1、Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 21/04/2008 08:05, Uncontrolled Copy, (c) BSIg49g50g3g38g50g51g60g44g49g42g3g58g44g55g43g50g56g55g3g37g54g44g3g51g40g53g48g44g54g54g44g50g49g3g40g59g38g40g51g55g3g36g54g3g51g40g53g48g44g55g55g40g39g3g37g60g3g38g50g51g60g53g44g42g43g55g3g47g36g58r
2、equirements, testing, markingThe European Standard EN 15270:2007 has the status of a British StandardICS 97.100.30Pellet burners for small heating boilers Definitions, BRITISH STANDARDBS EN 15270:2007BS EN 15270:2007Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 21/04/2008 08:05, Uncontrolle
3、d Copy, (c) BSIThis British Standard was published under the authority of the Standards Policy and Strategy Committee on 31 January 2008 BSI 2008ISBN 978 0 580 56069 9Amendments/corrigenda issued since publicationDate CommentsCompliance with a British Standard cannot confer immunity from legal oblig
4、ations.National forewordThis British Standard is the UK implementation of EN 15270:2007.The UK participation in its preparation was entrusted to Technical Committee RHE/10, Heating boilers.A list of organizations represented on this committee can be obtained on request to its secretary.This publicat
5、ion does not purport to include all the necessary provisions of a contract. Users are responsible for its correct application.EUROPEAN STANDARDNORME EUROPENNEEUROPISCHE NORMEN 15270December 2007ICS 97.100.30English VersionPellet burners for small heating boilers - Definitions,requirements, testing,
6、markingBrleurs granuls pour petites chaudires de chauffage -Dfinitions, exigences, essais, marquagePelletbrenner fr kleine Heizkessel - Definitionen,Anforderungen, Prfung, KennzeichnungThis European Standard was approved by CEN on 3 November 2007.CEN members are bound to comply with the CEN/CENELEC
7、Internal Regulations which stipulate the conditions for giving this EuropeanStandard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such nationalstandards may be obtained on application to the CEN Management Centre or to any CEN m
8、ember.This European Standard exists in three official versions (English, French, German). A version in any other language made by translationunder the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as theofficial versions.CEN member
9、s are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland,France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,Romania, Slovakia, Slovenia, Spain, Sweden, Swit
10、zerland and United Kingdom.EUROPEAN COMMITTEE FOR STANDARDIZATIONCOMIT EUROPEN DE NORMALISATIONEUROPISCHES KOMITEE FR NORMUNGManagement Centre: rue de Stassart, 36 B-1050 Brussels 2007 CEN All rights of exploitation in any form and by any means reservedworldwide for CEN national Members.Ref. No. EN
11、15270:2007: ELicensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 21/04/2008 08:05, Uncontrolled Copy, (c) BSIEN 15270:2007 (E) 2 Contents Page Foreword3 1 Scope 4 2 Normative references 4 3 Terms, definitions and symbols.4 4 Classification and groupings for pellet burners.8 5 Requirements.9 6 Tes
12、ting 16 7 Conformity evaluation.25 8 Marking .25 9 Operating instructions 25 10 Test report 27 Annex A (informative) Vocabulary.29 Annex B (informative) Fireproof non-metallic materials for pellet burners.32 Annex C (normative) Requirements for electronic burner start up functions and pellet-air rat
13、io controls34 Annex D (informative) Example of risk assessment to prevent back burning36 Annex E (informative) Example of risk assessment and the allocation of safety level for control functions using electronic devices for pellet burners38 Annex F (informative) Long term stability test (optional)40
14、 Annex G (informative) Measurement methods for some physical parameters.41 Annex H (normative) Determination of organic gaseous compounds content 44 Annex I (informative) Conformity evaluation46 Bibliography 49 Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 21/04/2008 08:05, Uncontrolled Cop
15、y, (c) BSIEN 15270:2007 (E) 3 Foreword This document (EN 15270:2007) has been prepared by Technical Committee CEN/TC 57 “Central heating boilers”, the secretariat of which is held by DIN. This European Standard shall be given the status of a national standard, either by publication of an identical t
16、ext or by endorsement, at the latest by June 2008, and conflicting national standards shall be withdrawn at the latest by June 2008. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN and/or CENELEC shall not be held responsible
17、for identifying any or all such patent rights. According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germ
18、any, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom. Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 21/04/2008 08:05, Uncontrolled Copy, (c)
