1、April 2010 Translation by DIN-Sprachendienst.English price group 26No part of this translation may be reproduced without prior permission ofDIN Deutsches Institut fr Normung e. V., Berlin. Beuth Verlag GmbH, 10772 Berlin, Germany,has the exclusive right of sale for German Standards (DIN-Normen).ICS
2、13.220.50; 91.060.50!$aZc“1625564www.din.deDDIN EN 15269-7Extended application of test results for fire resistance and/or smokecontrol for door, shutter and openable window assemblies, includingtheir elements of building hardware Part 7: Fire resistance for steel sliding doorsetsEnglish translation
3、of DIN EN 15269-7:2010-04Erweiterter Anwendungsbereich von Prfergebnissen zur Feuerwiderstandsfhigkeitund/oder Rauchdichtigkeit von Tren, Toren und Fenstern einschlielich ihrerBaubeschlge Teil 7: Feuerwiderstandsfhigkeit von Schiebetoren aus StahlEnglische bersetzung von DIN EN 15269-7:2010-04Applic
4、ation largie des rsultats dessai en matire de rsistance au feu et dtanchit la fume des blocs-portes, blocs-fermetures et ouvrants de fentres, y compris leslments intgrs de quincaillerie de btiment Partie 7: Rsistance au feu des blocs-portes coulissants en acierTraduction anglaise de DIN EN 15269-7:2
5、010-04www.beuth.deDocument comprises pagesIn case of doubt, the German-language original shall be considered authoritative.8104.10 DIN EN 15269-7:2010-04 A comma is used as the decimal marker. National foreword This standard has been prepared by Technical Committee CEN/TC 127 “Fire safety in buildin
6、gs” (Secretariat: BSI, United Kingdom). The responsible German body involved in its preparation was the Normenausschuss Bauwesen (Building and Civil Engineering Standards Committee), Working Committee NA 005-52-05 AA Brandverhalten von Baustoffen und Bauteilen Feuerschutz- und Rauchschutzabschlsse.
7、2 EUROPEAN STANDARD NORME EUROPENNE EUROPISCHE NORM EN 15269-7 November 2009 ICS 13.220.50; 91.060.50 English Version Extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardware - Part 7
8、: Fire resistance for steel sliding doorsets Application largie des rsultats dessai en matire de rsistance au feu et dtanchit la fume des blocs-portes, blocs-fermetures et ouvrants de fentres, y compris les lments intgrs de quincaillerie de btiment - Partie 7:Rsistance au feu des blocs-portes coulis
9、sants en acierErweiterter Anwendungsbereich von Prfergebnissen zur Feuerwiderstandsfhigkeit und/oder Rauchdichtigkeit von Tren, Toren und Fenstern einschlielich ihrer Baubeschlge - Teil 7: Feuerwiderstandsfhigkeit von Schiebetoren aus Stahl This European Standard was approved by CEN on 22 September
10、2009. CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtaine
11、d on application to the CEN Management Centre or to any CEN member. This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN Managemen
12、t Centre has the same status as the official versions. CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
13、 Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom. EUROPEAN COMMITTEE FOR STANDARDIZATION COMIT EUROPEN DE NORMALISATION EUROPISCHES KOMITEE FR NORMUNG Management Centre: Avenue Marnix 17, B-1000 Brussels 2009 CEN All rights of exploitation in any form and
14、 by any means reserved worldwide for CEN national Members. Ref. No. EN 15269-7:2009: EContents Page Foreword . 3Introduction . 41 Scope 52 Normative references 53 Terms and definitions . 64 Determination of the field of extended application 74.1 General . 74.2 Procedure for evaluation 74.3 Procedure
15、 for maximum field of extended application . 84.4 Interpretation of test results . 85 Extended application report . 86 Classification report 9Annex A (normative) Construction parameter variations 10Figures relating to Annex A . 64EN 15269-7:2009 (E) DIN EN 15269-7:2010-04 2Foreword This document (EN
16、 15269-7:2009) has been prepared by Technical Committee CEN/TC 127 “Fire safety in buildings”, the secretariat of which is held by BSI. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by May 2010, an
17、d conflicting national standards shall be withdrawn at the latest by May 2010. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN and/or CENELEC shall not be held responsible for identifying any or all such patent rights. This do
18、cument has been prepared under a mandate given to CEN by the European Commission and the European Free Trade Association, and supports essential requirements of EU Directive(s). According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bou
