joints 35 7.7
19、 Product orientation. 36 7.8 Exposure to thermal attack 37 7.9 Mounting and fixing for specific products and/or end use applications 37 Annex A Figures. 38 Bibliography . 40 CEN/TS 15447:2006Licensed Copy: Wang Bin, na, Thu Apr 19 08:04:59 GMT+00:00 2007, Uncontrolled Copy, (c) BSI3 Foreword This Te
20、chnical Specification (CEN/TS 15447:2006) has been prepared by Technical Committee CEN/TC 127 “Fire safety in buildings”, the secretariat of which is held by BSI. This Technical Specification has been prepared by ad hoc working group 40 (“Mounting and fixing in reaction to fire tests”) of Technical
21、Committee CEN/TC 127 (“Fire safety in buildings”). This document has been prepared on request of the CEC as support for CEN Technical Committees involved in the production of technical specifications under the Construction Products Directive (CPD). According to the CEN/CENELEC Internal Regulations,
22、the national standards organizations of the following countries are bound to announce this CEN Technical Specification: Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, N
23、orway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom. CEN/TS 15447:2006Licensed Copy: Wang Bin, na, Thu Apr 19 08:04:59 GMT+00:00 2007, Uncontrolled Copy, (c) BSI4 Introduction The Essential Requirements of the CPD apply to the construction works. Inter
24、pretative documents have been produced to form a link between the Essential Requirements and the performance characteristics of construction products incorporated in a permanent manner in construction works, i.e. in end-use application1. The Essential Requirement concerned in this document is “Safet
25、y in case of fire”, and from that requirement the reaction to fire performance of construction products only is considered. Technical specifications under the CPD, such as product standards, deal with construction products and their reaction to fire performance. For the assessment of reaction to fir
26、e performance the technical specifications use a set of supporting fire standards through reference to the classification standard EN 13501-1. Five reaction to fire test methods have been developed for the purpose of testing construction products, including products incorporated within building elem
27、ents. The procedure for classification is outlined in EN 13501-1 providing a choice of Euroclasses. Since EN ISO 1182 (“non-combustibility”) and EN ISO 1716 (“gross calorific potential”) deal with material characteristics and are thus independent of the end-use application of the product, the mounti
28、ng and fixing2instructions presented apply to EN 13823, EN ISO 9239-1 and EN ISO 11925-2. Technical specifications refer to EN 13501-1 for the assessment of reaction to fire performance. The EN 13501-1 refers to the five supporting test standards for determination of the relevant parameters. In prin
29、ciple a product standard should not refer directly to the test standards. However, where EN 13501-1 and the test standards do not fully define the mounting and fixing of a product in a test, the relevant product standard may add instructions to ensure that the test result is representative of the pr
30、oduct behaviour in one or more end-use applications when exposed to a fire in the relevant fire scenario. In the absence of standard mounting and fixing rules, a test result is only valid for the end-use application that is represented by the mounting and fixing (and other test configuration aspects
31、) used in the test3. As a consequence all other end-use applications have to be tested. EN 13501-1, test standards and substrate standard EN 13238 contain some aspects of standardised mounting and fixing, to some degree limiting the number of tests to be performed to classify a product, which can le
32、ad to CE-marking. To limit the number of tests further, standardised mounting and fixing test arrangements may be introduced in the technical specifications. This may reduce the number of m (b) a product (a combination of one or more materials) without taking into account the incorporation of the pr
33、oduct in the building; or (c) a product in its end-use application (i.e. taking into account the incorporation of the product in the building). This frame work should be used by technical specification writers to develop further specific rules for product groups. 1In some documents “end-use applicat
34、ion” is used as a global indication of the use of the product (e.g. use as wall lining or ceiling lining). The more detailed description of the way the product is incorporated in the building in the (global) “end-use application” is then referred to as “end-use condition” (including e.g. jointing, f
