1、April 2013 Translation by DIN-Sprachendienst.English price group 7No part of this translation may be reproduced without prior permission ofDIN Deutsches Institut fr Normung e. V., Berlin. Beuth Verlag GmbH, 10772 Berlin, Germany,has the exclusive right of sale for German Standards (DIN-Normen).ICS 2
2、3.080!*“7615956www.din.deDDIN EN 16297-3Pumps Rotodynamic pumps - Glandless circulators Part 3: Energy efficiency index (EEI) for circulators integrated inproducts;English version EN 16297-3:2012,English translation of DIN EN 16297-3:2013-04Pumpen Kreiselpumpen - Umwlzpumpen in Nassluferbauart Teil
3、3: Berechnung des Energieeffizienzindexes (EEI) von in Produkte integriertenUmwlzpumpen;Englische Fassung EN 16297-3:2012,Englische bersetzung von DIN EN 16297-3:2013-04Pompes Pompes rotodynamiques - Circulateurs sans presse-toupe Partie 3: Calcul de lindice defficacit nergtique (EEI) pour les circu
4、lateurs intgrsdans des produits;Version anglaise EN 16297-3:2012,Traduction anglaise de DIN EN 16297-3:2013-04www.beuth.deDocument comprises 10 pagesIn case of doubt, the German-language original shall be considered authoritative.04.13DIN EN 16297-3:2013-04 2 A comma is used as the decimal marker. N
5、ational foreword This document (EN 16297-3:2012) has been prepared by Technical Committee CEN/TC 197 “Pumps” (Secretariat: AFNOR, France). The responsible German body involved in its preparation was the Normenausschuss Maschinenbau (Mechanical Engineering Standards Committee), Working Committee NA 0
6、60-11-01 AA Kreiselpumpen of Section Kreiselpumpen. Representatives of manufacturers and users of glandless circulators, and of the employers liability insurance associations contributed to this standard. This standard contains specifications meeting the essential requirements set out in Annex I of
7、the “Machinery Directive”, Directive 2006/42/EC in conjunction with Directive 2009/125/EC and Commission Regulation (EC) No 641/2009, and which apply to machines that are either first placed on the market or commissioned within the EEA. This standard serves to facilitate proof of compliance with the
8、 essential requirements of these directives. Once this standard is cited in the Official Journal of the European Union, it is deemed a “harmonized” standard and thus, a manufacturer applying this standard may assume compliance with the requirements of the Machinery Directive (“presumption of conform
9、ity”). The European Standards referred to in Clause 2 and in the Bibliography of the EN have been published as the corresponding DIN EN or DIN EN ISO Standards with the same number. For the International Standards which have not been published as DIN ISO Standards with the same number, there are no
10、national standards available. EUROPEAN STANDARD NORME EUROPENNE EUROPISCHE NORM EN 16297-3 October 2012 ICS 23.080 English Version Pumps - Rotodynamic pumps - Glandless circulators - Part 3: Energy efficiency index (EEI) for circulators integrated in products Pompes - Pompes rotodynamiques - Circula
11、teurs sans presse-toupe - Partie 3: Calcul de lindice defficacit nergtique (EEI) pour les circulateurs intgrs dans des produits Pumpen - Kreiselpumpen - Umwlzpumpen in Nassluferbauart - Teil 3: Berechnung des Energieeffizienzindexes (EEI) von in Produkte integrierten Umwlzpumpen This European Standa
12、rd was approved by CEN on 18 August 2012. CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning su
13、ch national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN member. This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its ow
14、n language and notified to the CEN-CENELEC Management Centre has the same status as the official versions. CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany,
15、Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United Kingdom. EUROPEAN COMMITTEE FOR STANDARDIZATION COMIT EUROPEN DE NORMALISATION EUROPISCHES KOMITEE FR NORM
16、UNG Management Centre: Avenue Marnix 17, B-1000 Brussels 2012 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 16297-3:2012: EEN 16297-3:2012 (E) 2 Contents Page Foreword 3Introduction .41 Scope 52 Normative references 53 Terms and
17、definitions .54 Symbols and units .65 Performance requirements and safety requirements 66 Calculation of energy efficiency index (EEI) .66.1 General conditions 66.2 Procedure .66.2.1 Load profile for calculation of average compensated power input, PLavg66.2.2 Part load points of circulators integrat