19、BSIEN 15270:2007 (E) 4 1 Scope This European Standard relates to pellet burners having a maximum heat input of not more than 70 kW, intended for fitting with appropriate boilers for hot water, and intended for high quality pellets in accordance with CEN/TS 14961:2005 Annex A. This standard contains
20、requirements and test methods for safety, combustion quality, operating characteristics and maintenance of pellet burners and covers and also all external equipment that influences the safety systems. This standard also contains information on how to enable a correct match between pellet burner and
21、boiler. Pellet burners that are sold as a complete unit together with their own dedicated boilers are not covered. NOTE Other fuels will be considered in future amendments to this standard. 2 Normative references The following referenced documents are indispensable for the application of this docume
22、nt. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 230:2005, Automatic burner control systems for oil burners EN 298:2003, Automatic gas burner control systems for gas burners and gas
23、burning appliances with or without fans EN 12067-2:2004, Gas/air ratio controls for gas burners and gas burning appliances Part 2: Electronic types CEN/TS 14961:2005, Solid biofuels Fuel specifications and classes EN 15036-1, Heating boilers Test regulations for airborne noise emissions from heat ge
24、nerators Part 1: Airborne noise emissions from heat generators CEN/TS 15404, Solid recovered fuels Methods for the determination of ash melting behaviour by using characteristic temperatures prEN 15456, Heating boilers Electrical power consumption for heat generators System boundaries - Measurements
25、 EN 60335-2-102, Household and similar electrical appliances Safety Part 2-102: Particular requirements for gas, oil and solid-fuel burning appliances having electrical connections (IEC 60335-2-102:2004, modified) EN 60529, Degrees of protection provided by enclosures (IP code) (IEC 60529:1989) EN 6
26、0730-1:2002, Automatic electrical controls for household and similar use Part 1: General requirements (IEC 60730-1:1999,modified) EN 60730-2-5:2002, Automatic electrical controls for household and similar use Part 2-5: Particular requirements for automatic electrical burner control systems (IEC 6073
27、0-2-5:2000, modified) 3 Terms, definitions and symbols For the purpose of this standard, the following terms and definitions apply. NOTE For reference use only the equivalent terms in Danish, English, French, German and Swedish, are found in informative Annex A. Licensed Copy: Wang Bin, ISO/EXCHANGE
28、 CHINA STANDARDS, 21/04/2008 08:05, Uncontrolled Copy, (c) BSIEN 15270:2007 (E) 5 3.1 pellet burner device for burning pellets where the control can be of different types; on-off, mechanical, modulating or multi stage. The pellets can be fed horizontally, from above or from below 3.2 modulating burn
29、er burner where the throughput may be infinitely varied between the lower and upper limits 3.3 multistage burner burner where several firing stages can be utilised. Burners with only two firing rates are included in this category 3.4 ignition device device used to ignite the pellets in the burner he
30、ad of a pellet burner, it can be either manual, automatic or with a basic fire bed. The ignition can be caused by a hot air element, automatic ignition with liquid or gaseous fuels, electric coil or electric glow plug 3.5 basic fire bed quantity of glowing embers which ensures ignition of the test f
31、uel to be charged 3.6 conveyor system, auger, feed screw mechanical arrangement, normally incorporating a feed screw, used for transporting the pellets from the fuel hopper to the burner head 3.7 fuel hopper fuel store from which fuel is fed to the pellet burner 3.8 storage with external fuel hopper
32、 external fuel store from which fuel is fed to the pellet burner and which is separate from the pellet burner. It can be located either inside or outside the room where the pellet burner is located 3.9 storage with integral fuel hopper integral fuel store container from which fuel is fed to the pell
33、et burner and which is integral with the pellet burner 3.10 burner head part of a pellet burner where the pellets are burned 3.11 back burning situation in which the flames from the burning pellets in the burner head propagate and ignite the pellets in the conveyor system 3.12 temperature limiter sa
34、fety level B device that causes the safe shutdown and lockout of the fuel supply and/or the combustion air supply respectively if the limiter value exceeds a pre-set limit. According to EN 14597 it is a device of Type “TB” Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 21/04/2008 08:05, Unco
