1、BRITISH STANDARD BS EN 61334-3-22: 2001 IEC 61334-3-22: 2001 Distribution automation using distribution line carrier systems Part 3-22: Mains signalling requirements MV phase-to-earth and screen-to-earth intrusive coupling devices The European Standard EN 61334-3-22:2001 has the status of a British
2、Standard ICS 29.240.20; 33.200 NO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAWBS EN 61334-3-22:2001 This British Standard, having been prepared under the direction of the Electrotechnical Sector Policy and Strategy Committee title here, was published under the authority of the
3、 Standards Policy and Strategy Committee on 25 October 2001 BSI 25 October 2001 ISBN 0 580 38601 5 National foreword This British Standard is the official English language version of EN 61334-3-22:2001. It is identical with IEC 61334-3-22:2001. The UK participation in its preparation was entrusted t
4、o Technical Committee PEL/57, Power system control and associated communications, which has the responsibility to: A list of organizations represented on this committee can be obtained on request to its secretary. From 1 January 1997, all IEC publications have the number 60000 added to the old numbe
5、r. For instance, IEC 27-1 has been renumbered as IEC 60027-1. For a period of time during the change over from one numbering system to the other, publications may contain identifiers from both systems. Cross-references The British Standards which implement international or European publications refe
6、rred to in this document may be found in the BSI Standards Catalogue under the section entitled “International Standards Correspondence Index”, or by using the “Find” facility of the BSI Standards Electronic Catalogue. A British Standard does not purport to include all the necessary provisions of a
7、contract. Users of British Standards are responsible for their correct application. Compliance with a British Standard does not of itself confer immunity from legal obligations. aid enquirers to understand the text; present to the responsible international/European committee any enquiries on the int
8、erpretation, or proposals for change, and keep the UK interests informed; monitor related international and European developments and promulgate them in the UK. Summary of pages This document comprises a front cover, an inside front cover, the EN title page, pages 2 to 18, an inside back cover and a
9、 back cover. The BSI copyright date displayed in this document indicates when the document was last issued. Amendments issued since publication Amd. No. Date CommentsEUROPEAN STANDARD EN 61334-3-22 NORME EUROPENNE EUROPISCHE NORM March 2001 CENELEC European Committee for Electrotechnical Standardiza
10、tion Comit Europen de Normalisation Electrotechnique Europisches Komitee fr Elektrotechnische Normung Central Secretariat: rue de Stassart 35, B - 1050 Brussels 2001 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members. Ref. No. EN 61334-3-22:2001
11、E ICS 29.240.20;33.200 English version Distribution automation using distribution line carrier systems Part 3-22: Mains signaling requirements - MV phase-to-earth and screen-to-earth intrusive coupling devices (IEC 61334-3-22:2001) Automatisation de la distribution laide de systmes de communication
12、courants porteurs Partie 3-22: Exigences concernant la transmission des signaux sur le secteur - Dispositifs de couplage intrusif phase- terre et blindage-terre MT (CEI 61334-3-22:2001) Verteilungsautomatisierung mit Hilfe von Trgersystemen auf Verteilungsleitungen Teil 3-22: Netzbedingte Anforderun
13、gen an die Signalbertragung - Auenleiter - Erdleiter und eingefgte Schirm - Erdleiter Ankopplungs- einrichtungen fr Mittelspannung (IEC 61334-3-22:2001) This European Standard was approved by CENELEC on 2000-11-01. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which s
14、tipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the Central Secretariat or to any CENELEC member. This European Sta
15、ndard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CENELEC member into its own language and notified to the Central Secretariat has the same status as the official versions. CENELEC members are the nati
16、onal electrotechnical committees of Austria, Belgium, Czech Republic, Denmark, Finland, France, Germany, Greece, Iceland, Ireland, Italy, Luxembourg, Netherlands, Norway, Portugal, Spain, Sweden, Switzerland and United Kingdom.EN -43316-3:221002 - - 2 Foreword The text of document 57/477/FDIS, futur
17、e edition 1 of IEC 61334-3-22, prepared by IEC TC 57, Power system control and associated communications, was submitted to the IEC-CENELEC parallel vote and was approved by CENELEC as EN 61334-3-22 on 2000-11-01. The following dates were fixed: latest date by which the EN has to be implemented at na
18、tional level by publication of an identical national standard or by endorsement (dop) 2001-10-01 latest date by which the national standards conflicting with the EN have to be withdrawn (dow) 2003-11-01 Annexes designated “normative“ are part of the body of the standard. In this standard, annex ZA i
