1、December 2016 English price group 33No part of this translation may be reproduced without prior permission ofDIN Deutsches Institut fr Normung e. V., Berlin. Beuth Verlag GmbH, 10772 Berlin, Germany,has the exclusive right of sale for German Standards (DIN-Normen).ICS 13.220.50; 91.060.50!%g“2599168
2、www.din.deDIN EN 15269-5Extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardware Part 5: Fire resistance of hinged and pivoted metal framed glazed doorsets and openable windows;Englis
3、h version EN 152695:2014+A1:2016,English translation of DIN EN 15269-5:2016-12Erweiterter Anwendungsbereich von Prfergebnissen zur Feuerwiderstandsfhigkeit und/oder Rauchdichtigkeit von Tren, Toren und Fenstern einschlielich ihrer Baubeschlge Teil 5: Feuerwiderstandsfhigkeit von verglasten Drehflgel
4、tren und zu ffnenden Fenstern mit Metall(rohr)rahmen;Englische Fassung EN 152695:2014+A1:2016,Englische bersetzung von DIN EN 15269-5:2016-12Application tendue des rsultats dessais en matire de rsistance au feu et/ou dtanchit la fume des blocsportes, blocsfermetures et ouvrants de fentre, y compris
5、leurs lmentsde quincaillerie intgrs Partie 5: Rsistance au feu des blocsportes vitrs battants et pivotants, ossature mtallique,et des fentres vitres ossature mtallique;Version anglaise EN 152695:2014+A1:2016,Traduction anglaise de DIN EN 15269-5:2016-12SupersedesDIN EN 152695:201409www.beuth.deDocum
6、ent comprises 133 pagesDTranslation by DIN-Sprachendienst.In case of doubt, the German-language original shall be considered authoritative.12.16 DIN EN 15269-5:2016-12 2 A comma is used as the decimal marker. National foreword This document (EN 15269-5:2014+A1:2016) has been prepared by Technical Co
7、mmittee CEN/TC 127“Fire safety in buildings” (Secretariat: BSI, United Kingdom). The responsible German body involved in its preparation was DIN-Normenausschuss Bauwesen (DIN Standards Committee Building and Civil Engineering), Working Committee NA 005-52-05 AA Brandverhalten von Baustoffen und Baut
8、eilen Feuerschutz- und Rauchschutzabschlsse (SpA zu CEN/TC 127/WG 3 sowie Teilbereichen von CEN/TC 127/WG 2, CEN/TC 127/WG 7, CEN/TC 33 und ISO/TC 92/SC 2). This standard includes Amendment A1 approved by CEN on 2016-03-13. Amendments This standard differs from DIN EN 15269-5:2014-09 as follows: a)
9、in Table A.1, revisions have been made to construction parameters A.5.6, B.4.15 and B.4.16; b) revisions have been made to Figure A.15b, Figure A.25, Figure A.27, Figure A.30, Figure A.43a, Figure A.43b, Figure C.2, Figure C.3 and Figure C.5. Previous editions DIN EN 15269-5: 2014-09 EUROPEAN STANDA
10、RD NORME EUROPENNE EUROPISCHE NORM EN 15269-5:2014+A1 October 2016 ICS 13.220.50; 91.060.50 Supersedes EN 15269-5:2014English Version Extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building h
11、ardware - Part 5: Fire resistance of hinged and pivoted metal framed glazed doorsets and openable windows Application tendue des rsultats dessais en matire de rsistance au feu et/ou dtanchit la fume des blocs-portes, blocs-fermetures et ouvrants de fentre, y compris leurs lments de quincaillerie int
12、grs - Partie 5: Rsistance au feu des blocs-portes vitrs battants et pivotants, ossature mtallique, et des fentres vitres ossature mtallique Erweiterter Anwendungsbereich von Prfergebnissen zur Feuerwiderstandsfhigkeit und/oder Rauchdichtigkeit von Tren, Toren und Fenstern einschlielich ihrer Baubesc
13、hlge - Teil 5: Feuerwiderstandsfhigkeit von verglasten Drehflgeltren und zu ffnenden Fenstern mit Metall(rohr)rahmen This European Standard was approved by CEN on 17 April 2014 and includes Amendment 1 approved by CEN on 13 March 2016.CEN members are bound to comply with the CEN/CENELEC Internal Reg
14、ulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN mem
15、ber. This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same status as the official versions.
