1、raising standards worldwideNO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAWBSI Standards PublicationBS EN 13084-7:2012Free-standing chimneysPart 7: Product specifications of cylindricalsteel fabrications for use in single wall steelchimneys and steel linersCopyright European Co
2、mmittee for Standardization Provided by IHS under license with CENNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-BS EN 13084-7:2012 BRITISH STANDARDNational forewordThis British Standard is the UK implementation of EN 13084-7:2012.It supersedes BS EN 13084-7:2005
3、which is withdrawn.The UK participation in its preparation was entrusted to TechnicalCommittee B/506/14, Structural Chimneys and Flues.A list of organizations represented on this committee can beobtained on request to its secretary.This publication does not purport to include all the necessaryprovis
4、ions of a contract. Users are responsible for its correctapplication. The British Standards Institution 2013. Published by BSI StandardsLimited 2013ISBN 978 0 580 71230 2ICS 91.060.40Compliance with a British Standard cannot confer immunity fromlegal obligations.This British Standard was published u
5、nder the authority of theStandards Policy and Strategy Committee on 31 May 2013.Amendments issued since publicationDate Text affectedCopyright European Committee for Standardization Provided by IHS under license with CENNot for ResaleNo reproduction or networking permitted without license from IHS-,
6、-,-BS EN 13084-7:2012EUROPEAN STANDARD NORME EUROPENNE EUROPISCHE NORM EN 13084-7 December 2012 ICS 91.060.40 Supersedes EN 13084-7:2005English Version Free-standing chimneys - Part 7: Product specifications of cylindrical steel fabrications for use in single wall steel chimneys and steel liners Che
7、mines autoportantes - Partie 7: Spcifications de produit applicables aux fabrications cylindriques en acier pour chemines en acier paroi simple et parois intrieures en acier Freistehende Schornsteine - Teil 7: Produktfestlegungen fr zylindrische Stahlbauteile zur Verwendung in einschaligen Stahlscho
8、rnsteinen und Innenrohren aus StahlThis European Standard was approved by CEN on 27 October 2012. CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to
9、-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN member. This European Standard exists in three official versions (English, French, German). A version in any other language made by translat
10、ion under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same status as the official versions. CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland,
11、Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United Kingdom. EUROPEAN COMMITTEE FOR STANDARDIZATION CO
12、MIT EUROPEN DE NORMALISATION EUROPISCHES KOMITEE FR NORMUNG Management Centre: Avenue Marnix 17, B-1000 Brussels 2012 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 13084-7:2012: ECopyright European Committee for Standardization P
13、rovided by IHS under license with CENNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-BS EN 13084-7:2012EN 13084-7:2012 (E) 2 Contents Page Foreword 41 Scope 52 Normative references 53 Terms and definitions .54 Requirements .64.1 General 64.2 Performance characteris
14、tics 64.2.1 Mechanical resistance and stability.64.2.2 Resistance to fire .64.2.3 Gas tightness/Leakage 64.2.4 Flow resistance 64.2.5 Dimensioning/Thermal resistance .64.2.6 Thermal shock resistance .64.2.7 Resistance to freeze-thaw .74.3 Durability 74.4 Dangerous substances .75 Materials .75.1 Stee
15、ls 75.2 Coating . 125.3 Insulation . 125.4 Cladding . 126 Construction 126.1 Tolerances . 126.2 Welding 126.3 Construction details . 126.4 Insulation . 126.5 Cladding . 137 Evaluation of conformity 137.1 General . 137.1.1 Introduction . 137.1.2 Initial type testing . 137.1.3 Further type testing 137
16、.2 Factory production control 137.2.1 General . 137.2.2 Material records 147.2.3 Qualifications of the welders . 147.2.4 Welding quality control 147.2.5 Coatings . 147.2.6 Geometrical dimensions 148 Temperature classes 159 Product designation . 15Annex A (normative) Assessment of factory production
17、control . 16A.1 General . 16A.2 Initial inspection 16A.3 Continuous surveillance 16A.4 Frequency of inspection 17A.4.1 General . 17A.4.2 Surveillance intervals . 17A.4.3 Declaration of manufacturer 17A.4.4 Measures in non-compliance 17A.5 Reports 17Copyright European Committee for Standardization Pr