19、s normative. Annex ZA has been added by CENELEC. The International Electrotechnical Commission (IEC) and CENELEC draw attention to the fact that it is claimed that compliance with this International Standard/European Standard may involve the use of a patent concerning capacitive coupling devices. Th
20、e IEC and CENELEC take no position concerning the evidence, validity and scope of this patent right. The holder of this patent right has assured the IEC that he is willing to negotiate licences under reasonable and non-discriminatory terms and conditions with applicants throughout the world. In this
21、 respect, the statement of the holder of this patent right is registered with the IEC. Information may be obtained from: ABB Research Limited CH-5401 Baden Attention is drawn to the possibility that some of the elements of this International Standard/European Standard may be the subject of patent ri
22、ghts other than those identified above. IEC and CENELEC shall not be held responsible for identifying any or all such patent rights. _ Endorsement notice The text of the International Standard IEC 61334-3-22:2001 was approved by CENELEC as a European Standard without any modification. _ Page2 EN6133
23、4322:2001 25October200161334-3-22 IEC:2001 3 CONTENTS Page INTRODUCTION 4 Clause 1 Scope and object . 5 2 Normative references. 5 3 Definitions 6 4 Service conditions 8 4.1 Standard conditions 8 4.2 Climatic conditions 8 4.3 Power frequency. 8 5 General requirements. 8 5.1 Coupling capacitor connect
24、ed to capacitive coupling devices. 8 5.2 Safety and protection requirements on phase-to-earth capacitive coupling devices . 8 5.3 Safety and protection requirements on screen-to-earth intrusive inductive coupling devices. 9 5.4 Insulation requirements10 5.5 Carrier-frequency requirements10 5.6 Ratin
25、g plate .11 5.7 Tests .11 Figure 1 MV phase-to-earth capacitive coupling device .13 Figure 2 MV screen-to-earth intrusive inductive coupling device 14 Figure 3 Main components of an MV phase-to-earth capacitive coupling device.15 Figure 4 Main components of an MV screen-to-earth intrusive inductive
26、coupling device .15 Figure 5 Power frequency voltage test 16 Figure 6 Impulse voltage test17 Annex ZA (normative) Normative references to international publications with their corresponding European publications18 Page3 EN61334322:2001 25October200161334-3-22 IEC:2001 4 INTRODUCTION Requirements of
27、IEC 61334-3-21 are applicable for phase-to-phase isolated capacitive coupling devices for power-line carrier systems on distribution line carriers (DLC). However, no international standard is available for the application of screen-to-earth intrusive inductive coupling devices. Furthermore the alrea
28、dy standardised earthed capacitive coupling device for high voltage power-line carrier systems as described by IEC 60481 is not suitable for the application of DLC on medium voltage (MV) networks for the following reasons: from a technical point of view, network characteristics differ considerably f
29、rom HV to MV networks; handling of HV and MV equipment requires different operational means; from an economical point of view, the coupling device should have a price as low as possible. These considerations have led to the present standardisation of other coupling devices such as the MV phase-to-ea
30、rth capacitive coupling device and the screen-to-earth intrusive inductive coupling device. Figures 1 and 2 show solutions for these devices. Additional solutions may become available later. As other coupling devices are standardised, new parts to IEC 61334 will be added. Page4 EN61334322:2001 25Oct
31、ober200161334-3-22 IEC:2001 5 DISTRIBUTION AUTOMATION USING DISTRIBUTION LINE CARRIER SYSTEMS Part 3-22: Mains signalling requirements MV phase-to-earth and screen-to-earth intrusive coupling devices 1 Scope and object This part of IEC 61334 is applicable to MV phase-to-earth capacitive and screen-t
32、o-earth intrusive inductive coupling devices for medium voltage (MV) distribution line carrier (DLC) systems. Non-intrusive inductive coupling devices are not within the scope of this standard. The coupling device ensures a) the efficient transmission/reception of carrier-frequency signals between t
33、he DLC transceiver and the power line; b) the safety of personnel and the protection of the low-voltage parts of the installation against the effects of the power-frequency voltage and transient overvoltages. The object of this part of IEC 61334 is to establish definitions, requirements, methods of
34、testing and rated values for phase-to-earth capacitive and screen-to-earth intrusive inductive coupling devices to be used in MV-DLC systems. 2 Normative references The following normative documents contain provisions which, through reference in this text, constitute provisions of part of IEC 61334.
