1、raising standards worldwideNO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAWBSI Standards PublicationBS EN 50525-2-83:2011Electric cables Low voltage energy cables of rated voltages up to and including 450/750 V (U0/U) Part 2-83: Cables for general applications Multicore cables
2、with crosslinked silicone rubber insulationBS EN 50525-2-83:2011 BRITISH STANDARDNational forewordThis British Standard is the UK implementation of EN50525-2-83:2011. It partially supersedes BS7919:2001.The UK participation in its preparation was entrusted to TechnicalCommittee GEL/20/17, Electric C
3、ables - Low voltage.A list of organizations represented on this committee can beobtained on request to its secretary.This publication does not purport to include all the necessaryprovisions of a contract. Users are responsible for its correctapplication. BSI 2011ISBN 978 0 580 64374 3ICS 29.060.20Co
4、mpliance with a British Standard cannot confer immunity fromlegal obligations.This British Standard was published under the authority of theStandards Policy and Strategy Committee on 30 September 2011.Amendments issued since publicationDate Text affectedBS EN 50525-2-83:2011 BRITISH STANDARDNational
5、 forewordThis British Standard is the UK implementation of EN50525-2-83:2011. It partially supersedes BS7919:2001.The UK participation in its preparation was entrusted to TechnicalCommittee GEL/20/17, Electric Cables - Low voltage.A list of organizations represented on this committee can beobtained
6、on request to its secretary.This publication does not purport to include all the necessaryprovisions of a contract. Users are responsible for its correctapplication. BSI 2011ISBN 978 0 580 64374 3ICS 29.060.20Compliance with a British Standard cannot confer immunity fromlegal obligations.This Britis
7、h Standard was published under the authority of theStandards Policy and Strategy Committee on 30 September 2011.Amendments issued since publicationDate Text affectedThis British Standard is the UK implementation of EN 50525-2-83:2011. In the UKnull the BS EN 50525 series of standards nullontain null
8、omplenullsnullpersession details. The tanullle nullelonull nullest snullmmarinulles the relationship nulletnulleen these standards:Part 1 together with Supersedes2-81 BS null38-null:1nullnullnull2-null1null 2-null2 BS null00null: 200null2-11 nullin partnullnull 2-12null 2-21 nullin partnullnull 2-nu
9、ll1 BS null500:20002-11 nullin partnullnull 2-21 nullin partnullnull 2-51 nullin partnullnull 2-83null 3-21 BS nullnull1null:20012-31null 2-51 nullin partnull BS 6004:20003-null1 BS 7211:19982-22null 2-null2null 2-82null 3-11null 3-31 NoneNOTE All British Standards will remain current until they are
10、 withdrawn on 31 December 2012. British Standards in bold are only partially supersedednull and new editions onull BS null00null and BS null211 will be introduced on 1 nullanuary 2013.National nullnnenull Nnull nullinformatinullenull nullinulles information on the orinullins and identinullnullation
11、of partinullnulllar nullanullle tnullpes.BS EN 50525-2-83:2011EUROPEAN STANDARD EN 50525-2-83 NORME EUROPENNE EUROPISCHE NORM May 2011 CENELEC European Committee for Electrotechnical Standardization Comit Europen de Normalisation Electrotechnique Europisches Komitee fr Elektrotechnische Normung Mana
12、gement Centre: Avenue Marnix 17, B - 1000 Brussels 2011 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members. Ref. No. EN 50525-2-83:2011 E ICS 29.060.20 Supersedes HD 22.15 S2:2007English version Electric cables - Low voltage energy cables of rate
13、d voltages up to and including 450/750 V (U0/U) - Part 2-83: Cables for general applications - Multicore cables with crosslinked silicone rubber insulation Cbles lectriques - Cbles dnergie basse tension de tension assigne au plus gale 450/750 V (U0/U) - Partie 2-83: Cbles pour applications gnrales -
14、 Cbles multiconducteurs isols au siliconerticul Kabel und Leitungen - Starkstromleitungen mit Nennspannungen bis 450/750 V (U0/U) - Teil 2-83: Starkstromleitungen fr allgemeine Anwendungen - Mehradrige Leitungen mit vernetzter Silikon-Isolierung This European Standard was approved by CENELEC on 2011
15、-01-17. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be o
16、btained on application to the Central Secretariat or to any CENELEC member. This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CENELEC member into its own language and notified to the C
17、entral Secretariat has the same status as the official versions. CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, L
18、uxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom. BS EN 50525-2-83:2011EN 50525-2-83:2011 - 2 - Foreword This European Standard was prepared by the Technical Committee CENELEC TC 20, Electric cables. The text
