1、raising standards worldwideNO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAWBSI Standards PublicationPolymeric HV insulators for indoor and outdoor use General definitions, test methods and acceptance criteriaBS EN 62217:2013National forewordThis British Standard is the UK imple
2、mentation of EN 62217:2013. It is identical to IEC 62217:2012. It supersedes BS EN 62217:2006 which is withdrawn.The UK participation in its preparation was entrusted to Technical CommitteePEL/36, Insulators for power systems.A list of organizations represented on this committee can be obtained onre
3、quest to its secretary.This publication does not purport to include all the necessary provisions of acontract. Users are responsible for its correct application. The British Standards Institution 2013Published by BSI Standards Limited 2013ISBN 978 0 580 74888 2ICS 29.080.10Compliance with a British
4、Standard cannot confer immunity fromlegal obligations.This British Standard was published under the authority of the StandardsPolicy and Strategy Committee on 30 April 2013.Amendments issued since publicationAmd. No. Date Text affectedBRITISH STANDARDBS EN 62217:2013EUROPEAN STANDARD EN 62217 NORME
5、EUROPENNE EUROPISCHE NORM March 2013 CENELEC European Committee for Electrotechnical Standardization Comit Europen de Normalisation Electrotechnique Europisches Komitee fr Elektrotechnische Normung Management Centre: Avenue Marnix 17, B - 1000 Brussels 2013 CENELEC - All rights of exploitation in an
6、y form and by any means reserved worldwide for CENELEC members. Ref. No. EN 62217:2013 E ICS 29.080.10 Supersedes EN 62217:2006 English version Polymeric HV insulators for indoor and outdoor use - General definitions, test methods and acceptance criteria (IEC 62217:2012) Isolateurs polymriques haute
7、 tension pour utilisation lintrieur ou lextrieur - Dfinitions gnrales, mthodes dessai et critres dacceptation (CEI 62217:2012) Hochspannungs-Polymerisolatoren fr Innenraum- und Freiluftanwendung - Allgemeine Begriffe, Prfverfahren und Annahmekriterien (IEC 62217:2012) This European Standard was appr
8、oved by CENELEC on 2012-11-01. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such nati
9、onal standards may be obtained on application to the CEN-CENELEC Management Centre or to any CENELEC member. This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CENELEC member into its o
10、wn language and notified to the CEN-CENELEC Management Centre has the same status as the official versions. CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedoni
11、a, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom. BS EN 62217:2013EN 62217:2013 - 2 - Foreword The text of document 36/
12、321/FDIS, future edition 2 of IEC 62217, prepared by IEC TC 36 “Insulators“ was submitted to the IEC-CENELEC parallel vote and approved by CENELEC as EN 62217:2013. The following dates are fixed: latest date by which the document has to be implemented at national level by publication of an identical
13、 national standard or by endorsement (dop) 2013-09-08 latest date by which the national standards conflicting with the document have to be withdrawn (dow) 2015-11-01 This document supersedes EN 62217:2006. EN 62217:2013 includes the following significant technical change with respect to EN 62217:200
14、6: EN 62217:2006 included two other alternative tracking and erosion tests (a 5 000 hour multi-stress test and a tracking wheel test) which were based on tests developed by CIGRE and utilities. These tests are no longer given as normative alternatives following the results of a study/questionnaire b
15、y TC 36 on the relative merits of all three tracking and erosion tests. The 5 000 hour multi-stress test and a tracking wheel test are described in IEC/TR 62730:2012. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CENELEC and/or
16、CEN shall not be held responsible for identifying any or all such patent rights. Endorsement notice The text of the International Standard IEC 62217:2012 was approved by CENELEC as a European Standard without any modification. In the official version, for Bibliography, the following note has to be a
17、dded for the standard indicated: ISO 3274 NOTE Harmonized as EN ISO 3274. BS EN 62217:2013- 3 - EN 62217:2013 Annex ZA (normative) Normative references to international publications with their corresponding European publications The following documents, in whole or in part, are normatively reference
18、d in this document and are indispensable for its application. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. NOTE When an international publication has been modified by common modificatio