19、nd to implement this European Standard: Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, S
20、witzerland and the United Kingdom. EN 15269-7:2009 (E) DIN EN 15269-7:2010-04 3Introduction This European Standard is one of a series of standards listed below and intended to be used for the purpose of producing an extended application report based on the evaluation of one or more fire resistance a
21、nd/or smoke control tests. These standards may also be used to identify the best selection of test specimens required to cover a wide range of product variations. The EN 15269 series currently consists of: prEN 15269, Extended application of test results for fire resistance and/or smoke control for
22、door, shutter and openable window assemblies, including their elements of building hardware Part 1: General requirements Part 2: Fire resistance of hinged and pivoted steel doorsets Part 3: Fire resistance of hinged and pivoted timber doorsets and openable timber framed windows Part 5: Fire resistan
23、ce of hinged and pivoted metal framed glazed doorsets and openable windows Part 6: Fire resistance of sliding timber doorsets Part 10: Fire resistance of steel rolling shutters Part 11: Fire resistance of operable fabric curtains as well as EN 15269, Extended application of test results for fire res
24、istance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardware Part 7: Fire resistance for steel sliding doorsets Part 20: Smoke control for hinged and pivoted steel, timber and metal framed glazed doorsets Before there can be any conside
25、ration for extended application the doorset should have been tested in accordance with EN 1634-1 to achieve a test result which could generate a classification in accordance with EN 13501-2 at least equal to the classification subsequently required from extended application considerations. A review
26、of the doorset construction parameters can indicate that one or more characteristics may be improved by a particular parameter variation. All evaluations should be made on the basis of retaining the fire resistance classifications obtainable from testing to EN 1634-1, including those lower than the
27、test duration. However, this should never lead to an increased classification for any specific fire or smoke performance parameter beyond that achieved during any one test unless specifically identified in the relevant Construction Parameter Variation tables within this series of standards. The effe
28、ct on the durability of self closing of the doorsets following an extended application process is not addressed in this series of standards. EN 15269-7:2009 (E) DIN EN 15269-7:2010-04 41 Scope This European Standard, which should be read in conjunction with prEN 15269-1, covers the following types o
29、f steel based doorsets: horizontally sliding doorsets (single and double), telescopic doorsets (single and double) and single vertically sliding doorsets. This document prescribes the methodology for extending the application of test results obtained from test(s) conducted in accordance with EN 1634
30、-1. Subject to the completion of the appropriate test or tests selected from those identified in Clause 4 the extended application may cover all or some of the following non-exhaustive list: integrity only (E), radiation (EW) or insulated (EI1or EI2) classifications; door leaf; wall/ceiling fixed el
31、ements (frame/suspension system); glazing for door leaf; items of building hardware; decorative finishes; intumescent, smoke, draught or acoustic seals; alternative supporting construction(s). 2 Normative references The following referenced documents are indispensable for the application of this doc
32、ument. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 1363-1:1999, Fire resistance tests Part 1: General requirements EN 1634-1:2008, Fire resistance and smoke control tests for door,
33、shutter and openable window assemblies and elements of building hardware Part 1: Fire resistance tests for doors, shutters and openable windows EN 1634-2:2008, Fire resistance and smoke control tests for door, shutter and openable window assemblies and elements of building hardware Part 2: Fire resi
34、stance characterisation test for elements of building hardware EN 13501-2:2007, Fire classification of construction products and building elements Part 2: Classification using data from fire resistance tests, excluding ventilation services EN 15254-4:2008, Extended application of results from fire r
