1、BS EN 50525-3-11:2011Electric cables Low voltageenergy cables of rated voltagesup to and including 450/750 V(U0/U) -Part 3-11: Cables with special fireperformance Flexible cables withhalogen-free thermoplastic insulation, andlow emission of smokeBS EN 50525-3-11:2011 BRITISH STANDARDNational forewor
2、dThis British Standard is the UK implementation of EN50525-3-11:2011.The UK participation in its preparation was entrusted to TechnicalCommittee GEL/20/17, Electric Cables - Low voltage.A list of organizations represented on this committee can beobtained on request to its secretary.This publication
3、does not purport to include all the necessaryprovisions of a contract. Users are responsible for its correctapplication. BSI 2011ISBN 978 0 580 64375 0ICS 29.060.20Compliance with a British Standard cannot confer immunity fromlegal obligations.This British Standard was published under the authority
4、of theStandards Policy and Strategy Committee on 30 September 2011.Amendments issued since publicationDate Text affectedBS EN 50525-3-11:2011 BRITISH STANDARDNational forewordThis British Standard is the UK implementation of EN50525-3-11:2011.The UK participation in its preparation was entrusted to
5、TechnicalCommittee GEL/20/17, Electric Cables - Low voltage.A list of organizations represented on this committee can beobtained on request to its secretary.This publication does not purport to include all the necessaryprovisions of a contract. Users are responsible for its correctapplication. BSI 2
6、011ISBN 978 0 580 64375 0ICS 29.060.20Compliance with a British Standard cannot confer immunity fromlegal obligations.This British Standard was published under the authority of theStandards Policy and Strategy Committee on 30 September 2011.Amendments issued since publicationDate Text affectedThis B
7、ritish Standard is the UK implementation of EN 50525-3-11:2011.In the UK, the BS EN 50525 series of standards nullontain nullomplenullsnullpersession details. The tanullle nullelonull nullest snullmmarinulles the relationship nulletnulleen these standards:Part 1 together with Supersedes2-null1 BS nu
8、ll3null-null:1nullnullnull2-null1, 2-null2 BS null00null: 200null2-11 nullin partnull, 2-12, 2-21 nullin partnull, 2-null1 BS null500:20002-11 nullin partnull, 2-21 nullin partnull, 2-51 nullin partnull, 2-null3, 3-21 BS nullnull1null:20012-31, 2-51 nullin partnull BS 6004:20003-null1 BS 7211:19982-
9、22, 2-null2, 2-null2, 3-11, 3-31 NoneNOTE All British Standards will remain current until they are withdrawn on 31 December 2012. British Standards in bold are only partially supersedednull and new editions onull BS null00null and BS null211 will be introduced on 1 nullanuary 2013.BS EN 50525-3-11:2
10、011EUROPEAN STANDARD EN 50525-3-11 NORME EUROPENNE EUROPISCHE NORM May 2011 CENELEC European Committee for Electrotechnical Standardization Comit Europen de Normalisation Electrotechnique Europisches Komitee fr Elektrotechnische Normung Management Centre: Avenue Marnix 17, B - 1000 Brussels 2011 CEN
11、ELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members. Ref. No. EN 50525-3-11:2011 E ICS 29.060.20 Supersedes HD 21.14 S1:2003English version Electric cables - Low voltage energy cables of rated voltages up to and including 450/750 V (U0/U) - Part 3-11
12、: Cables with special fire performance - Flexible cables with halogen-free thermoplastic insulation, and low emission of smoke Cbles lectriques - Cbles dnergie basse tension de tension assigne au plus gale 450/750 V (U0/U) - Partie 3-11: Cbles performances spciales au feu - Cbles souples isols en ma
13、triau thermoplastique sans halogne, faible dgagement de fume Kabel und Leitungen - Starkstromleitungen mit Nennspannungen bis 450/750 V (U0/U) - Teil 3-11: Starkstromleitungen mit verbessertem Verhalten im Brandfall - Flexible halogenfreie, raucharme Leitungen mit thermoplastischer IsolierungThis Eu
14、ropean Standard was approved by CENELEC on 2011-01-17. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical referen
15、ces concerning such national standards may be obtained on application to the Central Secretariat or to any CENELEC member. This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CENELEC mem
16、ber into its own language and notified to the Central Secretariat has the same status as the official versions. CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary
17、, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom. BS EN 50525-3-11:2011EN 50525-3-11:2011 - 2 - Foreword This European Standard was prepared by the Technical Comm
18、ittee CENELEC TC 20, Electric cables. The text of the draft was submitted to the formal vote and was approved by CENELEC as EN 50525-3-11 on 2011-01-17. This document, which is one of a multipart series, supersedes HD 21.14 S1:2003. Attention is drawn to the possibility that some of the elements of