35、ntrolled Copy, (c) BSIEN 15270:2007 (E) 6 3.13 safety temperature limiter safety level C device that causes the safe shutdown and lockout of the fuel supply and/or the combustion air supply respectively if the limiter value exceeds a pre-set limit. According to EN 14597 it is a device of Type “STB”
36、3.14 sprinkle system safety device that allows small droplets of water to be released onto the pellets in the conveyor system if back burning occurs 3.15 drop chute sloping channel, through which the pellets fall from a conveyor system into a burner head or into moving equipment 3.16 cell feeder dev
37、ice that intermittently interrupts the fuel stream thus only allowing a small amount of pellets at a time to be supplied to the burner, thereby preventing the flue gases from reaching the hopper 3.17 fire damper mobile closure within a duct which is designed to prevent the passage of fire 3.18 combu
38、stion air supply air required by the pellet burner to ensure the safe and efficient combustion of pellets and supplied into the combustion chamber, which is entirely or partially used to burn the pellets in the burner head 3.19 ash discharge arrangement for removing the ash from the burner head or t
39、he combustion chamber which may be automatically controlled 3.20 non volatile lockout shutdown condition such that a restart can be accomplished only by a manual reset and by no other means 3.21 volatile lockout shutdown condition such that a restart can be accomplished by restoration of the electri
40、cal supply after its loss or by manual reset 3.22 heat input, in kW, amount of heat as a function of time released by the burner at a given throughput 3.23 maximum heat input, in kW, maximum heat input, at continuous burning, as specified by the manufacturer 3.24 minimum heat input, in kW, minimum h
41、eat input, at continuous burning, as specified by the manufacturer 3.25 excess air ratio ratio between the effectively introduced quantity of air and the theoretically required quantity of air Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 21/04/2008 08:05, Uncontrolled Copy, (c) BSIEN 15270
42、:2007 (E) 7 3.26 safety device device providing one or more safety related functions or parts of a safety related function, built in one physical unit 3.27 safety system system including the entire set of safety related controls and safety related measures or a part of it to provide the safety of th
43、e pellet burner or the part of it 3.28 Symbols, descriptions and units Symbols used in this standard are listed in Table 1. All gaseous volumes are expressed in m, and referred to 0 C and 1,013 bar. Table 1 Symbols, descriptions and units Symbol Description Unit a Ash content in the test fuel at dry
44、 bases mass fraction in % Bd Mass of test fuel referred to the test duration kg/h at dry bases Bw Mass of test fuel referred to the test duration kg/h at firing CC Carbon content of the test fuel mass fraction in % CCOCarbon monoxide content of the dry flue gases volume fraction in % CCO2Carbon diox
45、ide content of the dry flue gases volume fraction in % COGCCalculated content of organic gaseous compounds mg/m dry flue gas at 10 % O2CrCarbon content of residues referred to quantity of test fuel mass fraction in % CTHC,m Measured total hydrocarbon content expressed in mg/m methane equivalents in
46、wet flue gas mg/m methane CTHC,p Measured total hydrocarbon content expressed in mg/m propane equivalents in wet flue gas mg/m propane Gd Actual specific dry flue gas volume m/kg fuel Gw Actual specific wet flue gas volume m/kg fuel Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 21/04/2008 0
47、8:05, Uncontrolled Copy, (c) BSIEN 15270:2007 (E) 8 Table 1 (continued) Symbol Description Unit CH Hydrogen content mass fraction in % s mr Total residue in boiler after test kg O2, m Measured oxygen content in dry flue gas % as mean value OGC Organic gaseous compound Qib Heat input kW R Total resid
48、ue referred to the mass of test fuel mass fraction in % t Test duration h THC Total hydrocarbon content mg/m Tamb Ambient temperature C Treturn Return temperature C Tflow Flow temperature C CWMoisture content mass fraction in % Excess air ratio 4 Classification and groupings for pellet burners 4.1 C
49、lassification For the purpose of this standard pellet burners are classified in accordance with the following: Methods of control and grouped as detailed in 4.2; Means of ignition and grouped as detailed in 4.3; External or integral fuel hopper; Combustion chamber; Monobloc or other type of burner. 4.2 Methods of control of pellet burner Methods of control are grouped as follows: a. On-off control; b. Modulating control; c. Multi-stage control. 4.3 Means of ignition Means of ignition are grouped as follows: a. Manual ignition; b. Au