1、raising standards worldwideNO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAWBSI Standards PublicationDigital addressable lighting interface Part 205: Particular requirements for control gear Supply voltage controller for incandescent lamps (device type 4)BS EN 62386-205:2009Lice
2、nsed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 14/04/2010 07:45, Uncontrolled Copy, (c) BSINational forewordThis British Standard is the UK implementation of EN 62386-205:2009. It isidentical to IEC 62386-205:2009.The UK participation in its preparation was entrusted by Technical CommitteeCPL/34
3、, Lamps and related equipment, to Subcommittee CPL/34/3, Auxiliariesfor lamps.A list of organizations represented on this committee can be obtained onrequest to its secretary.This publication does not purport to include all the necessary provisions of acontract. Users are responsible for its correct
4、 application. BSI 2010ISBN 978 0 580 57540 2ICS 29.140.50; 29.140.99Compliance with a British Standard cannot confer immunity fromlegal obligations.This British Standard was published under the authority of the StandardsPolicy and Strategy Committee on 31 January 2010Amendments issued since publicat
5、ionAmd. No. Date Text affectedBRITISH STANDARDBS EN 62386-205:2009Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 14/04/2010 07:45, Uncontrolled Copy, (c) BSIEUROPEAN STANDARD EN 62386-205 NORME EUROPENNE EUROPISCHE NORM November 2009 CENELEC European Committee for Electrotechnical Standardiz
6、ation Comit Europen de Normalisation Electrotechnique Europisches Komitee fr Elektrotechnische Normung Central Secretariat: Avenue Marnix 17, B - 1000 Brussels 2009 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members. Ref. No. EN 62386-205:2009 E
7、ICS 29.140.50; 29.140.99 English version Digital addressable lighting interface - Part 205: Particular requirements for control gear - Supply voltage controller for incandescent lamps (device type 4) (IEC 62386-205:2009) Interface dclairage adressable numrique - Partie 205: Exigences particulires po
8、ur les appareillages de commande - Variateur de tension dalimentation pour les lampes incandescence (dispositifs de type 4) (CEI 62386-205:2009) Digital adressierbare Schnittstelle fr die Beleuchtung - Teil 205: Besondere Anforderungen an Betriebsgerte - Versorgungsspannungsregler fr Glhlampen (Gert
9、etyp 4) (IEC 62386-205:2009) This European Standard was approved by CENELEC on 2009-09-01. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-da
10、te lists and bibliographical references concerning such national standards may be obtained on application to the Central Secretariat or to any CENELEC member. This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under
11、 the responsibility of a CENELEC member into its own language and notified to the Central Secretariat has the same status as the official versions. CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Cyprus, the Czech Republic, Denmark, Estonia, Finland, Franc
12、e, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom. BS EN 62386-205:2009Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 14/04/2010
13、 07:45, Uncontrolled Copy, (c) BSIEN 62386-205:2009 - 2 - Foreword The text of document 34C/819/CDV, future edition 1 of IEC 62386-205, prepared by SC 34C, Auxiliaries for lamps, of IEC TC 34, Lamps and related equipment, was submitted to the IEC-CENELEC parallel vote and was approved by CENELEC as
14、EN 62386-205 on 2009-09-01. This standard is to be used in conjunction with EN 62386-101 and EN 62386-102, which contain general requirements for the relevant product type (control gear or control devices). The following dates were fixed: latest date by which the EN has to be implemented at national
15、 level by publication of an identical national standard or by endorsement (dop) 2010-06-01 latest date by which the national standards conflicting with the EN have to be withdrawn (dow) 2012-09-01 Annex ZA has been added by CENELEC. _ Endorsement notice The text of the International Standard IEC 623
16、86-205:2009 was approved by CENELEC as a European Standard without any modification. In the official version, for Bibliography, the following notes have to be added for the standards indicated: IEC 60598-1 NOTE Harmonized as EN 60598-1:2008 (modified). IEC 60669-2-1 NOTE Harmonized as EN 60669-2-1:2
17、004 (modified). IEC 60921 NOTE Harmonized as EN 60921:2004 (not modified). IEC 60923 NOTE Harmonized as EN 60923:2005 (not modified). IEC 60925 NOTE Harmonized as EN 60925:1991 (not modified). IEC 60929 NOTE Harmonized as EN 60929:2006 (not modified). IEC 61347-1 NOTE Harmonized as EN 61347-1:2008 (
