1、June 2010 Translation by DIN-Sprachendienst.English price group 24No part of this translation may be reproduced without prior permission ofDIN Deutsches Institut fr Normung e. V., Berlin. Beuth Verlag GmbH, 10772 Berlin, Germany,has the exclusive right of sale for German Standards (DIN-Normen).ICS 1
2、3.220.20!$i+“1700899www.din.deDDIN EN 54-23Fire detection and fire alarm systems Part 23: Fire alarm devices Visual alarm devicesEnglish translation of DIN EN 54-23:2010-06Brandmeldeanlagen Teil 23: Feueralarmeinrichtungen Optische SignalgeberEnglische bersetzung von DIN EN 54-23:2010-06Systmes dala
3、rme feu et de dtection dincendie Partie 23: Dispositifs dalarme feu Alarmes visuellesTraduction anglaise de DIN EN 54-23:2010-06See start of validitywww.beuth.deDocument comprises pagesIn case of doubt, the German-language original shall be considered authoritative.6806.10 DIN EN 54-23:2010-06 A com
4、ma is used as the decimal marker. Start of validity This standard is due to take effect on 1 December 2010. It should be noted that, in Germany, CE conformity marking of construction products will be permitted once this standard has been listed in the Bundesanzeiger (German Federal Law Gazette) and
5、from the date given therein. National foreword This standard has been prepared by Technical Committee CEN/TC 72 “Fire detection and fire alarm systems” (Secretariat: BSI, United Kingdom). The responsible German body involved in its preparation was the Normenausschuss Feuerwehrwesen (Firefighting and
6、 Fire Protection Standards Committee), Working Committee NA 031-02-01 AA Brandmelde- und Feueralarmanlagen. This standard specifies requirements for visual alarm devices for use in fire detection and alarm systems permanently installed in buildings or intended for outdoor applications (referred to i
7、n German as “BMS” and “BMA” equipment, respectively). The system requirements and technical application rules for fire detection and fire alarm systems complying with this standard are specified in national Standards DIN 14675 and DIN VDE 0833-2 (VDE 0833-2). Certification of conformity of such prod
8、ucts with the requirements specified in this standard is based on conformity evaluation of the products carried out by “Notified Bodies” in accordance with the EU Construction Products Directive (see clause 6 and Annex ZA of this standard) and the relevant provisions of the Bauproduktengesetz (BauPG
9、) (Construction Products Act). National Annex NA (informative) Bibliography DIN 14675, Fire alarm systems Design and operation DIN VDE 0833-2 (VDE 0833-2), Alarm systems for fire, intrusion and hold up Part 2: Requirements for fire alarm systems 89/106/EEC, Council Directive of 21 December 1988 on t
10、he approximation of the laws of the Member States relating to construction products Bauproduktengesetz BauPG, Gesetz ber das Inverkehrbringen von und den freien Warenverkehr mit Bauprodukten zur Umsetzung der Richtlinie 89/106/EWG des Rates vom 21. Dezember 1988 zur Angleichung der Rechts- und Verwa
11、ltungsvorschriften der Mitgliedsstaaten ber Bauprodukte und andere Rechtsakte der Europischen Gemeinschaften (Construction Products Act German Law implementing Council Directive 89/106/EEC of 21 December on the approximation of laws, regulations and administrative provisions of the Member States rel
12、ating to construction products) 2 EUROPEAN STANDARD NORME EUROPENNE EUROPISCHE NORM EN 54-23 March 2010 ICS 13.220.20 English Version Fire detection and fire alarm systems - Part 23: Fire alarm devices - Visual alarm devices Systmes dalarme feu et de dtection dincendie - Partie 23: Dispositifs dalar
13、me feu - Alarmes visuelles Brandmeldeanlagen - Teil 23: Feueralarmeinrichtungen - Optische Signalgeber This European Standard was approved by CEN on 23 January 2010. CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Stan
14、dard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN Management Centre or to any CEN member. This European Standard exists in three official versions (English, Frenc
15、h, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as the official versions. CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia,
16、 Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom. EUROPEAN COMMITTEE FOR STANDARDIZATI
17、ON COMIT EUROPEN DE NORMALISATION EUROPISCHES KOMITEE FR NORMUNG Management Centre: Avenue Marnix 17, B-1000 Brussels 2010 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 54-23:2010: EEN 54-23:2010 (E) 2 Contents Page Foreword 5Int
