1、raising standards worldwideNO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAWBSI Standards PublicationBS EN 13823:2010Reaction to fire tests forbuilding products Buildingproducts excluding flooringsexposed to the thermal attackby a single burning itemLicensed Copy: Wang Bin, ISO/
2、EXCHANGE CHINA STANDARDS, 12/01/2011 06:54, Uncontrolled Copy, (c) BSIBS EN 13823:2010 BRITISH STANDARDNational forewordThis British Standard is the UK implementation of EN 13823:2010. Itsupersedes BS EN 13823:2002 which is withdrawn.The UK participation in its preparation was entrusted to Technical
3、Committee FSH/21/7, Reaction to fire tests - Large and intermediatescale tests.A list of organizations represented on this committee can beobtained on request to its secretary.This publication does not purport to include all the necessaryprovisions of a contract. Users are responsible for its correc
4、tapplication. BSI 2010 ISBN 978 0 580 68815 7 ICS 13.220.50; 91.060.01; 91.100.01 Compliance with a British Standard cannot confer immunity fromlegal obligations.This British Standard was published under the authority of theStandards Policy and Strategy Committee on 31 October 2010. Amendments issue
5、d since publicationDate T e x t a f f e c t e dLicensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 12/01/2011 06:54, Uncontrolled Copy, (c) BSIBS EN 13823:2010EUROPEAN STANDARD NORME EUROPENNE EUROPISCHE NORM EN 13823 July 2010 ICS 13.220.50; 91.060.01; 91.100.01 Supersedes EN 13823:2002English V
6、ersion Reaction to fire tests for building products - Building products excluding floorings exposed to the thermal attack by a single burning item Essais de raction au feu des produits de construction - Produits de construction lexclusion des revtements de sol exposs une sollicitation thermique prov
7、oque par un objet isol en feu Prfungen zum Brandverhalten von Bauprodukten - Thermische Beanspruchung durch einen einzelnen brennenden Gegenstand fr Bauprodukte mit Ausnahme von Bodenbelgen This European Standard was approved by CEN on 25 June 2010. CEN members are bound to comply with the CEN/CENEL
8、EC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN Management Centre or to any
9、CEN member. This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as the official versions. C
10、EN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia,
11、 Spain, Sweden, Switzerland and United Kingdom. EUROPEAN COMMITTEE FOR STANDARDIZATION COMIT EUROPEN DE NORMALISATION EUROPISCHES KOMITEE FR NORMUNG Management Centre: Avenue Marnix 17, B-1000 Brussels 2010 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN nation
12、al Members. Ref. No. EN 13823:2010: ELicensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 12/01/2011 06:54, Uncontrolled Copy, (c) BSIBS EN 13823:2010EN 13823:2010 (E) 2 Contents Page Foreword . 4 Introduction 5 1 Scope 6 2 Normative references . 6 3 Terms and definitions . 6 4 Test facility 7 4.1
13、 General . 7 4.2 Test room . 7 4.3 Materials . 10 4.4 Test apparatus . 10 4.5 Smoke exhaust system 12 4.6 General measurement section equipment . 12 4.7 Other general equipment 13 5 Test specimen . 14 5.1 Dimensions of specimen 14 5.2 Mounting of specimen 14 5.2.1 Mounting as in end use application
14、14 5.2.2 Standard mounting . 14 5.3 Installation of the specimen wings in the trolley . 16 5.4 Number of specimens. 17 6 Conditioning 17 7 Principle . 17 8 Test procedure 18 8.1 General . 18 8.2 Testing operations 18 8.3 Visual observation and manual recording of data 19 8.3.1 General . 19 8.3.2 Pre
15、-test conditions 19 8.3.3 Lateral flame spread on the long wing . 19 8.3.4 Flaming particles or droplets . 19 8.3.5 End of test conditions 21 8.3.6 Recorded events . 21 8.4 Automated recording of data . 21 8.5 Early termination of test . 22 9 Expression of results 22 10 Test report . 22 Annex A (nor
16、mative) Calculation procedures . 24 A.1 General . 24 A.1.1 General remarks 24 A.1.2 Calculations to be performed on the test data 25 A.1.3 Calculations to be performed on calibration data . 25 A.1.4 Standard data set 25 A.2 Synchronization of data . 25 A.3 Checking equipment response 27 A.3.1 Temper
17、ature readings 27 A.3.2 Drift in gas concentration measurement 27 A.3.3 Drift in light attenuation measurement . 27 Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 12/01/2011 06:54, Uncontrolled Copy, (c) BSIBS EN 13823:2010EN 13823:2010 (E) 3 A.4 Exposure period 28 A.5 Heat output 28 A.5.1 C
18、alculation of heat release rate (HRR) 28 A.5.2 Calculation of THR(t) and THR600s. 31 A.5.3 Calculation of FIGRA0,2MJand FIGRA0,4MJ(fire growth rate indices) 32 A.6 Smoke production . 33 A.6.1 Calculation of smoke production rate (SPR) . 33 A.6.2 Calculation of TSP(t) and TSP600s36 A.6.3 Calculation