19、ns, indicated by (mod), the relevant EN/HD applies. Publication Year Title EN/HD Year IEC 60050-471 2007 International Electrotechnical Vocabulary - Part 471: Insulators - - IEC 60060-1 - High-voltage test techniques - Part 1: General definitions and test requirements EN 60060-1 - IEC 60068-2-11 - E
20、nvironmental testing - Part 2: Tests - Test Ka: Salt mist EN 60068-2-11 - IEC 60507 - Artificial pollution tests on high-voltage insulators to be used on a.c. systems EN 60507 - IEC 60695-11-10 - Fire hazard testing - Part 11-10: Test flames - 50 W horizontal and vertical flame test methods EN 60695
21、-11-10 - IEC 60721-1 - Classification of environmental conditions - Part 1: Environmental parameters and their severities EN 60721-1- IEC/TS 60815-1 - Selection and dimensioning of high-voltage insulators intended for use in polluted conditions - Part 1: Definitions, information and general principl
22、es - - ISO 868 - Plastics and ebonite - Determination of indentation hardness by means of a durometer (Shore hardness) EN ISO 868 - ISO 4287 - Geometrical Product Specifications (GPS) - Surface texture: Profile method - Terms, definitions and surface texture parameters EN ISO 4287 - ISO 4892-1 - Pla
23、stics - Methods of exposure to laboratory light sources - Part 1: General guidance EN ISO 4892-1 - ISO 4892-2 - Plastics - Methods of exposure to laboratory light sources - Part 2: Xenon-arc lamps EN ISO 4892-2 - BS EN 62217:2013 2 62217 IEC:2012 CONTENTS INTRODUCTION . 6 1 Scope and object 7 2 Norm
24、ative references . 7 3 Terms and definitions . 8 4 Identification . 10 5 Environmental conditions 10 6 Information on transport, storage and installation 11 7 Classification of tests 11 7.1 Design tests 11 7.2 Type tests . 12 7.3 Sample tests . 12 7.4 Routine tests . 12 8 General requirements for in
25、sulator test specimens 12 9 Design tests . 13 9.1 General . 13 9.2 Tests on interfaces and connections of end fittings . 13 9.2.1 General . 13 9.2.2 Test specimens 13 9.2.3 Reference voltage and temperature for verification tests . 13 9.2.4 Reference dry power frequency test . 13 9.2.5 Product speci
26、fic pre-stressing 13 9.2.6 Water immersion pre-stressing . 14 9.2.7 Verification tests 14 9.3 Tests on shed and housing material . 15 9.3.1 Hardness test 15 9.3.2 Accelerated weathering test . 15 9.3.3 Tracking and erosion test 1 000 h salt fog test Procedure 16 9.3.4 Flammability test 18 9.4 Tests
27、on the core material . 18 9.4.1 Porosity Test (Dye penetration test) . 18 9.4.2 Water diffusion test 19 Annex A (informative) Difference between the tracking and erosion and accelerated ageing test on polymeric insulators . 23 Annex B (informative) Recommended application of tests . 24 Annex C (info
28、rmative) Explanation of the concept of classes for the design tests 25 Bibliography . 26 Figure 1 Examples of test specimen for core material . 19 Figure 2 Example of boiling container for the water diffusion test 20 Figure 3 Electrodes for the voltage test 21 Figure 4 Voltage test circuit 22 BS EN
29、62217:201362217 IEC:2012 3 Table 1 Normal environmental conditions . 11 Table 2 Initial NaCl content of the water as a function of the specimen dimensions 17 Table 3 Flammability requirements 18 BS EN 62217:2013 6 62217 IEC:2012 INTRODUCTION Polymeric insulators consist either of one insulating mate
30、rial (resin insulators) or two or several insulating materials (composite insulators). The insulating materials are generally cross-linked organic materials synthesised from carbon or silicon chemistry and form the insulating body. Insulating materials can be composed from organic materials containi
31、ng various inorganic and organic ingredients, such as fillers and extenders. End fittings are often used at the ends of the insulating body to transmit mechanical loads. Despite these common features, the materials used and the construction details employed by different manufacturers may be widely d
32、ifferent. The tests given in this standard are those which are, in general, common to a great majority of insulator designs and materials, whatever their final application. They have been regrouped in this standard to avoid repetition in the relevant product standards and drift between procedures as
33、 the various product standards are drafted or revised. The majority of these tests have been grouped together as “Design tests“, to be performed only once for insulators of the same design. The design tests are intended to eliminate insulator designs, materials or manufacturing technologies which ar
34、e not suitable for high-voltage applications. The influence of time on the electrical properties of the complete polymeric insulator and its components (core material, housing, interfaces etc.) has been considered in specifying the design tests in order to ensure a satisfactory lifetime under normal