18、modified). IEC 61347-2-3 NOTE Harmonized as EN 61347-2-3:2001 (not modified). IEC 61547 NOTE Harmonized as EN 61547:1995 (not modified). CISPR 15 NOTE Harmonized as EN 55015:2006 (not modified). _ BS EN 62386-205:2009Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 14/04/2010 07:45, Uncontroll
19、ed Copy, (c) BSI- 3 - EN 62386-205:2009 Annex ZA (normative) Normative references to international publications with their corresponding European publications The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited appli
20、es. For undated references, the latest edition of the referenced document (including any amendments) applies. NOTE When an international publication has been modified by common modifications, indicated by (mod), the relevant EN/HD applies. Publication Year Title EN/HD Year IEC 62386-101 2009 Digital
21、 addressable lighting interface - Part 101: General requirements - System EN 62386-101 2009 IEC 62386-102 2009 Digital addressable lighting interface - Part 102: General requirements - Control gearEN 62386-102 2009 BS EN 62386-205:2009Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 14/04/2010
22、 07:45, Uncontrolled Copy, (c) BSI 2 62386-205 IEC:2009 CONTENTS INTRODUCTION.5 1 Scope.6 2 Normative references .6 3 Terms and definitions .6 4 General description 7 5 Electrical specifications 7 6 Interface power supply .7 7 Transmission protocol structure7 8 Timing 7 9 Method of operation .7 10 D
23、eclaration of variables8 11 Definition of commands 9 12 Test procedures .16 Bibliography27 Figure 1 Application extended configuration command sequence example.10 Figure 2 Test sequence QUERY DIMMER STATUS and QUERY FEATURES .17 Figure 3 Test sequence QUERY FAILURE STATUS.18 Figure 4 Test sequence C
24、OMMANDS 242 to 248 .20 Figure 5 Test sequence SELECT DIMMING CURVE, QUERY DIMMING CURVE and QUERY DIMMER STATUS .21 Figure 6 Test sequence REFERENCE SYSTEM POWER .22 Figure 7 Test sequence REFERENCE SYSTEM POWER .23 Figure 8 Test sequence QUERY REFERENCE MEASUREMENT FAILED 24 Figure 9 Test sequence
25、QUERY EXTENDED VERSION NUMBER .25 Figure 10 Test sequence RESERVED APPLICATION EXTENDED COMMANDS26 Table 1 Declaration of variables.8 Table 2 Dimming method bits.12 Table 3 Summary of the application extended command set 15 Table 4 Command 241 QUERY FAILURE STATUS test conditions.19 Table 5 Query co
26、mmands 242 to 248 test table .20 BS EN 62386-205:2009Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 14/04/2010 07:45, Uncontrolled Copy, (c) BSI62386-205 IEC:2009 5 INTRODUCTION This first edition of IEC 62386-205 is published in conjunction with IEC 62386-101 and IEC 62386-102. The division
27、 of IEC 62386 into separately published parts provides for ease of future amendments and revisions. Additional requirements will be added as and when a need for them is recognized. This International Standard, and the other parts that make up the IEC 62386-200 series, in referring to any of the clau
28、ses of IEC 62386-101 or IEC 62386-102, specify the extent to which such a clause is applicable and the order in which the tests are to be performed. The parts also include additional requirements, as necessary. All parts that make up the IEC 62386-200 series are self-contained and therefore do not i
29、nclude references to each other. Where the requirements of any of the clauses of IEC 62386-101 or IEC 62386-102 are referred to in this International Standard by the sentence “The requirements of IEC 62386-1XX, clause n apply”, this sentence is to be interpreted as meaning that all requirements of t
30、he clause in question of Part 101 or Part 102 apply, except any which are inapplicable to the specific type of lamp control gear covered by Part 205. All numbers used in this International Standard are decimal numbers unless otherwise noted. Hexadecimal numbers are given in the format 0xVV, where VV
31、 is the value. Binary numbers are given in the format XXXXXXXXb or in the format XXXX XXXX, where X is 0 or 1; “x“ in binary numbers means “dont care“. BS EN 62386-205:2009Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 14/04/2010 07:45, Uncontrolled Copy, (c) BSI 6 62386-205 IEC:2009 DIGITAL
32、 ADDRESSABLE LIGHTING INTERFACE Part 205: Particular requirements for control gear Supply voltage controller for incandescent lamps (device type 4) 1 Scope This International Standard specifies a protocol and test procedures for the control by digital signals of electronic control gear associated wi
33、th incandescent lamps. 2 Normative references The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. IEC
34、 62386-101:2009, Digital addressable lighting interface Part 101: General requirements System IEC 62386-102:2009, Digital addressable lighting interface Part 102: General requirements Control gear 3 Terms and definitions For the purposes of this document, the terms and definitions given in Clause 3