19、of the draft was submitted to the formal vote and was accepted by CENELEC as EN 50525-2-83 on 2011-01-17. This document, which is one of a multipart series, supersedes HD 22.15 S2:2007. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent righ
20、ts. CEN and CENELEC shall not be held responsible for identifying any or all such patent rights. The following dates are proposed: latest date by which the EN has to be implemented at national level by publication of an identical national standard or by endorsement (dop) 2012-01-17 latest date by wh
21、ich the national standards conflicting with the EN have to be withdrawn (dow) 2014-01-17 _ BS EN 50525-2-83:2011- 3 - EN 50525-2-83:2011 Contents Page 1 Scope 42 Normative references . 43 Terms and definitions . 54 Heat resistant cables (180 C) . 54.1 Cables H05SS-F and braided cables H05SST-F 54.2
22、Cables H05SSD3-K and braided cables H05SSD3T-K, with strain-bearing element . 6Annex A (normative) Tests for cables to EN 50525-2-83 8Annex B (normative) General data . 10Annex C (normative) Requirements for compatibility test . 11C.1 Test conditions . 11C.2 Requirements . 11Bibliography . 12Tables
23、Table A.1 8Table B.1 10Table C.1 Requirements . 11BS EN 50525-2-83:2011EN 50525-2-83:2011 - 4 - 1 Scope This European Standard applies to multicore cables insulated and sheathed with heat resistant crosslinked silicone rubber. Types with or without an overall textile braid, and with or without a str
24、ain-bearing element, are included. The cables are of rated voltages U0/U 300/500 V. The cables are intended for use within high temperature zones, either: - in fixed installations with mechanical protection (cables to 4.1); or - for flexible use under low mechanical stress (cables to 4.2). The maxim
25、um conductor operating temperature for each of the cables in this standard is 180 C. NOTE HD 516 contains extensive guidance on the safe use of cables in this standard. This EN 50525-2-83 should be read in conjunction with EN 50525-1, which specifies general requirements. 2 Normative references The
26、following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. NOTE One or more references to the standards below ar
27、e in respect of a specific sub-division of that standard, for instance a clause, a table, a class or a type. Cross-references to these standards are undated and, at all times, the latest version applies. EN 50363-1 Insulating, sheathing and covering materials for low voltage energy cables Part 1: Cr
28、oss-linked elastomeric insulating compounds EN 50363-2-1 Insulating, sheathing and covering materials for low voltage energy cables Part 2-1: Cross-linked elastomeric sheathing compounds EN 50395 Electrical test methods for low voltage energy cables EN 50396 Non electrical test methods for low volta
29、ge energy cables EN 50525-1 Electric cables Low voltage energy cables of rated voltages up to and including 450/750 V (U0/U) Part 1: General requirements EN 60228 Conductors of insulated cables (IEC 60228) EN 60332-1-2 Tests on electric and optical fibre cables under fire conditions Part 1-2: Test f
30、or vertical flame propagation for a single insulated wire or cable Procedure for 1 kW pre-mixed flame (IEC 60332-1-2) EN 60811-1-2 Insulating and sheathing materials of electric and optical cables Common test methods Part 1-2: General application Thermal ageing methods (IEC 60811-1-2) EN 60811-1-4 I
31、nsulating and sheathing materials of electric and optical cables Common test methods Part 1-4: General application Tests at low temperature (IEC 60811-1-4) EN ISO 6892-1 2009 Metallic materials Tensile testing Part 1: Method of test at room temperature (ISO 6892-1:2009) BS EN 50525-2-83:2011- 5 - EN
32、 50525-2-83:2011 3 Terms and definitions For the purposes of this document the terms and definitions given in Clause 3 of EN 50525-1 apply. 4 Heat resistant cables (180 C) 4.1 Cables H05SS-F and braided cables H05SST-F 4.1.1 Construction 4.1.1.1 Conductor The conductor shall be class 5, according to
33、 EN 60228. 4.1.1.2 Sizes of cable The sizes of cable shall be: Number of cores: 2, 3, 4 or 5 Nominal cross section: 0,75 mm up to 2,5 mm for 2 and 5 cores 0,75 mm up to 6 mm for 3 and 4 cores 4.1.1.3 Insulation The insulation shall be a cross-linked elastomeric compound of Type EI 2 to EN 50363-1 ap
34、plied around each conductor. 4.1.1.4 Assembly of cores The cores shall be twisted together. 4.1.1.5 Sheath The core assembly shall be covered with a sheath. The sheath shall be a cross-linked compound of Type EM 9 to EN 50363-2-1 applied around the cores. The sheath shall fill the spaces between the
