1、raising standards worldwideNO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAWBSI Standards PublicationBS EN 15869-2:2010Inland navigation vessels Electrical shore connection, three phase current 400 V, up to 63 A, 50 HzPart 2: Onshore unit, safety requirementsCopyright European C
2、ommittee for Standardization Provided by IHS under license with CENNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-BS EN 15869-2:2010 BRITISH STANDARDNational forewordThis British Standard is the UK implementation of EN 15869-2:2010. The UK participation in its pre
3、paration was entrusted to T e c h n i c a l Committee SME/32/-/11, Ships and marine technology - Intermodal, inland navigation and short sea shipping.A list of organizations represented on this committee can be obtained on request to its secretary.This publication does not purport to include all the
4、 necessary provisions of a contract. Users are responsible for its correct application. The British Standards Institution 2013. Published by BSI Standards Limited 2013.ISBN 978 0 580 63978 4 ICS 47.020.60; 47.060; 93.140 Compliance with a British Standard cannot confer immunityfrom legal obligations
5、.This British Standard was published under the authority of the Standards Policy and Strategy Committee on 31 January 2013.Amendments issued since publicationDate T e x t a f f e c t e dCopyright European Committee for Standardization Provided by IHS under license with CENNot for ResaleNo reproducti
6、on or networking permitted without license from IHS-,-,-BS EN 15869-2:2010EUROPEAN STANDARD NORME EUROPENNE EUROPISCHE NORM EN 15869-2 February 2010 ICS 47.020.60; 47.060; 93.140 English Version Inland navigation vessels - Electrical shore connection, three phase current 400 V, up to 63 A, 50 Hz - P
7、art 2: Onshore unit, safety requirements Bateaux de navigation intrieure - Connexion au rseau lectrique terrestre, courant triphas 400 V, 63 A, 50 Hz -Partie 2: Unit terrestre, exigences de scurit Fahrzeuge der Binnenschifffahrt - Elektrischer Landanschluss, Drehstrom 400 V, bis 63 A, 50 Hz - Teil 2
8、: Landseitiger Teil, sicherheitstechnische Anforderungen This European Standard was approved by CEN on 25 December 2009. CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard withou
9、t any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN Management Centre or to any CEN member. This European Standard exists in three official versions (English, French, German). A version in any other language m
10、ade by translation under the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as the official versions. CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Fi
11、nland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom. EUROPEAN COMMITTEE FOR STANDARDIZATION COMIT EUROPEN DE NORMALISATION EUROPISCHES
12、 KOMITEE FR NORMUNG Management Centre: Avenue Marnix 17, B-1000 Brussels 2010 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 15869-2:2009: ECopyright European Committee for Standardization Provided by IHS under license with CENNot
13、 for ResaleNo reproduction or networking permitted without license from IHS-,-,-BS EN 15869-2:2010EN 15869-2:2010 (E) 2 Contents Page Foreword3 Introduction .4 1 Scope 5 2 Normative references 5 3 Terms and definitions .6 4 Safety requirements 7 4.1 General7 4.2 Mechanical safety 8 4.3 Electrical sa
14、fety8 4.4 Other provisions 9 5 Designation 9 6 Marking .9 7 Manufacturers declaration of conformity.9 Bibliography 10 Figures Figure 1 Block diagram of an electrical power-supply station with two connector units. 7 Copyright European Committee for Standardization Provided by IHS under license with C
15、ENNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-BS EN 15869-2:2010EN 15869-2:2010 (E) 3 Foreword This document (EN 15869-2:2010) has been prepared by Technical Committee CEN/TC 15 “Inland navigation vessels”, the secretariat of which is held by DIN. This European
16、 Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by August 2010, and conflicting national standards shall be withdrawn at the latest by August 2010 EN 15869, Inland navigation vessels Electrical shore connection T
17、hree-phase current 400 V, up to 63 A, 50 Hz comprises: Part 1: General requirements Part 2: Onshore unit, safety requirements Part 3: On-board unit, safety requirements According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to imp
18、lement this European Standard: Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerlan
