1、BSI Standards PublicationPowertrack systemsPart 21: Particular requirements for powertrack systems intended for wall and ceiling mountingBS EN 61534-21:2014National forewordThis British Standard is the UK implementation of EN 61534-21:2014. It isidentical to IEC 61534-21:2014. It supersedes BS EN 61
2、534-21:2006 which iswithdrawn.The UK participation in its preparation was entrusted to TechnicalCommittee PEL/213, Cable management.A list of organizations represented on this committee can be obtained onrequest to its secretary.This publication does not purport to include all the necessary provisio
3、ns of a contract. Users are responsible for its correct application. The British Standards Institution 2014.Published by BSI Standards Limited 2014ISBN 978 0 580 75730 3ICS 29.060.10; 29.120.20Compliance with a British Standard cannot confer immunity fromlegal obligations.This British Standard was p
4、ublished under the authority of theStandards Policy and Strategy Committee on 30 September 2014.Amendments/corrigenda issued since publicationDate Text affectedBRITISH STANDARDBS EN 61534-21:2014EUROPEAN STANDARD NORME EUROPENNE EUROPISCHE NORM EN 61534-21 August 2014 ICS 29.060.10; 29.120.20 Supers
5、edes EN 61534-21:2006 English Version Powertrack systems - Part 21: Particular requirements for powertrack systems intended for wall and ceiling mounting (IEC 61534-21:2014) Systmes de conducteurs prfabriqus - Partie 21: Exigences particulires pour les systmes de conducteurs prfabriqus destins au mo
6、ntage sur des murs et des plafonds (CEI 61534-21:2014) Stromschienensysteme - Teil 21: Besondere Anforderungen fr Stromschienensysteme fr Wand und Decke (IEC 61534-21:2014) This European Standard was approved by CENELEC on 2014-07-24. CENELEC members are bound to comply with the CEN/CENELEC Internal
7、 Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN
8、ELEC member. This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the same status as the officia
9、l versions. CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Mal
10、ta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom. European Committee for Electrotechnical Standardization Comit Europen de Normalisation Electrotechnique Europisches Komitee fr Elektrotechnische Normung CEN-CENELEC
11、Management Centre: Avenue Marnix 17, B-1000 Brussels 2014 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members. Ref. No. EN 61534-21:2014 E BS EN 61534-21:2014EN 61534-21:2014 - 2 - Foreword The text of document 23A/701/FDIS, future edition 2 of IEC
12、61534-21, prepared by SC 23A “Cable management systems“, of IEC/TC 23 “Electrical accessories“ was submitted to the IEC-CENELEC parallel vote and approved by CENELEC as EN 61534-21:2014. The following dates are fixed: latest date by which the document has to be implemented at national level by publi
13、cation of an identical national standard or by endorsement (dop) 2015-04-24 latest date by which the national standards conflicting with the document have to be withdrawn (dow) 2017-07-24 This document supersedes EN 61534-21:2006. Attention is drawn to the possibility that some of the elements of th
14、is document may be the subject of patent rights. CENELEC and/or CEN shall not be held responsible for identifying any or all such patent rights. This standard covers the Principle Elements of the Safety Objectives for Electrical Equipment Designed for Use within Certain Voltage Limits (LVD - 2006/95
15、/EC). Endorsement notice The text of the International Standard IEC 61534-21:2014 was approved by CENELEC as a European Standard without any modification. BS EN 61534-21:2014- 3 - EN 61534-21:2014 Annex ZA (normative) Normative references to international publications with their corresponding Europe
16、an publications The following documents, in whole or in part, are normatively referenced in this document and are indispensable for its application. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments)
17、applies. NOTE 1 When an International Publication has been modified by common modifications, indicated by (mod), the relevant EN/HD applies. NOTE 2 Up-to-date information on the latest versions of the European Standards listed in this annex is available here: www.cenelec.eu. Publication Year Title E
18、N/HD Year IEC 61534-1 + A1 2011 2014 Powertrack systems - Part 1: General requirements EN 61534-1 + A1 2011 2014 BS EN 61534-21:2014 2 IEC 61534-21:2014 IEC 2014 CONTENTS 1 Scope 5 2 Normative references 5 3 Terms and definitions 5 4 General requirements 6 5 General notes on tests 6 6 Ratings 6 7 Cl