35、of IEC 62386-101:2009 and Clause 3 of IEC 62386-102:2009 apply, together with the following. 3.1 reference measurement measurement of the actual lamp load NOTE Control gear determines the actual lamp load with internal procedures and measurements, not specified by this standard. 3.2 detection of loa
36、d decrease recognition that the actual lamp load is significantly below the load measured during a successful reference measurement NOTE The criteria for regarding a load increase or decrease as significant can only be defined by the manufacturer, and these criteria should be described in the manual
37、. 3.3 detection of load increase recognition that the actual lamp load is significantly above the load measured during a successful reference measurement NOTE The criteria for regarding a load increase or decrease as significant can only be defined by the manufacturer, and these criteria should be d
38、escribed in the manual. 3.4 thermal overload the maximum permissible gear temperature is exceeded BS EN 62386-205:2009Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 14/04/2010 07:45, Uncontrolled Copy, (c) BSI62386-205 IEC:2009 7 3.5 thermal shut down gear switches off the lamp because autom
39、atic reduction of output level failed to prevent a persistent thermal overload 3.6 light level reduction due to thermal overload light level reduction with the objective of decreasing gear temperature. 3.7 load over-current shutdown gear switches off the lamp because automatic reduction of output le
40、vel failed to prevent a persistent over-current condition. 4 General description The requirements of Clause 4 of IEC 62386-101:2009 and Clause 4 of IEC 62386-102:2009 shall apply. 5 Electrical specifications The requirements of Clause 5 of IEC 62386-101:2009 and Clause 5 of IEC 62386-102:2009 shall
41、apply. 6 Interface power supply The requirements of Clause 6 of IEC 62386-101:2009 and Clause 6 of IEC 62386-102:2009 shall apply if a power supply is integrated with the control gear. 7 Transmission protocol structure The requirements of Clause 7 of IEC 62386-101:2009 and Clause 7 of IEC 62386-102:
42、2009 shall apply. 8 Timing The requirements of Clause 8 of IEC 62386-101:2009 and Clause 8 of IEC 62386-102:2009 shall apply. 9 Method of operation 9.1 General The requirements of Clause 9 of IEC 62386-101:2009 and Clause 9 of IEC 62386-102:2009 shall apply with the following additions and adaptatio
43、ns: The dimming curve, whether logarithmic or linear, shall apply for a lamp type and rating suitable for the use by the control gear. The dimming mode in the case of a fixed-mode universal dimmer shall only be changeable by the means of a switch or other physical controls on the dimmer, and not fro
44、m the interface. NOTE This eliminates the danger of unintentional changes during system programming. BS EN 62386-205:2009Licensed Copy: Wang Bin, ISO/EXCHANGE CHINA STANDARDS, 14/04/2010 07:45, Uncontrolled Copy, (c) BSI 8 62386-205 IEC:2009 9.2 Detection of load decrease If the actual lamp load is
45、significantly below the load measured during a successful reference measurement, the control gear might switch off the lamp if this is necessary for its safe operation and the flag bit load decrease shall be set. 9.3 Detection of load increase If the actual lamp load is significantly above the load
46、measured during a successful reference measurement, the control gear might switch off if this is necessary for its safe operation and the flag bit load increase shall be set. 9.4 Lamp replacement on control gear with load increase/decrease feature If a lamp is replaced with one of a different power,
47、 the control gear may falsely detect load decrease or load increase. In this case, correct detection of load decrease or load increase shall require a successful REFERENCE SYSTEM POWER measurement. NOTE In some cases, replacement of a lamp with one of the same power may require a new REFERENCE SYSTE
48、M MEASUREMENT for correct detection of load decrease or load increase. 10 Declaration of variables The requirements of Clause 10 of IEC 62386-101:2009 and Clause 10 of IEC 62386-102:2009 shall apply, with the following additional variables for this device type, indicated in Table 1. Table 1 Declarat
49、ion of variables Variable Default value Reset value Range of validity Memory a“DIMMING CURVE” 0 No change 0 1; (2 255 reserved) 1 byte “DIMMER STATUS” 0000 00UU bNo change except bit 4 is reset to 0 0 - 255 1 byte RAM c“DIMMER FEATURES” Factory burn-in No change 0 - 255 each byte 3 bytes ROM “FAILURE STATUS BYTE 1” UUU0 UUUU bNo change 0 - 255 1 byte RAM c“FAILURE STATUS BYTE 2” 000U UUUU bNo change 0