19、d and the United Kingdom. Copyright European Committee for Standardization Provided by IHS under license with CENNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-BS EN 15869-2:2010EN 15869-2:2010 (E) 4 Introduction Inland navigation vessels are equipped with a varie
20、ty of electrical loads operating at 230 V or 400 V. While underway, continuous electrical power supply is provided by the onboard system from generators driven by diesel engines. When the vessel is berthed, these generators have to remain in operation if there is no suitable onshore power supply ava
21、ilable. In some cases, this leads to intense noise pollution both for the crew on the vessel itself and on other vessels lying alongside and also for residents ashore. The exhaust fumes are an additional pollution factor. The electrical shore connections specified in this standard make it possible t
22、o provide the vessels with an electrical power supply while berthed and to eliminate noise and exhaust pollution. This calls for a uniform Europe-wide connection that can be activated and deactivated by the vessels crew in all ports and berths, if possible, without requiring any assistance from shor
23、e-based personnel. This standard contains electrical safety requirements for the prevention of hazards in making, using and breaking the shore connection. Furthermore, cashless settlement for the electricity used shall be possible, ideally a standard Europe-wide payment system. Electrical shore conn
24、ections with a permissible current of over 63 A as used for passenger ships with a hotelling function are not covered by this standard. . . Copyright European Committee for Standardization Provided by IHS under license with CENNot for ResaleNo reproduction or networking permitted without license fro
25、m IHS-,-,-BS EN 15869-2:2010EN 15869-2:2010 (E) 5 1 Scope This European Standard specifies requirements applicable to equipment for shore-to-vessel supply of three-phase 400 V electrical power up to 63 A and a frequency of 50 Hz to berthed inland navigation vessels. This part of the European Standar
26、d specifies safety requirements for the onshore unit of the electrical shore connection. This part of the European Standard applies only to the supply of inland navigation vessels in ports and berths for commercial shipping. Supply stations for leisure craft and houseboats in marinas or similar loca
27、tions have to meet the requirements of IEC 60364-7-709. For low-voltage electrical installations, the requirements specified in the HD 60364 and HD 384 series are applicable generally. The requirements in this part of EN 15869 supplement, amend or supersede some of the requirements in HD 60364/HD 38
28、4 Parts 1 to 6. Where no requirements are given in this part of EN 15869, the requirements specified in the HD 60364 and HD 384 are applicable; a detailed list is given in the Bibliography. 2 Normative references The following referenced documents are indispensable for the application of this docume
29、nt. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 15869-1, Inland navigation vessels Electrical shore connection, three-phase current 400 V, up to 63 A, 50 Hz Part 1: General requirem
30、ents EN 14145, Holders for lifebuoys EN 60309-1, Plugs, socket-outlets and couplers for industrial purposes Part 1: General requirements (IEC 60309-1:1999) EN 60309-2, Plugs, socket-outlets and couplers for industrial purposes Part 2: Dimensional interchangeability requirements for pin and contact-t
31、ube accessories (IEC 60309-2:1999) EN 60309-4, Plugs, socket-outlets and couplers for industrial purposes Part 4: Switched socket-outlets and connectors with or without interlock (IEC 60309-4:2006, modified) EN 60529, Degrees of protection provided by enclosures (IP code) (IEC 60529:1989) EN 60898-1
32、, Electrical accessories Circuit-breakers for overcurrent protection for household and similar installations Part 1: Circuit-breakers for a.c. operation (IEC 60898-1:2002, modified) EN 61008-1, Residual current operated circuit-breakers without integral overcurrent protection for household and simil
33、ar uses (RCCBs) Part 1: General rules (IEC 61008-1:1996 + A1:2002, modified) HD 22.16.S2, Cables of rated voltages up to and including 450/750 V and having cross-linked insulation Part 16: Water resistant polychloroprene or equivalent synthetic elastomer sheathed cables Copyright European Committee
34、for Standardization Provided by IHS under license with CENNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-BS EN 15869-2:2010EN 15869-2:2010 (E) 6 3 Terms and definitions For the purposes of this document, the following terms and definitions apply. 3.1 electrical sh