18、roduction .71 Scope 82 Normative references 83 Terms, definitions and abbreviations 93.1 Definitions 93.2 Abbreviations 104 Requirements 104.1 General . 104.2 Operational reliability . 104.2.1 Duration of operation . 104.2.2 Provision for external conductors 104.2.3 Flammability of materials . 114.2
19、.4 Enclosure protection 114.2.5 Access . 114.2.6 Manufacturers adjustments 114.2.7 On site adjustments of behaviour . 114.2.8 Requirements for software controlled devices . 114.3 Performance parameters under fire conditions 134.3.1 Coverage volume 134.3.2 Variation of light output . 134.3.3 Minimum
20、and maximum effective luminous intensity 134.3.4 Light colour . 134.3.5 Light temporal pattern and frequency of flashing . 144.3.6 Marking and data 144.3.7 Synchronization (option with requirements) . 154.4 Durability . 164.4.1 Temperature resistance . 164.4.2 Humidity resistance 164.4.3 Shock and v
21、ibration resistance . 164.4.4 Corrosion resistance Sulphur dioxide (SO2) corrosion (endurance) . 164.4.5 Electrical stability EMC, immunity (operational) 175 Tests and evaluation methods 175.1 General . 175.1.1 Atmospheric conditions for tests . 175.1.2 Operating conditions for tests 175.1.3 Mountin
22、g arrangements . 175.1.4 Tolerances . 185.1.5 Provision for tests 185.1.6 Test schedule 185.1.7 Reproducibility 205.2 Operational reliability . 205.2.1 Duration of operation . 205.2.2 Provision for external conductors 215.2.3 Flammability of materials . 215.2.4 Enclosure protection 215.2.5 Access .
23、225.2.6 Manufacturers adjustments 235.2.7 On site adjustments of behaviour . 23DIN EN 54-23:2010-06 EN 54-23:2010 (E) 3 5.2.8 Requirements for software controlled devices 235.3 Performance parameters under fire conditions . 235.3.1 Coverage volume . 235.3.2 Variation of luminous intensity 235.3.3 Mi
24、nimum and maximum light intensity . 245.3.4 Light colour 245.3.5 Light pattern and frequency of flashing 245.3.6 Marking and data . 245.3.7 Synchronization (option with requirements) 245.4 Durability 265.4.1 Temperature resistance 265.4.2 Humidity resistance 295.4.3 Shock and vibration resistance .
25、335.4.4 Corrosion resistance Sulphur dioxide (SO2) corrosion (endurance) 375.4.5 Electrical stability Electromagnetic compatibility (EMC), immunity . 386 Evaluation of conformity 396.1 General . 396.2 Initial type testing 406.2.1 General . 406.2.2 Test samples 406.2.3 Test reports 406.3 Factory prod
26、uction control. 416.3.1 General . 416.3.2 General requirements . 416.3.3 Product specific requirements . 426.3.4 Initial inspection of factory and FPC . 436.3.5 Surveillance of FPC . 436.4 Procedure for modifications. 446.5 One-off products, pre-production products (e.g. prototypes) and products pro
27、duced in very low quantities 44Annex A (normative) Method for measuring the light distribution from a VAD . 46A.1 General . 46A.2 Test apparatus . 46A.3 Instrumentation . 46A.4 Test room . 46A.5 Arrangement for measuring the effective luminous intensity 48A.6 Calculation of Ieff(av). 52A.7 Calculati
28、on of coverage distance 52Annex B (normative) Comparative light output level measurement for VADs . 53B.1 General . 53B.2 Light test chamber 53B.3 Calibration of the light test chamber . 53B.4 Mounting arrangements 54B.5 Measurement of effective average illumination . 54Annex C (informative) Constru
29、ction of the light test chamber and associated equipment for comparative measurements . 55C.1 Light test chamber 55C.2 Surface finishes . 55Annex D (informative) Comparison of flammability test requirements in various standards 57D.1 Introduction 57D.2 Relevant standards . 57D.3 Vertical burning tes
30、ts 57D.4 Horizontal burning tests . 58D.4.1 IEC 60695-11-10 and UL 94 . 58D.4.2 IEC 60695-11-20 and UL 94 . 59DIN EN 54-23:2010-06 EN 54-23:2010 (E) 4 Annex ZA (informative) Clauses of this European Standard addressing the provisions of the EU Construction Products Directive (89/106/EEC) 60ZA.1 Scop
31、e and relevant characteristics 60ZA.2 Procedures for the attestation of conformity of VADs . 62ZA.2.1 System of attestation of conformity . 62ZA.2.2 EC Certificate of conformity 63ZA.3 CE marking and labelling . 63Bibliography . 66DIN EN 54-23:2010-06 EN 54-23:2010 (E) 5 Foreword This document (EN 5
32、4-23:2010) has been prepared by Technical Committee CEN/TC 72 “Fire detection and fire alarm systems”, the secretariat of which is held by BSI. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by Sept
33、ember 2010, and conflicting national standards shall be withdrawn at the latest by March 2013. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN and/or CENELEC shall not be held responsible for identifying any or all such patent