35、ixing and position in relation to adjacent products). In this document the two terms are both covered by “end-use application”, in line with the definition given in EN 13501-1. 2In this document “mounting and fixing” is often abbreviated as “m mounting the applicability of the resulting classificati
36、on is likely to be limited (to the end-use application(s) represented by the chosen m density; colour; surface coating; composition of product; geometry and structure, e.g. shape, number and composition of layers; substrate; method of fixing; joints, type and position; air gaps; CEN/TS 15447:2006Lic
37、ensed Copy: Wang Bin, na, Thu Apr 19 08:04:59 GMT+00:00 2007, Uncontrolled Copy, (c) BSI10 edges; product orientation; exposure to thermal attack. The parameters of this list that may be part of the m this may damage fixings and may open joints. Thin products in contact with a support may lose a sig
38、nificant amount of heat to the support limiting the progress of the flame front. CEN/TS 15447:2006Licensed Copy: Wang Bin, na, Thu Apr 19 08:04:59 GMT+00:00 2007, Uncontrolled Copy, (c) BSI12 5.2.2 Rules in the reaction to fire standards EN 13501-1:2002, 6.3 and 13: “Typical positions in relation to
39、 other products” (than floorings) “are for example: Free standing: without any product immediately behind or in front of it. In this case the product shall be tested free standing with an appropriate support. On a substrate: glued, mechanically fastened or simply in contact. In this case the product
40、 shall be tested with a substrate and fastening representing the end use application.” “Taking into account the role of the substrates and the fixings on the potential contribution of a product to a fire, a single product may be classified in different classes as a function of its end use applicatio
41、n. If only one end use is envisaged, only that end use shall be tested.” “The applicability of test results obtained for products attached to a substrate is limited to the method of attachment used in the test. If generic adhesives are used, the results apply for all adhesives of the same type, appl
42、ied in similar quantities. Generic refers to adhesives giving the same or higher reaction to fire classification to the product in question, as that tested. Subject to the above, generic may also apply to adhesives of a defined type (e.g. polyvinylpyrolidone, polyvinylacetate). If specific adhesives
43、 are used. the results apply only for the specific adhesives.” EN 13238:2001, 5.2: “The method of attachment, e.g, adhesive, shall be representative of end-use application. The method of attachment in end-use practice shall be reproduced in the preparation of the specimen for test i.e. end-use adhes
44、ive and end-use quantities etc. If the order in which the attachments are conducted is known, this shall also be reproduced in the test specimen e.g. if the adhesive is applied to the substrate and not to the surface product in practice, then it shall be applied to the substrate during test specimen
45、 preparation. The same or greater time for curing and drying as used in end-use practice shall also be allowed.” EN 13823:2002, 5.2.2: “Boards that are fixed mechanically to a substrate in the end use application shall be tested fixed to a substrate using appropriate fixings. Fixings that stick out
46、of the specimen surface shall be placed in such a way that the specimen wing can be placed against the U-profile at the bottom and against the other specimen wing at its side, over its full length.” “Products that in their end use application are glued to a substrate shall be tested glued to a subst
47、rate.” 5.2.3 Recommendations All products The method of fixing should be specified in any m&f test arrangement used. It should consist of at least the composition, type, size, position and number of fixings and including the position of supporting elements like battens. If no influence of the fixing
48、 to the reaction to fire performance is expected and a product does not collapse or distort during testing, the test specimen should just be mechanically pressed by the backing board against the U-profiles of the SBI-apparatus. CEN/TS 15447:2006Licensed Copy: Wang Bin, na, Thu Apr 19 08:04:59 GMT+00
49、:00 2007, Uncontrolled Copy, (c) BSI13 Free standing products For rigid free standing products which can stand without support and which are expected not to collapse during test, distance holders should be used between the product and the backing board and the product should be held only at the periphery of the product. For the following free standing products a supporting frame and spacers should be used (the supporting frame should be representative of the end-use application): those supported in end-use, those expected to collapse, fall apar