35、ore connection equipment consisting of electrical power-supply station, cable set and feed unit for the supply of electrical power to inland navigation vessels in ports and at berths EN 15869-1:2010 3.2 electrical power-supply station shore-side part of the electrical shore connection with one or mo
36、re connector units EN 15869-1:2010 3.3 connector unit unit for connecting an inland navigation vessel EN 15869-1:2010 3.4 activation medium system for activating the supply of power and cashless settlement of the costs EN 15869-1:2010 3.5 feed unit all the onboard devices for receiving the electrica
37、l power on board EN 15869-1:2010 Copyright European Committee for Standardization Provided by IHS under license with CENNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-BS EN 15869-2:2010EN 15869-2:2010 (E) 7 4 Safety requirements 4.1 General Key 1 fuse 2 overvoltag
38、e protector (if necessary) 3 three-phase meter (according to EN 15869-1) 4 circuit breaker 5 residual current operated circuit breaker 6 activation medium with enabling contactor 7 socket outlet (according to EN 15869-1) Figure 1 Block diagram of an electrical power-supply station with two connector
39、 units The electrical power-supply station (see Figure 1) has a three-phase fuse, an overvoltage protector (optional) and one or more connector units. A connector unit consists of a circuit breaker, a residual current operated circuit breaker and 16 A (32 A and 63 A also optional) socket outlets, me
40、ter and activation medium. Copyright European Committee for Standardization Provided by IHS under license with CENNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-BS EN 15869-2:2010EN 15869-2:2010 (E) 8 The circuit breaker, residual current operated circuit breaker
41、and socket outlets shall be protected against misuse, e.g. by being located behind a door or flap that can only be opened with the activation medium (see EN 15869-1). The door or flap shall also be lockable even when the connection has been made so that it can only be opened with the activation medi
42、um. Furthermore, the connection cables shall not have any crush points or shear points. The electrical power-supply station shall be equipped with lighting that sufficiently illuminates the socket outlets, electricity meter, circuit breaker and residual current operated circuit breaker, as well as t
43、he area where the operator stands. In darkness, it shall be permanently illuminated or illuminated on approach for at least five minutes, e.g. by using a motion detector. A set of operating instructions shall be available explaining the necessary operating stages and containing the following informa
44、tion, at least: a) “Only use connection cables according to HD 22.16, marked with H07RNF!“; b) “400 V, 50 Hz“; c) “Maximum permissible continuous load“ (11 kW at 16 A, 22 kW at 32 A or 44 kW at 63 A); d) “The socket outlet is protected by an RCCB (30 mA)“; e) “Information on laying the connection ca
45、ble safely“; f) if appropriate, the electricity price. The operating instructions shall be written in the local language of the place where the station is set up, as well as in German, Dutch, French, English, Polish, Serbo-Croat and Hungarian. In locally limited operating areas, the selection of lan
46、guages can be reduced. The instructions shall be available either on a display with a language selection or on a permanently fitted sign. 4.2 Mechanical safety The housing of the electrical power-supply station shall be sufficiently mechanically resistant, durable, flame-resistant and non-hydroscopi
47、c. It shall be permanently fitted and it shall not be possible to open it with commercially available tools. The electrical power-supply station shall be constructed for an ambient temperature of 20 C to +60 C. If necessary, these limiting values shall be increased according to the temperatures to b
48、e expected in the region where the installation site is located. 4.3 Electrical safety The complete electrical power-supply station shall have at least IP 55 degree of protection according to EN 60529, with the exception of the door or flap according to 4.1. Metal housings or housing components shall be connected to the on-site earthing system. If the electrical power-supply station is fed with a voltage higher than stated in EN 15869-1, isolation (isolating transformer) shall be provided. The socket outlet shall: meet the requirements of EN 60309-1, EN 6
copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有