35、 cores and fillers, if any. 4.1.1.6 Braid For cable type H05SST-F the sheath shall be provided with a braid of suitable material. The braid shall have a uniform texture, without knots or gaps. 4.1.1.7 Marking The cable shall be marked with the CENELEC code H05SS-F for cables without braid, or H05SST
36、-F for cables with braid. The marking shall comply with Clause 6 of EN 50525-1. 4.1.2 Requirements Each cable shall comply with the appropriate requirements given in EN 50525-1, and the particular requirements of this Part. BS EN 50525-2-83:2011EN 50525-2-83:2011 - 6 - Testing shall be in accordance
37、 with Annex A, and the relevant tests indicated in column 6. The dimensions of the cables shall conform to Table B.1 for the relevant size. The requirements to be met for the compatibility test shall be as given in Annex C. 4.2 Cables H05SSD3-K and braided cables H05SSD3T-K, with strain-bearing elem
38、ent 4.2.1 Construction 4.2.1.1 Conductor The conductor shall be class 5, according to EN 60228. 4.2.1.2 Sizes of cable The sizes of cable shall be: - Number of cores: 2, 3, 4 or 5; - Nominal cross section: 0,75 mm or 1 mm. 4.2.1.3 Insulation The insulation shall be a cross-linked elastomeric compoun
39、d of Type EI 2 to EN 50363-1 applied around each conductor. 4.2.1.4 Strain-bearing element The strain-bearing element shall be of non-metallic material. The strain-bearing element can be constructed as a single strain-bearing element or divided in two or more elements. 4.2.1.5 Assembly of cores The
40、cores shall be twisted together. The strain-bearing element(s) shall be twisted together with the cores, and for the 3, 4 and 5 core cables the strain-bearing element shall be in the centre of the cable. 4.2.1.6 Sheath The core assembly shall be covered with a sheath. The sheath shall be a cross-lin
41、ked compound of Type EM 9 to EN 50363-2-1 applied around the cores. The sheath shall fill the spaces between the cores and fillers, if any. 4.2.1.7 Braid For cable type H05SSD3T-K the sheath shall be provided with a braid of suitable material. The braid shall have a uniform texture, without knots or
42、 gaps. 4.2.1.8 Marking The cable shall be marked with the CENELEC code H05SSD3-K for cables without braid, or H05SSD3T-K for cables with braid. The marking shall comply with Clause 6 of EN 50525-1. BS EN 50525-2-83:2011- 7 - EN 50525-2-83:2011 4.2.2 Requirements Each cable shall comply with the appr
43、opriate requirements given in EN 50525-1, and the particular requirements of this Part. Testing shall be in accordance with Annex A, and the relevant tests indicated in column 7. The dimensions of the cables shall conform to Table B.1 for the relevant size. The requirements to be met for the compati
44、bility test shall be as given in Annex C. The strain-bearing element shall have in total a minimum load at break of 300 N, before and after ageing on complete cable at a temperature of (200 3) C for 240 h. The strain-bearing element shall have a limited elongation compatible with cores in order to a
45、void excessive stresses on them. BS EN 50525-2-83:2011EN 50525-2-83:2011 - 8 - Annex A (normative) Tests for cables to EN 50525-2-83 Table A.1 1 2 3 4 5 6 7 Ref. No. Tests a Category of test Test method described in Applicability of test Subclause EN (Sub)clause 4.1 4.2 H05SSH05SSD31 Electrical test
46、s b 1.1 Resistance of conductors T, S 50395 5 X X 1.2 Voltage test on completed cable at 2 000 V T, S 50395 6 X X 1.3 Voltage test on cores according to the specified insulation thickness T, S 50395 7 1.3.1 - at 1 500 V up to and including 0,6 mm X X 1.3.2 - at 2 000 V above 0,6 mm X - 1.4 Absence o
47、f faults in insulation R 5039510 X X 1.5 Surface resistance of sheath T 50395 11 X X 2 Constructional and dimensional tests 2.1 Checking of compliance with constructional provisions T, S 50525-1 Inspection and manual tests X X 2.2 Measurement of thickness of insulation T, S 50396 4.1 X X 2.3 Measure
48、ment of thickness of sheath T, S 50396 4.2 X X 2.4 Measurement of overall diameter 2.4.1 - mean value T, S 50396 4.4 X X 2.4.2 - ovality T, S 50396 4.4 X X 2.5 Solderability test (plain conductors) T 50396 8.2 X X 3 Insulation material tests T 50363-1 c - X X 4 Sheath material tests T 50363-2-1 c -
49、X X 5 Compatibility test T 60811-1-2 8.1.4 X X 6 Impact test at - 25 C T 60811-1-4 8.5 X X 7 Mechanical strength of completed cable d 7.1 Flexing test followed, after immersion in water, by a voltage test T 50396 6.2 X - - at 2 000 V for two core cables - at 1 500 V for cables having more than two cores T T 50395 50395 7 7 X X - - BS EN 50525-2-83:2011- 9 - EN 50525-2-83:2011 Table A.1 (concluded) 1 2 3 4 5 6 7 Ref. No. Tests a Category of test Test meth