1、April 2010 Translation by DIN-Sprachendienst.English price group 9No part of this translation may be reproduced without prior permission ofDIN Deutsches Institut fr Normung e. V., Berlin. Beuth Verlag GmbH, 10772 Berlin, Germany,has the exclusive right of sale for German Standards (DIN-Normen).ICS 1
2、3.220.10!$b9“1632257www.din.deDDIN EN 15182-4Hand-held branchpipes for fire service use Part 4: High pressure branchpipes PN 40 (includes Amendment A1:2009)English translation of DIN EN 15182-4:2010-04Strahlrohre fr die Brandbekmpfung Teil 4: Hochdruckstrahlrohre PN 40 (enthlt nderung A1:2009)Englis
3、che bersetzung von DIN EN 15182-4:2010-04Lances main destines aux services dincendie et de secours Partie 4: Lances haute pression PN 40 (Amendement A1:2009 inclus)Traduction anglaise de DIN EN 15182-4:2010-04SupersedesDIN EN 15182-4:2007-05www.beuth.deIn case of doubt, the German-language original
4、shall be considered authoritative.Document comprises 13 pages04.10 DIN EN 15182-4:2010-04 2 A comma is used as the decimal marker. National foreword This standard has been prepared by Technical Committee CEN/TC 192 “Fire service equipment” (Secretariat: BSI, United Kingdom), Working Group WG 8 “Port
5、able equipment for projecting extinguishing agents supplied by fire fighting pumps” (Secretariat: AFNOR, France). The responsible German body involved in its preparation was the Normenausschuss Feuerwehrwesen (Fire-fighting and Fire Protection Standards Committee), Working Committee NA 031-04-04 AA
6、Schluche und Armaturen. The modifications made to the previous edition, DIN EN 15182-4:2007-05, were necessary to leave as little room for interpretation as possible. A national standard on high pressure branchpipes did not exist until the publication of the previous edition DIN EN 15182-4:2007-05.
7、This European Standard does not specify requirements relating to couplings for connection to pressure hoses as there are no European Standards on couplings for this purpose. For this reason, these should be specifically agreed at the time of ordering in order to ensure the compatibility of all firef
8、ighting water supply system components in Germany. For high pressure branchpipes PN 40 to DIN EN 15182-4 there are no standardized solid couplings PN 40 available. It is recommended to use screwed connections. Attention is drawn to the possibility that some of the elements of this document may be th
9、e subject of patent rights. DIN shall not be held responsible for identifying any or all such patent rights. Branchpipes complying with this European Standard may be marked with a suitable markN1)as proof of conformity. Amendments This standard differs from DIN EN 15182-4:2007-05 as follows: a) In t
10、he definitions of the high pressure branchpipes and types, “variable pattern” has been replaced by “adjustable pattern”. b) The reference pressure for the determination of the hydraulic characteristics is now 6 bar 0,1 bar. Previous editions DIN EN 15182-4: 2007-05 N1) National footnote: The Normena
11、usschuss Feuerwehrwesen (Firefighting and Fire Protection Standards Committee) of DIN provides information on suitable marks of conformity at: DIN, Burggrafenstrae 6, 10787 Berlin. This information is also available online at www.fnfw.din.de. EUROPEAN STANDARD NORME EUROPENNE EUROPISCHE NORM EN 1518
12、2-4:2007+A1 November 2009 ICS 13.220.10 Supersedes EN 15182-4:2007English Version Hand-held branchpipes for fire service use - Part 4: High pressure branchpipes PN 40 Lances main destines aux services dincendie et de secours - Partie 4: Lances haute pression PN 40 Strahlrohre fr die Brandbekmpfung -
13、 Teil 4: Hochdruckstrahlrohre PN 40 This European Standard was approved by CEN on 23 December 2006 and includes Amendment 1 approved by CEN on 29 September 2009. CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard
14、 the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN Management Centre or to any CEN member. This European Standard exists in three official versions (English, French, G
15、erman). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as the official versions. CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czec
16、h Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom. EUROPEAN COMMITTEE FOR STANDARDIZATION COMIT EURO
17、PEN DE NORMALISATION EUROPISCHES KOMITEE FR NORMUNG Management Centre: Avenue Marnix 17, B-1000 Brussels 2009 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 15182-4:2007+A1:2009: EEN 15182-4:2007+A1:2009 (E) 2 Contents Page Forewo