18、ovided by IHS under license with CENNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-BS EN 13084-7:2012EN 13084-7:2012 (E) 3 Annex ZA (informative) Clauses of this European Standard addressing the provisions of the EU Construction Products Directive . 18Bibliography
19、 24Copyright European Committee for Standardization Provided by IHS under license with CENNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-BS EN 13084-7:2012EN 13084-7:2012 (E) 4 Foreword This document (EN 13084-7:2012) has been prepared by Technical Committee CEN/T
20、C 297 “Free-standing industrial chimneys”, the secretariat of which is held by DIN. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by June 2013, and conflicting national standards shall be withdrawn
21、 at the latest by June 2013. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN and/or CENELEC shall not be held responsible for identifying any or all such patent rights. This document supersedes EN 13084-7:2005. This document h
22、as been prepared under a mandate given to CEN by the European Commission and the European Free Trade Association, and supports essential requirements of EU Directive(s). For relationship with EU Directive(s), see informative Annex ZA, which is an integral part of this document. Compared with EN 1308
23、4-7:2005, the following changes have been made: a) Corrigendum of 2008 was incorporated; b) 6.2 was revised; c) 7.2.4 was revised. This European Standard, EN 13084, Free-standing chimneys, consists of the following parts: Part 1: General requirements; Part 2: Concrete chimneys; Part 4: Brick liners
24、Design and execution; Part 5: Material for brick liners Product specifications; Part 6: Steel liners Design and execution; Part 7: Product specifications of cylindrical steel fabrications for use in single wall steel chimneys and steel liners (the present document); Part 8: Design and execution of m
25、ast construction with satellite components. The following European Standard additionally applies: EN 1993-3-2, Eurocode 3: Design of steel structures Part 3-2: towers, masts and chimneys Chimneys. According to the CEN/CENELEC Internal Regulations, the national standards organisations of the followin
26、g countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norw
27、ay, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom. Copyright European Committee for Standardization Provided by IHS under license with CENNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-BS EN 13084-7:2012EN
28、 13084-7:2012 (E) 5 1 Scope This European Standard deals with steel products for single wall steel chimneys and liners which are produced either in series or as single items. It is a product standard which specifies the performance requirements of cylindrical steel fabrications for use in single wal
29、l steel chimneys and steel liners for free-standing chimneys used to convey the flue gas to the outside atmosphere. It also specifies the requirements for insulation and cladding being part of the single wall steel chimney and liner. It provides for the evaluation of conformity of single wall steel
30、chimneys and liners to this European Standard. 2 Normative references The following documents, in whole or in part, are normatively referenced in this document and are indispensable for its application. For dated references, only the edition cited applies. For undated references, the latest edition
31、of the referenced document (including any amendments) applies. EN 287-1, Qualification test of welders Fusion welding Part 1: Steels EN 1090-2, Execution of steel structures and aluminium structures Part 2: Technical requirements for steel structures EN 1418, Welding personnel Approval testing of we
32、lding operators for fusion welding and resistance weld setters for fully mechanized and automatic welding of metallic materials EN 1993-1-6, Eurocode 3 Design of steel structures Part 1-6: Strength and Stability of Shell Structures EN 1993-3-2, Eurocode 3 Design of steel structures Part 3-2: Towers,
33、 masts and chimneys Chimneys EN 10025-2, Hot rolled products of structural steels Part 2: Technical delivery conditions for non-alloy structural steels EN 10025-5, Hot rolled products of structural steels Part 5: Technical delivery conditions for structural steels with improved atmospheric corrosion
34、 resistance EN 10028-2, Flat products made of steels for pressure purposes Part 2: Non-alloy and alloy steels with specified elevated temperature properties EN 10088-2, Stainless steels Part 2: Technical delivery conditions for sheet/plate and strip of corrosion resisting steels for general purposes