16、CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland
17、, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United Kingdom. EUROPEAN COMMITTEE FOR STANDARDIZATION COMIT EUROPEN DE NORMALISATION EUROPISCHES KOMITEE FR NORMUNG CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels 2016 CEN All rights of exploitation in
18、 any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 15269-5:2014+A1:2016 EContents Page European foreword . 3 Introduction 4 1 Scope 5 2 Normative references 5 3 Terms and definitions . 6 4 Determination of the field of extended application . 6 4.1 General 6 4.2 How t
19、o use extended application rules in Annex A. 6 4.3 Procedure for maximum field of extended application 7 4.4 Analysis of resistance to fire test results 8 5 Extended application report . 8 6 Classification report . 8 Annex A (normative) Construction parameter variations 9 Annex B (normative) Arrange
20、ments for doorsets incorporating side and / or over panels . 122 Annex C (normative) Relationship showing the relevant Parts of EN 15269 that which should be used depending upon the type of doorset 126 Bibliography . 131 EN 15269-5:2014+A1:2016 (E) DIN EN 15269-5:2016-12 2 European foreword This doc
21、ument (EN 15269-5:2014+A1:2016) has been prepared by Technical Committee CEN/TC 127 “Fire safety in buildings”, the secretariat of which is held by BSI. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the lates
22、t by April 2017, and conflicting national standards shall be withdrawn at the latest by April 2017. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN and/or CENELEC shall not be held responsible for identifying any or all such p
23、atent rights. This document includes Amendment 1 approved by CEN on 2016-03-13. This document supersedes EN 15269-5:2014. The start and finish of text introduced or altered by amendment is indicated in the text by tags !“. This document has been prepared under a mandate given to CEN by the European
24、Commission and the European Free Trade Association, and supports basic work requirements of Regulation (EU) 305/2011. According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bu
25、lgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland,
26、Turkey and the United Kingdom. EN 15269-5:2014+A1:2016 (E) DIN EN 15269-5:2016-12 3 Introduction This document is one of a series of standards listed below and intended to be used for the purpose of producing an extended application report based on the evaluation of one or more fire resistance and/o
27、r smoke control tests. These standards may also be used to identify the best selection of test specimens required to cover a wide range of product variations. EN 15269 ,Extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies incl
28、uding their elements of building hardware, currently consists of: Part 1: General requirements; Part 2: Fire resistance of hinged and pivoted steel doorsets; Part 3: Fire resistance of hinged and pivoted timber doorsets and openable timber framed windows; Part 4: Fire resistance of hinged and pivote
29、d glass doorsets (in preparation); Part 5: Fire resistance of hinged and pivoted metal framed glazed doorsets and openable windows; Part 6: Fire resistance of sliding timber doorsets; Part 7: Fire resistance of sliding steel doorsets; Part 8: Fire resistance of horizontally folding timber doorsets (
30、in preparation); Part 9: Fire resistance of horizontally folding steel doorsets (in preparation); Part 10: Fire resistance of steel rolling shutter assemblies; Part 11: Fire resistance of operable fabric curtains; Part 20: Smoke control for hinged and pivoted steel, timber and metal framed glazed do
31、orsets. EN 15269-5:2014+A1:2016 (E) DIN EN 15269-5:2016-12 4 1 Scope This European Standard covers hinged and pivoted steel (any kind) and aluminium based framed, glazed doorsets or openable windows. This European Standard prescribes the methodology for extending the application of test results obta
32、ined from resistance to fire test(s) conducted in accordance with EN 1634-1. Subject to the completion of the appropriate test or tests selected from those identified in Clause 4 the extended application may cover all or some of the following examples: integrity (E), integrity/radiation (EW) or inte
33、grity/insulation (EI1or EI2) classifications; doorsets and openable windows; door / window leaf (leaves); glazing and non-glazed panels in doorset and openable window; items of building hardware; decorative finishes; intumescent, smoke, draught or acoustic seals; alternative supporting construction(