18、rd 3 1 Scope 4 2 Normative references 4 3 Terms and definitions .4 4 Requirements .5 5 Testing and proofs.9 DIN EN 15182-4:2010-04 EN 15182-4:2007+A1:2009 (E) 3 Foreword This document (EN 15182-4:2007+A1:2009) has been prepared by Technical Committee CEN/TC 192 “Fire service equipment”, the secretar
19、iat of which is held by BSI. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by May 2010, and conflicting national standards shall be withdrawn at the latest by May 2010. Attention is drawn to the po
20、ssibility that some of the elements of this document may be the subject of patent rights. CEN and/or CENELEC shall not be held responsible for identifying any or all such patent rights. This document includes Amendment 1, approved by CEN on 2009-09-29. This document supersedes EN 15182-4:2007. The s
21、tart and finish of text introduced or altered by amendment is indicated in the text by tags!“X EN 15182 consists of the following parts, under the general title Hand-held branchpipes for fire service use: Part 1 : Common requirements; Part 2 : Combination branchpipes PN 16; Part 3 : Smooth bore jet
22、and/or one fixed spray jet angle branchpipes PN 16; Part 4: High pressure branchpipes PN 40. According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Cyprus, Czech Rep
23、ublic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom. DIN EN 15182-4:2010-04 EN 15182-4:2007+A1:2009 (E) 4 1
24、 Scope In addition to the requirements given in EN 15182-1, this document applies to hand-held high pressure branchpipes (nozzles) PN 40 with a maximum flow rate of 200 l/min at a reference pressure of 6 bar (0,6 MPa). It deals with: safety requirements; performance requirements; test methods; class
25、ification and designation; operating instructions; marking and maintenance. This part of this European Standard applies to branchpipes as defined in Annex A of EN 15182-1:2007. 2 Normative references The following referenced documents are indispensable for the application of this document. For dated
26、 references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 15182-1:2007, Hand-held branchpipes for fire service use Part 1: Common requirements 3 Terms and definitions For the purposes of this document, th
27、e terms and definitions given in EN 15182-1:2007 and the following apply. 3.1 high pressure branchpipe branchpipe including a shut-off device and !an adjustable pattern“ corresponding to the following definitions NOTE Branchpipe is defined in 3.1 of EN 15182-1:2007. 3.1.1 high pressure branchpipe ty
28、pe 1 high pressure branchpipe with !adjustable pattern“ at variable flow NOTE Changing pattern changes the flow. 3.1.2 high pressure branchpipe type 2 high pressure branchpipe with !adjustable pattern“ at constant flow NOTE Changing pattern does not change the flow. DIN EN 15182-4:2010-04 EN 15182-4
29、:2007+A1:2009 (E) 5 3.1.3 high pressure branchpipe type 3 high pressure branchpipe with !adjustable pattern“ at selectable, constant flow NOTE Changing pattern does not change the flow. 3.1.4 high pressure branchpipe type 4 (automatic branchpipe) high pressure branchpipe with constant pressure NOTE
30、Changing pattern does not change the flow. 3.1.4.1 high pressure branchpipe type 4.1 high pressure branchpipe with !adjustable pattern“ at constant pressure 3.1.4.2 high pressure branchpipe type 4.2 high pressure branchpipe with !adjustable pattern“ and selectable flow at constant pressure 3.2 jet 3
31、.2.1 narrow spray jet intermediate position between the straight jet and the wide spray jet providing throw as well as protection 3.2.2 wide spray jet jet solely providing protection for the operator(s) 3.3 haptical device single mechanical device engaging detents 4 Requirements 4.1 General The bran
32、chpipes, covered by this standard, shall comply with EN 15182-1. 4.2 Mechanical characteristics 4.2.1 Dimensions and mass The branchpipes (without inlet coupling) shall not exceed the dimensions and masses specified in Table 1. DIN EN 15182-4:2010-04 EN 15182-4:2007+A1:2009 (E) 6 Table 1 Dimensions
33、and mass Dimensions mm Mass kg 550 350 150 3,5 NOTE 1 The maximum mass does not apply to sea water-resistant branchpipes. NOTE 2 To avoid unsafe disconnection of the branchpipe from the hose during fire service use, the inlet of the branchpipe should be connected to the hose with an appropriate devi
34、ce. 4.2.2 Operating and handling elements 4.2.2.1 The torques needed to move the operating elements shall not exceed the values given in Table 2 at pressures up to the nominal pressure. Table 2 Torque Type of operating element Maximum torque Nm Lever 15Valve handle 15 Trigger 15Rotating operating el