34、 rights. This document has been prepared under a mandate given to CEN by the European Commission and the European Free Trade Association, and supports essential requirements of EU Directive(s). For relationship with EU Directive(s), see informative Annex ZA, which is an integral part of this documen
35、t. EN 54, Fire detection and fire alarm systems, consists of the following parts: Part 1: Introduction Part 2: Control and indicating equipment Part 3: Fire alarm devices Sounders Part 4: Power supply equipment Part 5: Heat detectors Point detectors Part 7: Smoke detectors Point detectors using scat
36、tered light, transmitted light or ionization Part 10: Flame detectors Point detectors Part 11: Manual call points Part 12: Smoke detectors Line detectors using an optical light beam Part 13: Compatibility assessment of system components Part 14: Guidelines for planning, design, installation, commiss
37、ioning, use and maintenance (in preparation) Part 16: Voice alarm control and indicating equipment Part 17: Short-circuit isolators Part 18: Input/output devices Part 20: Aspirating smoke detectors Part 21: Alarm transmission and fault warning routing equipment Part 22: Resettable line-type heat det
38、ectors (in preparation) DIN EN 54-23:2010-06 EN 54-23:2010 (E) 6 Part 23: Fire alarm devices VADs Part 24: Components of voice alarm systems Loudspeakers Part 25: Components using radio links Part 26: Point fire detectors Carbon monoxide fire detectors (in preparation) Part 27: Duct smoke detectors
39、(in preparation) Part 28: Non-resettable (digital) line-type heat detectors (in preparation) Part 29: Multi-sensor fire detectors Point detectors using a combination of smoke and heat sensors (in preparation) Part 30: Multi-sensor fire detectors Point detectors using a combination of carbon monoxide
40、 and heat sensors (in preparation) According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany
41、, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom. DIN EN 54-23:2010-06 EN 54-23:2010 (E) 7 Introduction The purpose of a visual fire alarm device (VA
42、D) is to warn person(s) within, or in the vicinity of, a building of the occurrence of a fire emergency in order to enable such person(s) to take appropriate measures. This European Standard allows manufacturers to specify VADs in terms of the range at which the required illumination is met. Three c
43、ategories of device are defined, one for ceiling mounted devices, one for wall mounted devices and an open category. The maximum range of the VAD is tested by measuring the light output in a hemisphere surrounding it to determine its light distribution. As the light output of some VADs can change ov
44、er time due, for example, to the effect of self-heating, a test has been introduced to check that the variation of light output over time is within an acceptable limit. This European Standard gives common requirements for the construction and robustness of VADs as well as for their performance under
45、 climatic, mechanical and electrical interference conditions which are likely to occur in the service environment. VADs are classified in one of two application environment types, i.e. Type A and Type B. More severe climatic conditions are applied to devices that are primarily intended for outdoor a
46、pplications (Type B) than those primarily intended for indoor applications (Type A). DIN EN 54-23:2010-06 EN 54-23:2010 (E) 8 1 Scope This European Standard specifies the requirements, test methods and performance criteria for visual alarm devices in a fixed installation intended to signal a visual
47、warning of a fire between the fire detection and fire alarm system and the occupants of a building (see item C of Figure 1 of EN 54-1:1996). It is intended to cover only those devices which derive their operating power by means of a physical electrical connection to an external source such as a fire
48、 alarm system. This European Standard specifies the evaluation of conformity and the marking of the visual alarm devices. This European Standard applies to visual alarm devices that rely on software for their operation and to those that do not. This European Standard applies only to pulsing or flashing visual alarm devices, for example xenon beacons or rotating beacons. Devices giving continuous light output are excluded from this European Standard. This European Standard is not intended to cover visual indicators, for example those on detectors or on th