18、ed in products .66.2.3 Test conditions 76.2.4 Calculation of average compensated power input, PL,avg.76.2.5 Calculation of energy efficiency index (EEI), EEI.7Annex ZA (informative) Relationship between this European Standard and the requirements of Commission Regulation (EC) No 641/2009 .8DIN EN 16
19、297-3:2013-04 EN 16297-3:2012 (E) 3 Foreword This document (EN 16297-3:2012) has been prepared by Technical Committee CEN/TC 197 “Pumps”, the secretariat of which is held by AFNOR. This European Standard shall be given the status of a national standard, either by publication of an identical text or
20、by endorsement, at the latest by April 2013, and conflicting national standards shall be withdrawn at the latest by April 2013. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN and/or CENELEC shall not be held responsible for i
21、dentifying any or all such patent rights. This document has been prepared under a mandate given to CEN by the European Commission and the European Free Trade Association, and supports essential requirements of EU Directive(s). For relationship with EU Directive(s), see informative Annex ZA, which is
22、 an integral part of this document. EN 16297 consists of the following parts under the general title Pumps Rotodynamic pumps Glandless circulators: Part 1: General requirements and procedures for testing and calculation of energy efficiency index (EEI); Part 2: Calculation of energy efficiency index
23、 (EEI) for standalone circulators; Part 3: Energy efficiency index (EEI) for circulators integrated in products. According to the CEN/CENELEC Internal Regulations, the national standards organisations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgari
24、a, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turke
25、y and the United Kingdom. DIN EN 16297-3:2013-04 EN 16297-3:2012 (E) 4 Introduction This European Standard has been prepared under mandate M/469 EN of 22 June 2010 given to CEN by the European Commission and the European Free Trade Association to provide a means of conforming to Requirements of the
26、EU Directive 2005/32/EC of 6 July 2005 and Commission Regulation (EC) 641/2009 of 22 July 2009 by describing procedures for measurement and calculation of hydraulic power, power consumption, and energy efficiency index of DIN EN 16297-3:2013-04 EN 16297-3:2012 (E) 5 1 Scope This European Standard sp
27、ecifies the procedure for calculating the energy efficiency index (EEI) of circulators integrated in products. 2 Normative references The following documents, in whole or in part, are normatively referenced in this document and are indispensable for its application. For dated references, only the ed
28、ition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 809:1998+A1:2009, Pumps and pump units for liquids Common safety requirements EN 16297-1:2012, Pumps Rotodynamic pumps Glandless circulators Part 1: General requirements
29、and procedures for testing and calculation of energy efficiency index (EEI) EN 60335-2-51:2003, Household and similar electrical appliances Safety Part 2-51: Particular requirements for stationary circulation pumps for heating and service water installations 3 Terms and definitions For the purpose o
30、f this document, the terms and definitions given in EN 16297-1:2012 and the following apply. 3.1 circulators integrated in products circulator designed to operate dependently of a product that generates and/or transfers heat Note 1 to entry For the purpose of this document, the term circulator is us
31、ed in the following in place of circulators integrated in products 3.2 specific speed of a circulator dimensionless quantity used to classify pump impellers as to their type and proportions Note 1 to entry Specific speed of a circulator is calculated by: 0,7560sQnnH= where: ns is specific speed of a
32、 circulatorn is rotational speed in r.p.m. in this instance n100%defined at Q100%and H100%Q is flow rate in this instance defined as Q100% (see also EN 16297-1)H is Head in this instance defined as H100% (see also EN 16297-1) Note 2 to entry n100% is determined by linear interpolation of speeds arou