35、ements 10 Rotating inlet elements for fixed couplings or screwed hose 5 4.2.2.2 For branchpipes that are opened and closed with a valve handle or a trigger, the “closed“ position shall be located in the direction of the flow. If a different operating element is used, the “closed“ position shall be c
36、learly identified. 4.2.3 Flow adjustment positions If a branchpipe has a device to select flow rate, the flow rates settings shall be easily identifiable by both visual and mechanical means (haptical device with corresponding numerical values). If using a rotating operating element for flow adjustme
37、nt, the adjustment shall be achieved by a rotation movement of maximum 180. 4.2.4 Jet adjustment positions The various jet positions shall be clearly marked. The narrow spray jet position (see 4.3.5) shall be easily identifiable by both visual and mechanical means (haptical devices). Jet adjustment
38、from a straight jet to a wide spray jet with a spray angle of at least 100 shall be achieved by a rotation movement between 70 and maximum 180. NOTE This requirement is included in the standard as a safety detail to provide the user with a means to produce a wide protective spray jet of at least 100
39、 achieved within a 180 rotation (one hand twist movement). DIN EN 15182-4:2010-04 EN 15182-4:2007+A1:2009 (E) 7 It shall be possible to open the branchpipe in a spray angle of at least 30. 4.3 Hydraulic characteristics 4.3.1 Pressures The following pressures shall be used for determining the hydraul
40、ic characteristics: reference pressure: pR= 6 bar ! 0,1 bar“; median pressure for type 4 branchpipes: pm; nominal pressure: pN= 40 bar; test pressure: pt= 60 bar; burst pressure: pB= 100 bar. 4.3.2 Flow rates All flow rates indicated on the branchpipe shall be measured at straight jet position and a
41、t the maximum spray angle position. Table 3 shall apply to the deviation in flow rates which can be set at the reference pressure pR. NOTE 1 The deviation should also apply when the shape of the stream is altered. Table 3 Deviation in the flow rate Flow rate Q l/min Deviation limit 0 to 100 0/+20 l/
42、min Above 100 0/+ 10 % (of set rate) NOTE 2 The manufacturer should, in addition to EN 15182-1:2007, item 8.1.2, provide information concerning optimal flow rate settings regarding hose size and hose length in an instruction handbook. 4.3.3 Effective throw The high pressure branchpipes shall achieve
43、, for each flow rate position, an effective throw effd as shown in Figure 1, when set to a straight jet at the reference pressure. DIN EN 15182-4:2010-04 EN 15182-4:2007+A1:2009 (E) 8 Key X Flow rate Q in l/min Y Effective throw effd in m Figure 1 Effective throw 4.3.4 Wide spray jet The wide spray
44、jet shall have a spray angle of at least 100 . 4.3.5 Narrow spray jet A narrow spray jet position between the straight jet and the wide spray jet positions shall be provided on the branchpipe. The narrow spray jet shall have a spray angle of at least 30 . 4.3.6 Type 4 branchpipes For type 4 branchpi
45、pes, the manufacturer shall give the regulation range (pressure at the beginning of the range and pressure at the end of the range), from which the median pressure is calculated. With the valve fully open, the flow should be set at both the minimum and maximum flow and the pressure for each shall be
46、 read. This pressure shall not deviate from the median pressure by more than 30 %. This information shall be provided in graphic format as shown in Annex C of EN 15182-1:2007. DIN EN 15182-4:2010-04 EN 15182-4:2007+A1:2009 (E) 9 4.4 Leak-tightness The closed branchpipe shall show no leakage during 1
47、 min at the test pressure pt= 60 bar. NOTE No leakage means no visible weeping or drop formation. The opened branchpipe shall show no leakage during 1 min at the nominal pressure pN = 40 bar. 4.5 Hydrostatic requirements The branchpipes shall fulfill the tests defined in 5.5. 5 Testing and proofs 5.
48、1 General Unless otherwise specified, tests shall be carried out at the reference pressure pR, after the tests specified in part 1 of this European Standard, in the following order. 5.2 Jet spray angle 5.2.1 Spray angle measurement Arrange the branchpipe on a fixed support in a horizontal position 1
49、,5 m above the ground, in a zone where the wind speed is lower than 2 m/s (see Figure 2). Arrange vertically a rule in the longitudinal axis of the extremity of the branchpipe at a distance of 1 m. This rule, with a height of 3 m, shall have three coloured zones symmetrically arranged on both sides of the longitudinal axis. The outside diameters of the zones are defined in the Table 4. Table 4 Outside diameter of the zones Colour of the zone Outside diameter m Angle Black (b) 0,54 100