35、esistance tests Non-loadbearing walls Part 4: Glazed constructions prEN 15269-1:2007, Extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardware Part 1: General requirements EN 15269-7:
36、2009 (E) DIN EN 15269-7:2010-04 5prEN 15269-2, Extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardware Part 2: Fire resistance of hinged and pivoted steel doorsets EN ISO 13943:2000,
37、 Fire safety Vocabulary (ISO 13943:2000) 3 Terms and definitions For the purposes of this document, the terms and definitions given in EN 1363-1:1999, EN ISO 13943:2000, EN 1634-1:2008, EN 1634-2:2008 and prEN 15269-1:2007 together with the following apply. 3.1 full scale test test of a full size do
38、orset in accordance with EN 1634-1 3.2 leaf/element/panel different parts of a doorset as indicated in Figures 1 and 2 below 123Key 1 panel 2 leaf 3 element Figure 1 Double leaf telescopic door EN 15269-7:2009 (E) DIN EN 15269-7:2010-04 621Key 1 panel 2 leaf Figure 2 Double leaf sliding door 4 Deter
39、mination of the field of extended application 4.1 General 4.1.1 Before there can be any consideration for extended application the doorset shall have been tested and classified in accordance with EN 1634-1 and EN 13501-2 respectively in order to establish a classification for the doorset. 4.1.2 A re
40、view of the doorset construction parameters can indicate that one or more characteristics may be improved by a particular parameter variation. All evaluations shall be made on the basis of retaining the classifications obtainable from testing to EN 1634-1, including those lower than the test duratio
41、n. However, this shall never lead to an increased classification for any specific parameter beyond that achieved during any one test unless specifically identified in the relevant Construction Parameter Variation tables. 4.1.3 All evaluations shall be made on the basis of retaining the classificatio
42、n obtained from testing to EN 1634-1. 4.1.4 If, by following the ensuing procedure, any part of the classification cannot be achieved by extended application rules that part of classification shall be omitted from the subsequent extended application report and classification report. 4.2 Procedure fo
43、r evaluation 4.2.1 Identify the variations from the original test specimen(s) which are required to be covered by an extended application report. 4.2.2 Locate the variations in the appropriate parameter variation by reference to columns (1) and (2) of Table A.1. 4.2.3 Review the type of classificati
44、on to be retained from column (3) of Table A.1 and establish from the contents of column (4) of Table A.1 whether any extended application is available without the need for further testing. 4.2.4 Where this is deemed to be possible this can be recorded in the extended application report together wit
45、h any appropriate restrictions and the stated rules from column (4) in Table A.1. 4.2.5 Where the variations required can only be achieved from additional testing according to column (5) in Table A.1, the additional test can be made on a similar specimen type to the original test EN 15269-7:2009 (E)
46、 DIN EN 15269-7:2010-04 7against which the extended application is sought. Alternatively, column (5) in Table A.1 identifies an option for alternative testing and relevant test parameters. 4.3 Procedure for maximum field of extended application 4.3.1 It is possible to provide a limited field of exte
47、nded application from the results of a single test. However, where a manufacturer intends to produce a range of doors incorporating single doors and also double doors, with or without glazing, with alternative elements of building hardware, etc., it is recommended that careful consideration is given
48、 to the complete range of doorset designs and options in order to minimise the testing required before testing commences. 4.3.2 Establish all the parameter variations which are required to be part of the product range. 4.3.3 Select specimen(s) for the first test(s) in the series to ensure that the m
49、ost important parameter variations for the manufactured products are covered. 4.3.4 Complete the first test or a series of tests and prepare a field of direct application and possibly a classification report from the results of the test(s). 4.3.5 Establish which of the original desired parameter variations have not been covered by the direct application and classification report. 4.3.6 Identify these parameter variations in Annex A and establi