33、nd Q100%and H100% 3.3 inline pump housing pump housing where inlet and outlet are on the same axis DIN EN 16297-3:2013-04 EN 16297-3:2012 (E) 6 4 Symbols and units For the purpose of this document, the symbols, quantities and units given in Table 1 of EN 16297-1:2012 apply. 5 Performance requirement
34、s and safety requirements The requirements of EN 16297-1, EN 809 and EN 60335-2-51 apply. 6 Calculation of energy efficiency index (EEI) 6.1 General conditions Circulators integrated in products shall be dismantled from the product and measured with a reference pump housing; Circulators without pump
35、 housing intended to be integrated in a product shall be measured with a reference pump housing. 6.2 Procedure 6.2.1 Load profile for calculation of average compensated power input, PLavgThe load profile for circulators integrated in products is shown in Table 1. Table 1 Load profile for calculation
36、 of average compensated power input, PL,avgQ in % of Q100%Time in % of annual operating hours 100 L1 = 6 752 = 15 50 L3 = 35 254 = 44 6.2.2 Part load points of circulators integrated in products Part load operating points are measured by using following procedure: a) Calculate Hrefat each part load
37、point on the reference control curve (see Figure 4 in EN 16297-1:2012). b) If a circulator has a differential pressure control mode then follow the procedure specified in EN 16297-2. Otherwise the system curve and speed of the circulator by using the communication interface for external signals (def
38、ined by the manufacturer) to meet the part load points Figure 1. DIN EN 16297-3:2013-04 EN 16297-3:2012 (E) 7 HQH100%2(Q0%, )(Q100%, H100%)nQQi % Q100%n100%ni%aKey a system curve Figure 1 Part load point 6.2.3 Test conditions 6.2.3.1 Signal generator for external signals The speed is changed via an
39、external signal. A signal specification and/or signal generator can be required from the circulator manufacturer. 6.2.4 Calculation of average compensated power input, PL,avgThe average compensated power input, PL,avg, is calculated as: PP PP PPP P= + + += + + +L,avg 1 L,100% 2 L,75% 3 L,50% 4 L,25%
40、L,100% L,75% L,50% L,25%L LLL0,06 0,15 0,35 0,446.2.5 Calculation of energy efficiency index (EEI), EEIFor product integrated circulators, the energy efficiency index (EEI), EEI, is calculated as: L,avg L,avgEEI 20%ref ref0,49PPC = except for circulators integrated in products designed for primary c
41、ircuits for thermal solar systems and for heat pumps where the energy efficiency index (EEI), EEI, is calculated as: 1, 3 6 1, 3 6ss3,8 3,830 30L,avg L,avgEEI 20%ref ref10491nnPPCe e = = It is permissible to substitute the parameter EEIby the abbreviation EEI in data sheets, manuals, leaflets, broch
42、ures etc. DIN EN 16297-3:2013-04 EN 16297-3:2012 (E) 8 Annex ZA (informative) Relationship between this European Standard and the requirements of Commission Regulation (EC) No 641/2009 This European Standard has been prepared under a mandate given to CEN by the European Commission and the European F
43、ree Trade Association to provide a means of conforming to requirements Commission Regulation (EC) No 641/2009 of 22 July 2009: implementing Directive 2005/32/EC1of the European Parliament and of the Council with regard to ecodesign requirements for glandless standalone circulators and glandless circ
44、ulators integrated in products Once this standard is cited in the Official Journal of the European Union under that Commission Regulation , compliance with the clauses of this standard given in Table ZA.1 confers, within the limits of the scope of this standard, a presumption of conformity with the
45、corresponding requirements of that and associated EFTA regulations. Table ZA.1 Correspondence between this European Standard and Commission Regulation (EC) No 641/2009 Clauses and sub-clauses of this EN Requirements of CommissionRegulation (EC) No 641/2009 Qualifying remarks/Notes Part 1: 6.2.1 Anne
46、x II, 2., 3. Calculation of Phyd Part 1: 6.2.2 Annex II, 2., 4. Calculation of Pref Part 1: 6.2.4 Annex II, 2., 5. Reference control curve Part 1: 6.2.9 Annex II, 2., 9. Calculation of EEI Part 2: 6.2.5 Annex II, 2., 9. Calculation of EEI Part 3: 6.2.5 Annex II, 2., 9. Calculation of EEI WARNING Other requirements and other EU Directives may be applicable to the product(s) falling within the scope of this standard. 1The Directive was replaced by the Directive 2009/125/EC. DIN EN 16297-3:2013-04