19、of SMOGRA (smoke growth rate index) . 36 A.7 Calculations for calibrations Propane heat release . 37 Annex B (informative) Precision of test method . 38 B.1 General remarks and results . 38 B.2 Calculation of test results 39 B.3 Statistical analysis 39 B.4 Statistical results 39 Annex C (normative)
20、Calibration procedures 43 C.1 Procedures for separate pieces of equipment . 43 C.1.1 General . 43 C.1.2 Oxygen analyser adjustment . 43 C.1.3 Oxygen analyser output noise and drift . 43 C.1.4 Carbon dioxide analyser adjustment 44 C.1.5 Check of propane mass flow controller 44 C.1.6 Light system cali
21、bration . 44 C.2 System response calibrations . 45 C.2.1 Burner switch response time . 45 C.2.2 Burner heat output step calibration 47 C.2.3 Heptane calibration . 50 C.2.4 Velocity profile factor kt,v52 C.2.5 Flow factor kt. 54 Annex D (informative) Calibration procedures 55 D.1 Procedures for separ
22、ate pieces of equipment . 55 D.1.1 General . 55 D.1.2 Oxygen analyser adjustment . 55 D.1.3 Carbon dioxide analyser adjustment 55 D.1.4 Check of propane mass flow controller 55 D.1.5 Optical filter check 56 D.2 Check of the thermal attack on the specimens . 57 D.2.1 General . 57 D.2.2 Procedure 57 A
23、nnex E (normative) Design drawings . 58 Annex F (informative) Data file format 93 Annex G (informative) Record sheet 96 Bibliography . 97 Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 12/01/2011 06:54, Uncontrolled Copy, (c) BSIBS EN 13823:2010EN 13823:2010 (E) 4 Foreword This document (EN
24、13823:2010) has been prepared by Technical Committee CEN/TC 127 “Fire safety in buidlings”, the secretariat of which is held by BSI. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by January 2011, a
25、nd conflicting national standards shall be withdrawn at the latest by January 2011. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN and/or CENELEC shall not be held responsible for identifying any or all such patent rights. Th
26、is document supersedes EN 13823:2002. This document has been prepared under a mandate given to CEN by the European Commission and the European Free Trade Association, and supports essential requirements of EU Directive(s). According to the CEN/CENELEC Internal Regulations, the national standards org
27、anizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, P
28、ortugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom. Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 12/01/2011 06:54, Uncontrolled Copy, (c) BSIBS EN 13823:2010EN 13823:2010 (E) 5 Introduction The classification of the reaction to fire performance of const
29、ruction products established by EC Decision 2000/147/EC (OJEU L50 of 23.2.2000) defines in Table 1 the reaction to fire classes for building products excluding floorings. The relevant test methods for determining the reaction to fire are being prepared by CEN/TC 127. Safety warning The attention of
30、all persons concerned with managing and carrying out the tests described in this standard is drawn to the fact that fire testing can be hazardous and that toxic and/or harmful smoke and gases can be produced during the test. An assessment of all potential hazards and risks to health should be made a
31、nd safety precautions should be identified and provided. Smoke and gases should be removed from the workplace. Written safety instructions should be issued. Appropriate training should be given to relevant personnel. Laboratory personnel should ensure that they follow written safety instructions at
32、all times. Special precautions are required for the propane gas supply system. The equipment, for example tubes, couplings, flow meters, should be approved for propane. The burner should be equipped with a remote-controlled ignition device, for example a pilot flame or a glow wire. There should be a
33、 warning system for leaking gas and a valve for immediate and automatic cut-off of the gas supply in case of extinction of the ignition flame. The pilot flames can be ignited directly by an operator in the test room, however, no one should be present in the test room during ignition of a burner. It
34、should be possible to operate the switch between auxiliary and main (primary) burner and the preceding main valve (to open or stop the propane supply) from outside the test room. Special precautions are required for the extinction of burning specimens. When the extinction is carried out because of i
