1、BSI Standards PublicationBS EN 15218:2013Air conditioners and liquidchilling packages withevaporatively cooledcondenser and with electricallydriven compressors for spacecooling Terms, definitions,test conditions, test methodsand requirementsBS EN 15218:2013 BRITISH STANDARDNational forewordThis Brit
2、ish Standard is the UK implementation of EN 15218:2013. Itsupersedes BS EN 15218:2006 which is withdrawn.The UK participation in its preparation was entrusted to TechnicalCommittee RHE/17, Testing of air conditioning units.A list of organizations represented on this committee can beobtained on reque
3、st to its secretary.This publication does not purport to include all the necessaryprovisions of a contract. Users are responsible for its correctapplication. The British Standards Institution 2013. Published by BSI StandardsLimited 2013ISBN 978 0 580 80673 5ICS 27.200; 91.140.30Compliance with a Bri
4、tish Standard cannot confer immunity fromlegal obligations.This British Standard was published under the authority of theStandards Policy and Strategy Committee on 31 August 2013.Amendments issued since publicationDate Text affectedBS EN 15218:2013EUROPEAN STANDARD NORME EUROPENNE EUROPISCHE NORM EN
5、 15218 July 2013 ICS 27.200; 91.140.30 Supersedes EN 15218:2006English Version Air conditioners and liquid chilling packages with evaporatively cooled condenser and with electrically driven compressors for space cooling - Terms, definitions, test conditions, test methods and requirements Climatiseur
6、s et groupes refroidisseurs de liquide condenseur refroidi par vaporation et compresseur entran par moteur lectrique pour la rfrigration des locaux - Termes, dfinitions, conditions dessai, mthodes dessai et exigences Luftkonditionierer und Flssigkeitskhlstze mit verdunstungsgekhltem Verflssiger und
7、elektrisch angetriebenen Verdichtern fr die Raumkhlung - Begriffe, Prfbedingungen, Prfverfahren und Anforderungen This European Standard was approved by CEN on 30 May 2013. CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this Europe
8、an Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN member. This European Standard exists in three official versions
9、(English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same status as the official versions. CEN members are the national standards bodies of Austria, Belg
10、ium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switze
11、rland, Turkey and United Kingdom. EUROPEAN COMMITTEE FOR STANDARDIZATION COMIT EUROPEN DE NORMALISATION EUROPISCHES KOMITEE FR NORMUNG Management Centre: Avenue Marnix 17, B-1000 Brussels 2013 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Re
12、f. No. EN 15218:2013: EBS EN 15218:2013EN 15218:2013 (E) 2 Contents Page Foreword 3 1 Scope 4 2 Normative references 4 3 Terms and definitions .5 4 Classification 5 5 Test conditions 6 5.1 Environmental conditions and electrical power supply requirements 6 5.2 Rating conditions.6 6 Rating capacity t
13、est 10 6.1 Basic principles 10 6.2 Test apparatus 10 6.2.1 Arrangement of the test apparatus . 10 6.2.2 Installation and connection of the test object . 11 6.3 Uncertainties of measurement 11 6.4 Test procedure 11 6.4.1 General . 11 6.4.2 Steady state condition . 11 6.4.3 Output measurement for unit
14、s with water tank . 12 6.4.4 Output measurement for units with continuous supply water circuit 13 6.4.5 Data to be recorded 13 7 Electrical consumptions for single duct and double duct units 14 7.1 Determination of power consumption due to standby mode 14 7.2 Determination of power consumption in of
15、f-mode . 14 7.3 Electricity consumption . 14 8 Air flow rate measurement of ducted units 14 9 Test report . 14 9.1 General information 14 9.2 Rating test results. 14 10 Requirements 15 11 Marking 15 12 Instructions . 16 Annex ZA (informative) Relationship between this European Standard and the requi
16、rements of Commission Regulation (EC) No 206/2012 17 BS EN 15218:2013EN 15218:2013 (E) 3 Foreword This document (EN 15218:2013) has been prepared by Technical Committee CEN/TC 113 “Heat pumps and air conditioning units”, the secretariat of which is held by AENOR. This European Standard shall be give
17、n the status of a national standard, either by publication of an identical text or by endorsement, at the latest by January 2014 and conflicting national standards shall be withdrawn at the latest by January 2014. Attention is drawn to the possibility that some of the elements of this document may b
18、e the subject of patent rights. CEN and/or CENELEC shall not be held responsible for identifying any or all such patent rights. This document supersedes EN 15218:2006. The main changes with respect to the previous edition are listed below: a) the addition of requirements related to the electrical co
