1、May 2012 Translation by DIN-Sprachendienst.English price group 12No part of this translation may be reproduced without prior permission ofDIN Deutsches Institut fr Normung e. V., Berlin. Beuth Verlag GmbH, 10772 Berlin, Germany,has the exclusive right of sale for German Standards (DIN-Normen).ICS 75
2、.200!$|=“1892627www.din.deDDIN EN 13617-2Petrol filling stations Part 2: Safety requirements for construction and performance of safebreaks for use on metering pumps and dispensersEnglish translation of DIN EN 13617-2:2012-05Tankstellen Teil 2: Sicherheitstechnische Anforderungen an Bau- und Arbeits
3、weise vonAbreikupplungen fr Zapfsulen und druckversorgte ZapfsulenEnglische bersetzung von DIN EN 13617-2:2012-05Stations-service Partie 2: Exigences de scurit relatives la construction et aux performances desraccords cassants utiliss pour les distributeurs de carburantTraduction anglaise de DIN EN
4、13617-2:2012-05SupersedesDIN EN 13617-2:2004-12www.beuth.deDocument comprises 21 pagesIn case of doubt, the German-language original shall be considered authoritative.04.12 DIN EN 13617-2:2012-05 2 A comma is used as the decimal marker. National foreword This standard has been prepared by Technical
5、Committee CEN/TC 393 “Equipment for storage tanks and for service stations” (Secretariat: DIN, Germany). The responsible German body involved in its preparation was the Normenausschuss Tankanlagen (Tank Installations Standards Committee), Working Committee NA 104-02-06 AA Abgabeeinrichtungen an Tank
6、stellen. Amendments This standard differs from DIN EN 13617-2:2004-12 as follows: a) a new note has been added at the end of the scope; b) an informative Annex C regarding environmental aspects has been included; c) normative references have been updated. Previous editions DIN EN 13617-2: 2004-12 EU
7、ROPEAN STANDARD NORME EUROPENNE EUROPISCHE NORM EN 13617-2 March 2012 ICS 75.200 Supersedes EN 13617-2:2004English Version Petrol filling stations - Part 2: Safety requirements for construction and performance of safe breaks for use on metering pumps and dispensers Stations-service - Partie 2: Exige
8、nces de scurit relatives la construction et aux performances des raccords cassants utiliss pour les distributeurs de carburant Tankstellen - Teil 2: Sicherheitstechnische Anforderungen an Bau- und Arbeitsweise von Abreikupplungen fr Zapfsulen und druckversorgte Zapfsulen This European Standard was a
9、pproved by CEN on 28 January 2012. CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such nati
10、onal standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN member. This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own langu
11、age and notified to the CEN-CENELEC Management Centre has the same status as the official versions. CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latv
12、ia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United Kingdom. EUROPEAN COMMITTEE FOR STANDARDIZATION COMIT EUROPEN DE NORMALISATION EUROPISCHES KOMITEE FR NORMUNG Management Centre: Avenue Marnix 17, B-100
13、0 Brussels 2012 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 13617-2:2012: EEN 13617-2:2012 (E) 2 Contents Page Foreword 31 Scope 42 Normative references 43 Terms and definitions .54 Explosion protection measures .55 Constructio
14、n .55.1 General 55.2 Hose breaks 65.3 Inlet threads 65.3.1 Safe break type 1 .65.3.2 Safe break type 2 .66 Physical properties 77 Operational requirements .88 Overview of tests .99 Information for use . 109.1 General . 109.2 Marking and instruction . 10Annex A (normative) General requirements of tes
15、t 11A.1 General . 11A.2 Tightness test 1 . 11A.3 Pressure separation test 1 . 11Annex B (normative) Tests 12B.1 Test liquid 12B.2 Fuel compatibility pre-conditioning 12B.3 Pre-conditioning mechanical impact test of re-usable safe breaks 12B.4 Tightness test 2 . 12B.5 Pressure separation test 2 . 13B
16、.6 Pressure test . 13B.7 Axial separation force test 1 13B.8 Axial separation force test 2 to nozzle breaks and pump breaks 13B.9 Non-axial separation force test 1 to nozzle breaks and pump breaks 14B.10 Non-axial separation force test 2 to nozzle breaks and pump breaks 14B.11 Axial separation force
17、 test 3 14B.12 Axial separation force test 4 14B.13 Liquid release test 14B.14 Re-connection test 1 15B.15 Re-connection test 2 15B.16 Electrical resistance test 15Annex C (informative) Environmental aspects 16Annex ZA (informative) Relationship between this European Standard and the Essential Requi