19、this document may be the subject of patent rights. CEN and CENELEC shall not be held responsible for identifying any or all such patent rights. The following dates were fixed: latest date by which the EN has to be implemented at national level by publication of an identical national standard or by e
20、ndorsement (dop) 2012-01-17 latest date by which the national standards conflicting with the EN have to be withdrawn (dow) 2014-01-17 _ BS EN 50525-3-11:2011- 3 - EN 50525-3-11:2011 Contents Page 1 Scope 42 Normative references . 43 Terms and definitions . 54 General purpose cables . 54.1 Light duty
21、 cables H03Z1Z1-F and H03Z1Z1H2-F 54.2 Ordinary duty cables H05Z1Z1-F and H05Z1Z1H2-F 6Annex A (normative) Tests for cables to EN 50525-3-11 8Annex B (normative) General data . 9Annex C (normative) Requirements for compatibility test . 11C.1 Test conditions . 11C.2 Requirements . 11Annex D (normativ
22、e) Water immersion test on sheath . 12D.1 General . 12D.2 Sampling and preparation of test pieces . 12D.3 Procedure . 12D.4 Evaluation of results . 12Bibliography . 13Tables Table A.1 8Table B.1 9Table B.2 10Table C.1 . 11BS EN 50525-3-11:2011EN 50525-3-11:2011 - 4 - 1 Scope EN 50525-3-11 applies to
23、 flexible cables, insulated and sheathed with halogen-free thermoplastic compound and having low emission of smoke and corrosive gases when exposed to fire. NOTE 1 Low emission of smoke is checked in accordance with EN 61034-2. Low emission of corrosive gases is checked as part of the check for abse
24、nce of halogens (see Annex B of EN 50525-1). The cables are of rated voltages U0/U up to and including 300/500 V. The cables are intended for the connection of domestic appliances to the fixed supply. Circular cables and flat cables are included. The maximum conductor operating temperature for each
25、of the cables in this standard is 70 C. NOTE 2 HD 516 contains extensive guidance on the safe use of cables in this standard. This EN 50525-3-11 should be read in conjunction with EN 50525-1, which specifies general requirements. 2 Normative references The following referenced documents are indispen
26、sable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. NOTE One or more references to the standards below are in respect of a specific sub-division of
27、that standard, for instance a clause, a table, a class or a type. Cross-references to these standards are undated and, at all times, the latest version applies. EN 50363-7 Insulating, sheathing and covering materials for low voltage energy cables - Part 7: Halogen-free, thermoplastic insulating comp
28、ounds EN 50363-8 Insulating, sheathing and covering materials for low voltage energy cables - Part 8: Halogen-free, thermoplastic sheathing compounds EN 50395 Electrical test methods for low voltage energy cables EN 50396 Non electrical test methods for low voltage energy cables EN 50525-1 Electric
29、cables - Low voltage energy cables of rated voltages up to and including 450/750 V (U0/U) - Part 1: General requirements EN 60228 Conductors of insulated cables (IEC 60228) EN 60332-1-2 Tests on electric and optical fibre cables under fire conditions - Part 1-2: Test for vertical flame propagation f
30、or a single insulated wire or cable - Procedure for 1 kW pre-mixed flame (IEC 60332-1-2) EN 60811-1-1 Insulating and sheathing materials of electric and optical cables - Common test methods - Part 1-1: General application - Measurement of thickness and overall dimensions - Tests for determining the
31、mechanical properties (IEC 60811-1-1) EN 60811-1-2 Insulating and sheathing materials of electric and optical cables - Common test methods - Part 1-2: General application - Thermal ageing methods (IEC 60811-1-2) EN 60811-1-4 Insulating and sheathing materials of electric and optical cables - Common
32、test methods - Part 1-4: General application - Tests at low temperature (IEC 60811-1-4) BS EN 50525-3-11:2011- 5 - EN 50525-3-11:2011 EN 61034-2 Measurement of smoke density of cables burning under defined conditions - Part 2: Test procedure and requirements (IEC 61034-2) 3 Terms and definitions For
33、 the purposes of this document the terms and definitions given in Clause 3 of EN 50525-1 apply. 4 General purpose cables 4.1 Light duty cables H03Z1Z1-F and H03Z1Z1H2-F 4.1.1 Construction 4.1.1.1 Conductor The conductor shall be class 5, according to EN 60228. 4.1.1.2 Sizes of cable The sizes of cab
34、le shall be: circular cables 0,5 mm2and 0,75 mm2 2, 3 and 4 core; flat cables 0,5 mm2and 0,75 mm2 2 core only. 4.1.1.3 Insulation The insulation shall be thermoplastic compound of Type TI 6 to EN 50363-7. 4.1.1.4 Assembly The cables shall be assembled as follows: circular cable: the cores shall be t