19、nsumption and the air flow rate measurement of ducted units; b) the addition of a table template containing the test results of the ducted units; c) the addition of an Annex Z related to the Commission Regulation (EC) n206/2012. This document has been prepared under a mandate given to CEN by the Eur
20、opean Commission and the European Free Trade Association, and supports essential requirements of EU Directive(s). For relationship with EU Directive(s), see informative Annex ZA, which is an integral part of this document. Although this document has been be prepared in the frame of the commission re
21、gulation (EU) No 206/2012 implementing Directive 2009/125/EC with regard to ecodesign requirements for air conditioners and comfort fans, it is also intended to support the essential requirements of the European Directive 2010/30/CE. According to the CEN/CENELEC Internal Regulations, the national st
22、andards organisations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
23、 Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom. BS EN 15218:2013EN 15218:2013 (E) 4 1 Scope This European Standard specifies the terms, definitions, test conditions, test methods and requirements for r
24、ating the performance of air conditioners and liquid chilling packages, with electrically driven compressors and with evaporatively cooled condenser when used for space cooling. The evaporatively cooled condenser is cooled by air and by the evaporation of external additional water. This additional e
25、xternal water is fed by a specific water supply circuit or by a water tank. This European Standard does not apply to air-to-air and air-to-water air conditioners with a condenser cooled by air and by the evaporation of water condensed on their evaporator. This European Standard applies to units equi
26、pped with a water tank or with a continuous water circuit supply that can also operate without water feeding. However the standard only concerns the testing of these units with water feeding. This European Standard applies to factory-made units which can be ducted. This European Standard applies to
27、factory-made units of either fixed capacity or variable capacity by any means. Packaged units, single split and multisplit systems are covered by this European Standard. With regard to units consisting of several parts, this European Standard applies only to those designed and supplied as a complete
28、 package. Evaporatively cooled condenser units that can also operate in heating mode shall have their performance in this mode determined according to EN 14511. Installations used for industrial processes cooling are not within the scope of this European Standard. This European Standard specifies th
29、e conditions for which performance data shall be declared for compliance to the Ecodesign regulation 206/2012 and to the Energy Labelling regulation 626/2011 of air conditioners with evaporatively cooled condenser in cooling mode. NOTE All the symbols given in this text can be used regardless of lan
30、guage. 2 Normative references The following documents, in whole or in part, are normatively referenced in this document and are indispensable for its application. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including an
31、y amendments) applies. EN 14511-1:2013, Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling Part 1: Terms, definitions and classification EN 14511-2, Air conditioners, liquid chilling packages and heat pumps with electrically d
32、riven compressors for space heating and cooling Part 2: Test conditions EN 14511-3:2013, Air conditioners, liquid chilling packages and heat pumps with electrically driven compressors for space heating and cooling Part 3: Test methods EN 14511-4:2013, Air conditioners, liquid chilling packages and h
33、eat pumps with electrically driven compressors for space heating and cooling Part 4: Operating requirements, marking and instructions BS EN 15218:2013EN 15218:2013 (E) 5 3 Terms and definitions For the purposes of this document, the terms and definitions given in EN 14511-1:2013 and the following ap
34、ply. 3.1 evaporatively cooled condenser heat exchanger that condenses refrigerant vapour by rejecting heat to a water and air mixture causing the water to evaporate and increase the enthalpy of air Note 1 to entry: Desuperheating and sub-cooling of the refrigerant may also occur. 3.2 water tank tank