35、 operating and environmental conditions. Pollution tests, according to IEC 60507 or IEC 61245, are not included in this document, the applicability of their methodology to composite insulators not having been proven and still requiring study by CIGRE. The results of such pollution tests performed on
36、 insulators made of polymeric materials do not correlate with experience obtained from service. Specific pollution tests for polymeric insulators are still under consideration. The 1 000 hour salt-fog tracking and erosion test given in this second edition of IEC 62217 is considered as a screening te
37、st intended to reject materials or designs which are inadequate. This test is not intended to predict long term performance for insulator designs under cumulative service stresses. For more information, see Annex C. The first edition of IEC 62217 (2005) included two other alternative tracking and er
38、osion tests (a 5 000 hour multi-stress test and a tracking wheel test) which were based on tests developed by CIGRE and utilities. These tests are no longer given as normative alternatives following the results of a study/questionnaire by TC 36 on the relative merits of all three tracking and erosio
39、n tests. The 5 000 hour multi-stress test and a tracking wheel test are described in IEC/TR 62730 (2012). Composite insulators are used in both a.c. and d.c. applications. In spite of this fact a specific tracking and erosion test procedure for d.c. applications as a design test has not yet been def
40、ined and accepted. The 1 000 hour a.c. tracking and erosion test described in this standard is used to establish a minimum requirement for the tracking resistance of the housing material. IEC Guide 111 has been followed wherever possible during the preparation of this standard. BS EN 62217:201362217
41、 IEC:2012 7 POLYMERIC HV INSULATORS FOR INDOOR AND OUTDOOR USE GENERAL DEFINITIONS, TEST METHODS AND ACCEPTANCE CRITERIA 1 Scope and object This International Standard is applicable to polymeric insulators whose insulating body consists of one or various organic materials. Polymeric insulators cover
42、ed by this standard include both solid core and hollow insulators. They are intended for use on HV overhead lines and in indoor and outdoor equipment. The object of this standard is to define the common terms used for polymeric insulators; to prescribe common test methods for design tests on polymer
43、ic insulators; to prescribe acceptance or failure criteria, if applicable; These tests, criteria and recommendations are intended to ensure a satisfactory life-time under normal operating and environmental conditions (see Clause 5). This standard shall only be applied in conjunction with the relevan
44、t product standard. 2 Normative references The following documents, in whole or in part, are normatively referenced in this document and are indispensable for its application. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document
45、(including any amendments) applies. IEC 60050-471:2007, International Electrotechnical Vocabulary Part 471: Insulators IEC 60060-1, High-voltage test techniques Part 1: General definitions and test requirements IEC 60068-2-11, Environmental testing Part 2: Tests. Test KA: Salt mist IEC 60507, Artifi
46、cial pollution tests on high-voltage insulators to be used on a.c. systems IEC 60695-11-10, Fire hazard testing Part 11-10: Test flames 50 W horizontal and vertical flame test methods IEC 60721-1, Classification of environmental conditions Part 1: Environmental parameters and their severities IEC 60
47、815-1, Selection and dimensioning of high-voltage insulators intended for use in polluted conditions Part 1: Definitions, information and general principles ISO 868, Plastics and ebonite Determination of indentation hardness by means of a durometer (Shore hardness) BS EN 62217:2013 8 62217 IEC:2012
48、ISO 4287, Geometrical Product Specifications (GPS) Surface Texture: Profile method Terms, definitions and surface texture parameters ISO 4892-1, Plastics Methods of exposure to laboratory light sources Part 1: General Guidance ISO 4892-2, Plastics Methods of exposure to laboratory light sources Part
49、 2: Xenon-arc sources 3 Terms and definitions For the purposes of this document the terms and definitions given in IEC 60050-471:2007 and the following apply: 3.1 high voltage (HV) voltage over 1 000 V a.c. or over 1 500 V d.c. or over 1 500 V peak value 3.2 polymeric insulator insulator whose insulating body consists of at least one organic based material Note 1 to entry: Polymeric insulators are also known as non-ceramic insulators. Note 2 to entry: Coupli