35、 For dated references, subsequent amendments to, or revisions of, any of these publications do not apply. However, parties to agreements based on this part of IEC 61334 are encouraged to investigate the possibility of applying the most recent editions of the normative documents indicated below. For
36、undated references, the latest edition of the normative document referred to applies. Members of IEC and ISO maintain registers of currently valid International Standards. IEC 60060-1: High voltage test techniques Part 1: General definitions and test requirements IEC 60358: Coupling capacitors and c
37、apacitor dividers IEC 60870-2-2: Telecontrol equipment and systems Part 2: Operating conditions Section 2: Environmental conditions (climatic, mechanical and other non-electrical influences) Page5 EN61334322:2001 25October200161334-3-22 IEC:2001 6 3 Definitions For the purposes of this part of IEC 6
38、1334, the following definitions apply. 3.1 MV phase-to-earth coupling method method in which the coupling device is connected between the conductor of one phase of the power line and earth 3.2 MV screen-to-earth coupling method method in which the coupling device is connected between the screen of t
39、he power line cable and earth NOTE Coupling may be achieved by an intrusive coupler where a coupler is introduced between cable screen and earth, or a non-intrusive coupler such as a split core, where the coupler is mounted around the screen of the MV cable or around the earthing lead. In this latte
40、r case the screen-earth loop builds up the primary winding of a coupling transformer. 3.3 MV phase-to-phase coupling method method in which the coupling device is connected between the conductor of one phase and the conductor of another phase of the power line isolated from the earth potential 3.4 c
41、oupling device set of capacitive coupling devices and intrusive inductive coupling devices 3.5 capacitive coupling device arrangement of elements which contributes to ensuring, together with the associated coupling capacitor, the transmission/reception, under prescribed conditions, of carrier-freque
42、ncy signals between the power line and the DLC transceivers. The capacitive coupling device contributes to all or part of the functions described below (see figure 3): tuning at the desired carrier-frequency value. This function may be performed by a tuning device; impedance matching between the pow
43、er line and the DLC equipment. This function may be performed by a transformer or autotransformer; galvanic isolation between primary and secondary section terminals of the capacitive coupling device. This function may be performed by the above-mentioned transformer if present; draining to earth of
44、the power-frequency current derived by the coupling capacitor. This function may be performed by an inductance, termed drain coil, or by the primary winding of the previously mentioned transformer, if present; limitation of voltage surges coming from the power line at the terminals of the capacitive
45、 coupling device. This function may be performed by surge arresters suitably arranged in the coupling device; overcurrent protection at the primary terminal. This function may be performed by a fuse, which is in series with the coupling capacitor. NOTE In common practice the decision on installation
46、 of a fuse often is taken by the customer, with regard to local requirements and the power line system design. Thus this decision may be a matter of explicit agreement between customer and manufacturer. Page6 EN61334322:2001 25October200161334-3-22 IEC:2001 7 3.6 intrusive inductive coupling device
47、arrangement of elements which contributes to ensuring the transmission/reception, under prescribed conditions, of carrier-frequency signals between the cable screen and the DLC transceivers. The intrusive inductive coupling device contributes to all or part of the functions described below (see figu
48、re 4): tuning at the desired carrier-frequency value. This function may be performed by a tuning device; draining to earth of the power-frequency current. This function is performed by the primary winding of a transformer or autotransformer; impedance matching between the cable screen and the DLC eq
49、uipment. This function may be performed by the above-mentioned transformer or autotransformer; galvanic isolation between primary and secondary section terminals of the intrusive inductive coupling device. This function may be performed by the above-mentioned transformer, if present. 3.7 earth terminal terminal of the coupling device which is intended to be connected directly to the local station e