35、 designed as an integral part of the unit to contain external additional water which is fed to the evaporatively cooled condenser 3.3 continuous supply water circuit circuit designed as an integral part of the unit to feed continuously the evaporatively cooled condenser with water from an external w
36、ater source 3.4 effective power input PEaverage electrical power input of the unit within a defined interval of time obtained from: power input for operating the compressor; power input for all control and safety devices of the unit; power input of the circulating pump which provides water to the ev
37、aporatively cooled condenser, if any; proportional power input of the conveying devices (e.g. fans, pumps) for ensuring the transport of the heat transfer media inside the unit, expressed in Watt. Note 1 to entry: For the purposes of this standard the present definition replaces the one in EN 14511-
38、1 and is used to calculate the EER and EERrated. 3.5 cleaning cycle interval of time during which water is sprayed on the evaporatively cooled condenser in order to remove fouling and scale buildup 3.6 functioning cycle interval of time elapsed between the start of two successive cleaning cycles for
39、 evaporatively cooled condenser units with a continuous water supply 4 Classification If the heat transfer medium for the indoor heat exchanger is water, the unit shall be denominated as evaporatively cooled condenser liquid chilling package. If the heat transfer medium for the indoor heat exchanger
40、 is air, the unit shall be denominated as evaporatively cooled condenser air conditioner. BS EN 15218:2013EN 15218:2013 (E) 6 5 Test conditions 5.1 Environmental conditions and electrical power supply requirements The tests shall be carried out under the environmental conditions specified in Table 1
41、 or Table 2 based on the location of the unit. For all units, electrical power voltage and frequency shall be given by the manufacturer. Table 1 Environmental conditions for units designed for indoor installation Type Measured quantities Rating test Evaporatively cooled condenser liquid chilling pac
42、kages with duct connection on the air inlet and outlet side Dry bulb temperature 15 C to 30 C Evaporatively cooled condenser liquid chilling packages without duct connection on the air inlet side Dry bulb temperature Wet bulb temperature As air inlet temperatures, see Table 5 or Table 6 Evaporativel
43、y cooled condenser air conditioners with duct connection on the indoor air inlet and outlet side Dry bulb temperature 15 C to 30 C Evaporatively cooled condenser air conditioners without duct connection on the indoor air inlet and outlet side Dry bulb temperature Wet bulb temperature As air inlet te
44、mperatures, see Table 3 or Table 4 Table 2 Environmental conditions for units designed for outdoor installation Type Measured quantities Rating test Evaporatively cooled condenser liquid chilling packages Dry bulb temperature Wet bulb temperature As air inlet temperatures, see Table 5 and Table 6 Ev
45、aporatively cooled condenser air conditioners with duct connection on the indoor air inlet and outlet side Dry bulb temperature Wet bulb temperature As inlet temperatures, see Table 3 and Table 4 5.2 Rating conditions For the rating tests, the appropriate test conditions apply in accordance with Tab
46、le 3 and Table 4 for evaporatively cooled condenser air conditioners or with Table 5 and Table 6 for evaporatively cooled condenser liquid chilling packages. BS EN 15218:2013EN 15218:2013 (E) 7 Table 3 Evaporatively cooled condenser air conditioner with continuous water supply circuit Evaporatively
47、cooled condenser Indoor heat exchanger Air Water Inlet dry bulb temperature Inlet wet bulb temperature Inlet temperature Inlet dry bulb temperature Inlet wet bulb temperature C C C C C Standard rating conditions Comfort (outdoor air / recycled air) double duct 35 24 15 27 19 Comfort (exhaust air / r
48、ecycled air) 27 19 15 27 19 Comfort (exhaust air / outdoor air) 27 19 15 35 24 Single duct a, b35 24 15 35 24 Control cabinet 35 24 15 35 24 Close control 35 24 15 24 17 Application rating conditions Comfort (outdoor air / recycled air) double duct 27 19 15 21 15 Single duct 27 19 15 27 19 Comfort (
49、outdoor air / recycled air) double duct 46 24 15 29 19 Control cabinet 50 30 15 35 24 Close control 27 19 15 21 15 aWhen using the calorimeter room method, pressure equilibrium between indoor and outdoor compartments shall be obtained by introducing into indoor compartment, air at the same rating temperature conditions. bThe pressure difference between the two compartments of the calorimeter room shall not be greater than 1,25 Pa. This pressure equilibrium can be achieved by using an equalising device or by creating an open