35、ntensive combustion of the specimens, it is recommended that a second operator is ready to intervene. Means for extinguishing should be available (e.g. since the heat output during intensive combustion can damage the apparatus). Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 12/01/2011 06:54
36、, Uncontrolled Copy, (c) BSIBS EN 13823:2010EN 13823:2010 (E) 6 1 Scope This European Standard specifies a method of test for determining the reaction to fire performance of construction products excluding floorings, and excluding products which are indicated in Table 1 of EC Decision 2000/147/EC, w
37、hen exposed to thermal attack by a single burning item (SBI). The calculation procedures are given in Annex A. Information on the precision of the test method is given in Annex B. The calibration procedures are given in Annexes C and D, of which C is a normative annex. NOTE This European Standard ha
38、s been developed to determine the reaction to fire performance of essentially flat products. The treatment of some families of products, e.g. linear products (pipes, ducts, cables etc.), can need special rules. 2 Normative references The following referenced documents are indispensable for the appli
39、cation of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 13238, Reaction to fire tests for building products Conditioning procedures and general rules for selection of s
40、ubstrates EN 13501-1:2007+A1:2009, Fire classification of construction products and building elements Part 1: Classification using data from reaction to fire tests EN 60584-1:1995, Thermocouples Part 1: Reference tables (IEC 60584-1:1995) EN ISO 13943:2000, Fire safety Vocabulary (ISO 13943:2000) 3
41、Terms and definitions For the purposes of this document, the terms and definitions given in EN ISO 13943:2000 and EN 13501-1:2007+A1:2009 and the following apply. 3.1 backing board calcium silicate panel used to back the specimen that can be placed directly against a free-standing test specimen or a
42、t a distance from it 3.2 specimen piece of a product, which is to be tested NOTE This can include the mounting technique used in its end-use application. This also can include an air gap and/or a substrate where appropriate. 3.3 substrate product which is used immediately beneath the product about w
43、hich information is required 3.4 THR600stotal heat release from the specimen in the first 600 s of exposure to the main (primary) burner flames Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 12/01/2011 06:54, Uncontrolled Copy, (c) BSIBS EN 13823:2010EN 13823:2010 (E) 7 3.5 LFS lateral flame
44、 spread on the long specimen wing NOTE The LFS is defined in more detail in 8.3.3. 3.6 TSP600stotal smoke production from the specimen in the first 600 s of exposure to the main (primary) burner flames 3.7 FIGRA0,2 MJmaximum of the quotient of heat release rate from the specimen and the time of its
45、occurrence using a THR-threshold of 0,2 MJ NOTE The FIGRA0,2 MJis described in more detail in A.5.3. 3.8 FIGRA0,4 MJmaximum of the quotient of heat release rate from the specimen and the time of its occurrence using a THR threshold of 0,4 MJ NOTE The FIGRA0,4 MJis described in more detail in A.5.3.
46、3.9 SMOGRA smoke growth rate maximum of the quotient of smoke production rate from the specimen and the time of its occurrence NOTE The SMOGRA is described in more detail in A.6.3. 3.10 sustained flaming persistence of flame on or over a surface for a minimum period of time EN ISO 13943:2000 4 Test
47、facility 4.1 General The SBI test facility shall consist of a test room, the test apparatus (trolley, frame, burners, hood, collector and ducting), the smoke exhaust system and general measuring equipment. These components are specified in 4.2 to 4.7. Design drawings are given in Annex E. Dimensions
48、 given in the drawings are nominal unless tolerances are given in the text. NOTE The air supply to the test room entering below the trolley should be fresh, uncontaminated air. 4.2 Test room 4.2.1 The test room shall have an inner height of (2,4 0,05) m and an inner floor area of (3,0 0,05) m in bot
49、h directions. The walls shall be made of stone type building blocks (e.g. cellular concrete), gypsum boards, calcium silicate boards or other boards classified as class A1 or A2. 4.2.2 One wall of the test room shall have an opening to insert the trolley from the surrounding laboratory into the test room. The opening shall be at least 1 470 mm wide and 2 450 mm high (dimensions of the frame). Windows shall be placed in the two walls facing the front side of the two Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 12/01/2011 06:54, Uncontrolled Copy
copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
备案/许可证编号:苏ICP备17064731号-1