19、assification . 6 8 Marking and documentation . 7 9 Construction 7 10 Clearances, creepage distances and solid insulation . 7 11 Protection against electric shock . 7 12 Terminals and terminations 7 13 Screws, current carrying parts and connections . 7 14 Mechanical strength 7 15 Insulation resistanc
20、e test and dielectric strength test . 9 16 Normal operation . 9 17 Temperature rise . 9 18 Short-circuit protection and short-circuit withstand strength . 9 19 Resistance to heat . 9 20 Fire hazard 9 21 External influences 9 22 Electromagnetic compatibility 9 Annex AA (normative) Additional test req
21、uirements for PT systems already complying with IEC 61534-21:2006 10 BS EN 61534-21:2014IEC 61534-21:2014 IEC 2014 5 POWERTRACK SYSTEMS Part 21: Particular requirements for powertrack systems intended for wall and ceiling mounting 1 Scope Clause 1 of IEC 61534-1:2011 and IEC 61534-1:2011/AMD1:2014 i
22、s applicable except as follows: 1.1 Addition: This part of IEC 61534 specifies the particular requirements and tests for PT systems intended for mounting on walls and/or ceiling. They may be installed flush or semi-flush, surface mounted, suspended or spaced away from the surface using fixing device
23、s. 2 Normative references Clause 2 of IEC 61534-1:2011 is applicable except as follows: Addition: IEC 61534-1:2011, Powertrack systems Part 1: General requirements IEC 61534-1:2011/AMD1:2014 3 Terms and definitions Clause 3 of IEC 61534-1:2011 and IEC 61534-1:2011/AMD1:2014 is applicable except as f
24、ollows: Additional terms and definitions: 3.101 wall PT system PT system which is suitable for mounting on a vertical surface or a vertical structure directly or with the use of fixing devices 3.102 ceiling PT system PT system which is suitable for mounting or suspending beneath a horizontal surface
25、 or horizontal structure directly or with the use of fixing devices 3.103 fixing devices system component used for the mechanical connection of the PT system to the supporting surface or supporting structure 3.104 external load mechanical load applied to the PT system from outside and not due to the
26、 mass of the system components BS EN 61534-21:2014 6 IEC 61534-21:2014 IEC 2014 3.105 suspension means mechanism for supporting a load (e.g. a luminaire) that hangs from the PT system 3.106 skirting PT system PT system which is suitable for mounting on the lower part of a wall close to the floor 4 G
27、eneral requirements Clause 4 of IEC 61534-1:2011 is applicable. 5 General notes on tests Clause 5 of IEC 61534-1:2011 is applicable except as follows: 5.3 Addition: 3 samples: subclause 14.3.101 3 samples: subclause 14.3.102 3 samples: subclause 14.3.103 6 Ratings Clause 6 of IEC 61534-1:2011 is app
28、licable. 7 Classification Clause 7 of IEC 61534-1:2011 is applicable except as follows: Additional subclauses: 7.101 According to external load withstand capability 7.101.1 Wall PT system 7.101.1.1 Wall PT system not intended to withstand an external load 7.101.1.2 Wall PT system capable of withstan
29、ding an external load from above 7.101.2 Ceiling PT system 7.101.2.1 Ceiling PT system not intended to withstand an external load 7.101.2.2 Ceiling PT system capable of withstanding an external load from above 7.102 According to provision for suspended loads 7.102.1 PT System without provision for s
30、uspended loads 7.102.2 PT System with provision for suspended loads BS EN 61534-21:2014IEC 61534-21:2014 IEC 2014 7 7.103 According to floor treatment when the PT system is mounted at the skirting position 7.103.1 Dry-treatment of floor 7.103.2 Wet-treatment of floor 8 Marking and documentation Clau
31、se 8 of IEC 61534-1:2011 and IEC 61534-1:2011/AMD1:2014 is applicable except as follows: 8.5 Addition of the following dashed items: for PT system according to 7.101.1.2 and 7.101.2.2, the maximum load in kg which can be withstood for PT system according to 7.102.2, the maximum load in kg which can
32、be suspended 9 Construction Clause 9 of IEC 61534-1:2011 is applicable. 10 Clearances, creepage distances and solid insulation Clause 10 of IEC 61534-1:2011 is applicable. 11 Protection against electric shock Clause 11 of IEC 61534-1:2011 and IEC 61534-1:2011/AMD1:2014 is applicable. 12 Terminals an
33、d terminations Clause 12 of IEC 61534-1:2011 is applicable. 13 Screws, current carrying parts and connections Clause 13 of IEC 61534-1:2011 and IEC 61534-1:2011/AMD1:2014 is applicable. 14 Mechanical strength Clause 14 of IEC 61534-1:2011 is applicable except as follows: 14.3 Static load test Delete
34、 subclauses 14.3.1, 14.3.2 and 14.3.3. Additional subclauses: 14.3.101 External load test PT systems shall withstand mechanical stresses applied to the PT system. BS EN 61534-21:2014 8 IEC 61534-21:2014 IEC 2014 Compliance is checked by the following test. At least two lengths of the PT system are j