35、 EN 10095, Heat resisting steels and nickel alloys EN 10204, Metallic products Types of inspection documents EN 13084-1:2007, Free-standing chimneys Part 1: General requirements EN 13084-6:2004, Free-standing chimneys Part 6: Steel liners Design and execution EN ISO 5817, Welding Fusion-welded joint
36、s in steel, nickel, titanium and their alloys (beam welding excluded) Quality levels for imperfections (ISO 5817:2003, corrected version:2005, including Technical Corrigendum 1:2006) 3 Terms and definitions For the purposes of this document, the terms and definitions given in EN 13084-1:2007 and EN
37、13084-6:2004 apply. The single wall steel chimney and steel liner should be considered in the same way for design and requirements. Copyright European Committee for Standardization Provided by IHS under license with CENNot for ResaleNo reproduction or networking permitted without license from IHS-,-
38、,-BS EN 13084-7:2012EN 13084-7:2012 (E) 6 4 Requirements 4.1 General For the purposes of this document, EN 13084-6 applies. The products of single wall steel chimney and liner manufactured in accordance with this European Standard shall comply with the requirements given in EN 13084-1 and EN 1993-3-
39、2. The design of steel chimneys should be covered by the Eurocodes dealing with chimneys and the requirements should be based on design and intended end use. 4.2 Performance characteristics 4.2.1 Mechanical resistance and stability Mechanical resistance and stability shall be verified in accordance
40、with EN 1993-3-2 taking into account the characteristic values given in Tables 1 to 3 in this standard. 4.2.2 Resistance to fire Resistance to fire relates only to a soot-fire occurring within the chimney. A chimney could convey air and/or different type of gases (see EN 13084-1). Soot-fire resistan
41、ce shall only be verified for products conveying within the flue gas emitted for solid combustibles. The resistance to fire shall be verified in accordance with EN 13084-6. If the product has been designed to be soot fire resistant, the product designation is “G”, otherwise the designation is “O”. 4
42、.2.3 Gas tightness/Leakage The product shall be gas tight and the class H0 shall be declared in accordance with EN 13084-6. In order to meet this requirement, the design shall be in accordance with EN 13084-6, and the manufacture shall be in accordance with the qualities and controls stated in this
43、standard. 4.2.4 Flow resistance The mean roughness value for steel to carry out flow calculations shall be declared in accordance with EN 13084-1:2007, Table A.3. The individual resistance coefficient of some forms is given in EN 13084-1:2007, Table A.4. 4.2.5 Dimensioning/Thermal resistance Flow ca
44、lculations shall be carried out in accordance with EN 13084-1. The thermal resistance shall be calculated on the basis of EN 13084-1:2007, A.2.2. NOTE Dimensions related to stability are calculated on the basis of 4.2.1. 4.2.6 Thermal shock resistance Generally, thermal shock resistance is not appli
45、cable to steel because rapid changes of temperature have no significant effect on steel chimneys and liners. For specific applications (such as turbines) thermal shock may be relevant and expert advice should be sought. Copyright European Committee for Standardization Provided by IHS under license w
46、ith CENNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-BS EN 13084-7:2012EN 13084-7:2012 (E) 7 4.2.7 Resistance to freeze-thaw Resistance to freeze-thaw is not relevant to steel chimneys and steel liners. 4.3 Durability The class of chemical attack shall be declare
47、d in accordance with EN 13084-1. Durability to chemical attack is covered by use of materials shown in Table 4. Other steels may be used provided their durability to the relevant chemical attack is demonstrated. Durability may also be achieved by other means including additional coatings and linings
48、. 4.4 Dangerous substances National regulations on dangerous substances may require verification and declaration on release, and sometimes content, when construction products covered by this standard are placed on those markets. In the absence of European harmonised test methods, verification and declaration on release/content should be carried out, taking into account national provisions in the place of use. NOTE An informative database covering European and national provis