18、rements of EU Directive 94/9/EC 18Bibliography . 19DIN EN 13617-2:2012-05 EN 13617-2:2012 (E) 3 Foreword This document (EN 13617-2:2012) has been prepared by Technical Committee CEN/TC 393 “Equipment for tanks and filling stations”, the secretariat of which is held by DIN. This European Standard sha
19、ll be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by September 2012, and conflicting national standards shall be withdrawn at the latest by September 2012. Attention is drawn to the possibility that some of the elements of this
20、 document may be the subject of patent rights. CEN and/or CENELEC shall not be held responsible for identifying any or all such patent rights. This document supersedes EN 13617-2:2004. This document has been prepared under a mandate given to CEN by the European Commission and the European Free Trade
21、 Association, and supports essential requirements of EU Directive(s). For relationship with EU Directive(s), see informative Annex ZA, which is an integral part of this document. According to edition EN 13617-2:2004 the following fundamental changes are given: a new note at the end of the scope: Fue
22、ls other than of Explosion Group IIA are excluded from this European Standard added; informative Annex C concerning environmental aspects added. The present standard is composed of the following parts: Part 1: Safety requirements for construction and performance of metering pumps, dispensers and rem
23、ote pumping units; Part 2: Safety requirements for construction and performance of safe breaks for use on metering pumps and dispensers; Part 3: Safety requirements for construction and performance of shear valves; Part 4: Safety requirements for construction and performance of swivels for use on me
24、tering pumps and dispensers. According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Gree
25、ce, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom. DIN EN 13617-2:2012-05 EN 13617-2:2012 (E) 4 1 Scope This European Standard specifies safety requ
26、irements for the construction and performance of safe breaks to be fitted to metering pumps and dispensers installed at filling stations and used to dispense liquid fuels into the tanks of motor vehicles, boats and light aircraft and into portable containers at flow rates up to 200 l min-1. The requ
27、irements apply to safe breaks at ambient temperatures from 20 C to +40 C with the possibility for an extended temperature range. It pays particular attention to electrical, mechanical and hydraulic characteristics of, and electrical apparatus incorporated within or mounted on, the safe break. This E
28、uropean Standard applies mainly to hazards related to the ignition of liquid fuels being dispensed or their vapour. This European Standard also addresses electrical and mechanical hazards. NOTE 1 This European Standard does not apply to equipment for use with liquefied petroleum gas (LPG) or liquefi
29、ed natural gas (LNG) or compressed natural gas (CNG). NOTE 2 Fuels other than of Explosion Group IIA are excluded from this European Standard. 2 Normative references The following documents, in whole or in part, are normatively referenced in this document and are indispensable for its application. F
30、or dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 228, Automotive fuels Unleaded petrol Requirements and test methods EN 1127-1, Explosive atmospheres Explosion prevention and protection P
31、art 1: Basic concepts and methodology EN 1360, Rubber and plastic hoses and hose assemblies for measured fuel dispensing systems Specification EN 13463-1:2009, Non-electrical equipment for use in potentially explosive atmospheres Part 1: Basic method and requirements EN 13483, Rubber and plastic hos
32、es and hose assemblies with internal vapour recovery for measured fuel dispensing systems Specification prEN 13617-1:2010, Petrol filling stations Part 1: Safety requirements for the construction and performance of metering pumps, dispensers and remote pumping units EN 60079-0, Explosive atmospheres
33、 Part 0: Equipment General requirements EN ISO 228-1, Pipe threads where pressure-tight joints are not made on the threads Part 1: Dimensions, tolerances and designation (ISO 228-1) EN ISO 1825, Rubber hoses and hose assemblies for aircraft ground fuelling and defuelling Specification (ISO 1825) EN