35、oined together including the electrical connection and installed according to the manufacturers instructions to a rigid support; the joint shall be placed midway between the fixing devices. A steel plate with a length of (150 20) mm, a width not less than the PT system and a thickness of (5 1) mm is
36、 positioned on the upper surface of the PT system centrally at the midpoint between the supports. For classifications 7.101.1.1 and 7.101.2.1, a vertical force is gradually applied on the steel plate up to (350 10) N over a period of (60 1) s and maintained for (60 1) min. For classifications accord
37、ing to 7.101.1.2 and 7.101.2.2, a vertical force is gradually applied on the steel plate up to (750 10) N or with a force declared by the manufacturer 2 %, whichever is the higher over a period of (60 1) s and maintained for (60 1) min. During the tests, the sample shall not break and shall neither
38、have parts that have worked loose, nor shall it show any deformation likely to impair electrical safety. After the test: The sample shall comply with Clause 10 and 11.1 of IEC 61534-1:2011 and IEC 61534-1:2011/AMD1:2014. There shall be no permanent deformation, which would prevent the correct insert
39、ion and withdrawal of the tap-off units. The samples shall withstand the test according to 15.2 but without the pre-conditioning of 15.1, and the tests of 11.3 of IEC 61534-1:2011 and IEC 61534-1:2011/AMD1:2014. 14.3.102 PT systems with provision for suspended loads PT systems classified according t
40、o 7.102.2 shall withstand mechanical loads applied to the suspension means in normal use. Compliance is checked by the following test. The provision for the suspension means is installed as for normal use according to the manufacturers instructions. Screwed connections, if any, intended to provide m
41、echanical support of the suspension means are tightened to the torque given in the relevant column of Table 5 of IEC 61534-1:2011 if not specified by the manufacturer. The suspension means is then loaded, without jerks, with a force declared by the manufacturer 2 % or if no force is declared then th
42、e test shall be performed with a force of (250 5) N , for (24 1) h. During the test, the PT system and the suspension means shall not become detached from one another and shall show no damage, which leads to non-compliance with this standard. 14.3.103 PT systems with tap-off units In normal use, the
43、 construction of the tap-off unit shall be such as to prevent disconnection from the PT or live parts becoming accessible. Compliance is checked by the following test. The tap-off unit is inserted as in normal use 10 times and withdrawn 10 times in the tap-off outlet with the PT system installed in
44、normal use as declared by the manufacturer. BS EN 61534-21:2014IEC 61534-21:2014 IEC 2014 9 The tap-off unit is inserted once more into the tap-off outlet as in normal use and a withdrawal force of (30 1) N is applied for (60 5) s parallel to the force on the tap-off unit in normal use as declared b
45、y the manufacturer. The tap-off unit shall not become disconnected from the PT and live parts shall not become accessible when tested according to 11.1.1.1 of IEC 61534-1:2011 and IEC 61534-1:2011/AMD1:2014. 15 Insulation resistance test and dielectric strength test Clause 15 of IEC 61534-1:2011 is
46、applicable. 16 Normal operation Clause 16 of IEC 61534-1:2011 is applicable. 17 Temperature rise Clause 17 of IEC 61534-1:2011 is applicable. 18 Short-circuit protection and short-circuit withstand strength Clause 18 of IEC 61534-1:2011 is applicable. 19 Resistance to heat Clause 19 of IEC 61534-1:2
47、011 is applicable. 20 Fire hazard Clause 20 of IEC 61534-1:2011 is applicable. 21 External influences Clause 21 of IEC 61534-1:2011 is applicable except as follows: Delete subclause 21.1.3. Additional subclause: 21.2.101 Protection against ingress of water for wet treatment of the floor Where PT sys
48、tems are fitted at the skirting position and the floor is subject to wet treatment then the PT system shall have a minimum degree of protection of IP X4. 22 Electromagnetic compatibility Clause 22 of IEC 61534-1:2011 is applicable. BS EN 61534-21:2014 10 IEC 61534-21:2014 IEC 2014 Annexes The annexe
49、s of IEC 61534-1:2011 and IEC 61534-1:2011/AMD1:2014 are applicable except as follows: Additional annex: Annex AA (normative) Additional test requirements for PT systems already complying with IEC 61534-21:2006 PT systems already complying with IEC 61534-21:2006 only require testing in accordance with the following clauses if appropriate: 18 Short-circuit protection and short-circuit withstand strength. 21.2.101 According to floor treatment when the PT system is mounted at t