35、wisted together; flat cable: the cores shall be laid parallel. NOTE A tape may be applied around the core assembly before application of the sheath. 4.1.1.5 Sheath The sheath shall be thermoplastic compound of Type TM 7 to EN 50363-8. The sheath shall fill the spaces between the cores, thus forming
36、a filling. 4.1.1.6 Marking The cable shall be marked with the CENELEC code H03Z1Z1-F for circular cables, or H03Z1Z1H2-F for flat cables. The marking shall comply with Clause 6 of EN 50525-1. 4.1.2 Requirements Each cable shall comply with the appropriate requirements given in EN 50525-1, and the pa
37、rticular requirements of this Part. BS EN 50525-3-11:2011EN 50525-3-11:2011 - 6 - Testing shall be in accordance with Annex A, and the relevant tests indicated in column 6. The dimensions of the cables shall conform to Table B.1 for the relevant size. The requirements to be met for the compatibility
38、 test shall be as given in Annex C. When tested in accordance with the method and procedure given in EN 61034-2, all sizes of cable shall exceed 60 % light transmittance throughout the test. 4.2 Ordinary duty cables H05Z1Z1-F and H05Z1Z1H2-F 4.2.1 Construction 4.2.1.1 Conductor The conductor shall b
39、e class 5, according to EN 60228. 4.2.1.2 Sizes of cable The sizes of cable shall be: circular cables 0,75 mm2to 4 mm2 2, 3, 4 and 5 core; flat cables 0,75 mm2and 1,0 mm2 2 core only. 4.2.1.3 Insulation The insulation shall be thermoplastic compound of Type TI 6 to EN 50363-7. 4.2.1.4 Assembly The c
40、ables shall be assembled as follows: circular cable: the cores, and the fillers if any, shall be twisted together; flat cable: the cores shall be laid parallel. For circular cable having two cores, the space between the cores shall be filled either by separate fillers or by the sheath filling the in
41、terstices. NOTE 1 For circular cables with three, four or five cores, a centre filler may be used. NOTE 2 A tape may be applied around the core assembly before application of the sheath. 4.2.1.5 Sheath The sheath shall be thermoplastic compound of Type TM 7 to EN 50363-8. The sheath shall fill the s
42、paces between the cores, thus forming a filling. 4.2.1.6 Marking The cable shall be marked with the CENELEC code H05Z1Z1-F for circular cables, or H05Z1Z1H2-F for flat cables. The marking shall comply with Clause 6 of EN 50525-1. BS EN 50525-3-11:2011- 7 - EN 50525-3-11:2011 4.2.2 Requirements Each
43、cable shall comply with the appropriate requirements given in EN 50525-1, and the particular requirements of this Part. Testing shall be in accordance with Annex A, and the relevant tests indicated in column 7. The dimensions of the cables shall conform to Table B.2 for the relevant size. The requir
44、ements to be met for the compatibility test shall be as given in Annex C. When tested in accordance with the method and procedure given in EN 61034-2, all sizes of cable shall exceed 60 % light transmittance throughout the test. BS EN 50525-3-11:2011EN 50525-3-11:2011 - 8 - Annex A (normative) Tests
45、 for cables to EN 50525-3-11 Table A.1 1 2 3 4 5 6 7 Ref No. Tests aCategory of test Test method described in Applicability of test Subclause EN (Sub)clause 4.1 4.2 H03Z1Z1H05Z1Z11 Electrical tests b 1.1 Resistance of conductors T, S 50395 5 X X 1.2 Voltage test on completed cable at 2 000 V T, S 50
46、395 6 X X 1.3 Voltage test on cores according to specified insulation thickness: 1.3.1 - at 1 500 V up to and including 0,6 mm T, S 50395 7 X X 1.3.2 - at 2 000 V above 0,6 mm T, S 50395 7 - X 1.4 Insulation resistance at 70 C T, S 50395 8.1 X X 1.5 Long term resistance of insulation to d.c. T 50395
47、 9 X X 1.6 Absence of faults in insulation R 50395 10 X X 1.7 Surface resistance of sheath T 50395 11 X X 2 Constructional and dimensional tests 2.1 Checking of compliance with constructional provisions T, S 50525-1 Inspection and manual tests X X 2.2 Measurement of thickness of insulation T, S 5039
48、6 4.1 X X 2.3 Measurement of thickness of sheath T, S 50396 4.2/4.3 X X 2.4 Measurement of overall dimensions 2.4.1 Mean value T, S 50396 4.4.1 X X 2.4.2 Ovality T, S 50396 4.4.2 X X 3 Insulation material tests T 50363-7 c - X X 4 Sheath material tests T 50363-8 c,d - X X 5 Compatibility test T 6081
49、1-1-2 8.1.4 X X 6 Impact test at - 5 C T 60811-1-4 8.5 X X 7 Mechanical strength of completed cable eFlexing test followed, after immersion in water, by a voltage test at 2 000 V on cores T 50396 50395 6.2 7 X X 8 Tests under fire conditions 8.1 Test on single vertical cable T 60332-1-2 - X X 8.2 Smoke emission T 61034-2 - X X 9 Assessment of halogens for all non-metallic materials T, S 50525-1 Annex B X X a The order give