34、s). 2 Normative references The following documents, in whole or in part, are normatively referenced in this document and are indispensable for its application. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any a
35、mendments) applies. EN 1363-1, Fire resistance tests Part 1: General Requirements EN 1634-1, Fire resistance and smoke control tests for door and shutter assemblies, openable windows and elements of building hardware Part 1: Fire resistance test for door and shutter assemblies and openable windows E
36、N 1634-2, Fire resistance and smoke control tests for door, shutter and openable window assemblies and elements of building hardware Part 2: Fire resistance characterisation test for elements of building hardware EN 13501-2:2007+A1:2009, Fire classification of construction products and building elem
37、ents Part 2: Classification using data from fire resistance tests, excluding ventilation services EN 15269-1, Extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardware Part 1: General
38、requirements EN ISO 13943, Fire safety Vocabulary (ISO 13943) EN 15269-5:2014+A1:2016 (E) DIN EN 15269-5:2016-12 5 3 Terms and definitions For the purposes of this document, the terms and definitions given in EN 1363-1, EN ISO 13943, EN 1634-1, EN 1634-2 and EN 15269-1 together with the following ap
39、ply. 3.1 full scale test test of a full scale doorset in accordance with EN 1634-1 3.2 small scale test test on elements of building hardware in accordance with EN 1634-2 and where the decision process given in EN 1634-2 permits its use 3.3 effective rebate depth-2 dimension of the door leaf thickne
40、ss of overlapping adjacent edges of door leaf relative to the door frame, transom or side panel or flush overpanel Note 1 to entry: At the meeting edges and for rebated leaves the dimension is the depth of the largest rebate. See Figure 1. Note 2 to entry: The effective rebate depth-2 is different f
41、rom the effective rebate depth definition given on other standards of the series EN 15269. 3.4 opening outwards means opening the doorleaf away from the fireside 4 Determination of the field of extended application 4.1 General 4.1.1 Before there can be any consideration for extended application the
42、doorset shall have been tested and classified in accordance with EN 1634-1 and EN 13501-2 respectively in order to establish a classification for the doorset. 4.1.2 A review of the construction parameters can indicate that one or more characteristics may be improved by a particular parameter variati
43、on. All evaluations shall be made on the basis of retaining the classifications obtainable from testing to EN 1634-1, including those lower than the test duration. However, this shall never lead to an increased classification for any specific parameter beyond that achieved by one resistance to fire
44、test unless specifically identified in the relevant Construction Parameter Variation tables. 4.1.3 If, by following the ensuing procedure, any part of the classification cannot be achieved by extended application rules that part of classification shall be omitted from the subsequent extended applica
45、tion report and classification report. 4.2 How to use extended application rules in Annex A 4.2.1 Identify the variations from the original resistance to fire test specimen(s) which are required to be covered by an extended application report. EN 15269-5:2014+A1:2016 (E) DIN EN 15269-5:2016-12 6 4.2
46、.2 Locate the variations in the appropriate parameter variation by reference to columns (1) and (2) of Table A.1. 4.2.3 Review the type of classification to be retained from column (3) and establish from the contents of column (4) whether any extended application is available beyond the direct appli
47、cation rules in EN 1634-1 without the need for further testing. 4.2.4 Where this is deemed to be possible this can be recorded in the extended application report together with any appropriate restrictions and the stated rules from column (4) of Table A.1. 4.2.5 Where the variations required can only be achieved from additional testing, the additional resistance to fire test can be made on a similar specimen type i.e. a doorset of the same or more onerous configuration where the leaf construction is fundamentally the same as tested. Alternatively, column (5) identifie
copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有
备案/许可证编号:苏ICP备17064731号-1