34、ISO 8031:2009, Rubber and plastics hoses and hose assemblies Determination of electrical resistance and conductivity (ISO 8031:2009) ISO 261, ISO general-purpose metric screw threads General plan ISO 965-2, ISO general purpose metric screw threads Tolerances Part 2: Limits of sizes for general purpo
35、se external and internal screw threads Medium quality ISO 11925-3, Reaction to fire tests Ignitability of building products subjected to direct impingement of flame Part 3: Multi-source test DIN EN 13617-2:2012-05 EN 13617-2:2012 (E) 5 3 Terms and definitions For the purposes of this document, the t
36、erms and definitions given in prEN 13617-1:2010 and the following apply. 3.1 safe break device to minimize fuel spillage and to stop fuel flow achieved by separation between nozzle and metering pump or dispenser within a defined range of forces 3.2 safe break type 1 safe break constructed for liquid
37、 lines only 3.3 safe break type 2 safe break constructed for liquid lines combined with vapour recovery lines 3.4 nozzle break safe break fitted directly into the nozzle inlet, or integral with the nozzle 3.5 hose break safe break fitted within the delivery hose circuit 3.6 pump break safe break fit
38、ted directly to the fixed hydraulics 3.7 re-usable safe break safe break that, once operated, may be re-assembled for further use 3.8 non re-usable safe break safe break that, once operated, cannot be re-assembled for further use 4 Explosion protection measures 4.1 Explosion protection measures shal
39、l be taken in accordance with EN 11271 and Annex B of prEN 13617-1:2010. 4.2 The safe break shall be explosion protected and shall be Category 2 in accordance with EN 134631. The vapour path of a vapour recovery safe break shall be Category 1 in accordance with EN 134631. The safe break shall fulfil
40、 the requirements for temperature class T3 and Group IIA to EN 60079-0 or EN 134631. 5 Construction 5.1 General 5.1.1 All electrical and non-electrical equipment and components, intended for use in potentially explosive atmospheres, shall be designed and constructed according to good engineering pra
41、ctice and in conformity with the required categories for group II equipment to ensure avoidance of any ignition source. To classify the category of the equipment it shall be subjected to an ignition hazard assessment in accordance with 5.2 of EN 13463-1:2009. 5.1.2 All materials used in the construc
42、tion shall be chemically and dimensionally stable under known service conditions. Materials likely to come into contact with fuels in both liquid and vapour phases shall be resistant to attack by these fuels. Compliance shall be demonstrated by manufacturers declaration and compliance with the tests
43、 B.1 to B.16 inclusive. DIN EN 13617-2:2012-05 EN 13617-2:2012 (E) 6 5.1.3 Light alloys when used shall conform to the requirements of 6.4.4.2 of EN 134631:2009. If other specifications for explosion protected equipment impose more stringent requirements then the more stringent requirement shall app
44、ly. 5.1.4 Outside surfaces likely to be handled shall be free of sharp edges. 5.1.5 If protective covers are fitted they shall be constructed such that they allow ventilation and evaporation of fuel even if some shrinkage occurs. They shall not affect the performance of the safe break. 5.1.6 Safe br
45、eaks Type 1 and Type 2, except nozzle breaks, when operated shall close liquid lines both up stream and down stream of the break. 5.1.7 For safe breaks Type 2 it is not required to close vapour lines either side of the break. A means to close off vapour lines may be included. 5.1.8 On re-usable safe
46、 breaks, the sections that break away shall be constructed so that the means of reconnection cannot be damaged by impacts suffered as a result of separation. 5.1.9 The construction shall be such that on reconnection of a re-usable device, or attempted reconnection of a non re-usable device, fluid sh
47、all not be sprayed out during the reconnection action. 5.2 Hose breaks Hose breaks which incorporate hose shall use hose conforming to EN 1360, EN ISO 1825 or EN 13483. 5.3 Inlet threads 5.3.1 Safe break type 1 Form 1 threads for the hose connection shall be parallel threads according to EN ISO 2281
48、 according to Table 1. The sealing surfaces of the internal and external threads shall be designed such that they are suitable for use with an appropriate seal. Table 1 Form 1 Thread specifications Nominal inlet size inch FEMALE THREADSa MALE THREADSb Maximum thread depth mm Minimum thread length mm ” 12,5 11,01” 15,5 14,01 1/4