1、October 2015 Translation by DIN-Sprachendienst.English price group 13No part of this translation may be reproduced without prior permission ofDIN Deutsches Institut fr Normung e. V., Berlin. Beuth Verlag GmbH, 10772 Berlin, Germany,has the exclusive right of sale for German Standards (DIN-Normen).IC
2、S 27.060.30!%FmP“2357445www.din.deDIN EN 16583Heat exchangers Hydronic room fan coils units Determination of the sound power level;English version EN 16583:2015,English translation of DIN EN 16583:2015-10Wrmebertrager WasserLuftVentilatorkonvektoren Bestimmung des Schallleistungspegels;Englische Fas
3、sung EN 16583:2015,Englische bersetzung von DIN EN 16583:2015-10changeurs thermiques Ventiloconvecteurs eau Dtermination du niveau de puissance acoustique;Version anglaise EN 16583:2015,Traduction anglaise de DIN EN 16583:2015-10www.beuth.deDocument comprises 24 pagesIn case of doubt, the German-lan
4、guage original shall be considered authoritative.D09.15DIN EN 16583:2015-10 2 A comma is used as the decimal marker. National foreword This document (EN 16583:2015) has been prepared by Technical Committee CEN/TC 113 “Heat pumps and air conditioning units” (Secretariat: AENOR, Spain). The responsibl
5、e German body involved in its preparation was the DIN-Normenausschuss Kltetechnik (DIN Standards Committee Refrigeration Technology), Working Committee NA 044-00-06 AA Elektromotorisch angetriebene Wrmepumpen und Luftkonditionierungsgerte. EUROPEAN STANDARD NORME EUROPENNE EUROPISCHE NORM EN 16583 A
6、ugust 2015 ICS 27.060.30 English Version Heat exchangers - Hydronic room fan coils units - Determination of the sound power level changeurs thermiques - Ventilo-convecteurs eau - Dtermination du niveau de puissance acoustique Wrmebertrager - Wasser-Luft-Ventilatorkonvektoren - Bestimmung des Schalll
7、eistungspegels This European Standard was approved by CEN on 27 June 2015. CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliog
8、raphical references concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN member. This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsib
9、ility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same status as the official versions. CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republi
10、c of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United Kingdom. EUROPEAN COMMITTEE FOR STANDARDIZATION COMIT EUROPEN DE NORMALIS
11、ATION EUROPISCHES KOMITEE FR NORMUNG CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels 2015 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 16583:2015 EEN 16583:2015 (E) 2 Contents Page European foreword .3 1 Scope 4
12、 2 Normative references 4 3 Terms and definitions .5 4 Measuring instruments .5 5 Operation of the unit .6 6 Installation 7 6.1 General 7 6.2 Non ducted units7 6.2.1 General 7 6.2.2 Floor mounted unit 7 6.2.3 Wall mounted unit 8 6.2.4 High wall mounted unit .9 6.2.5 Cassette and under ceiling mounte
13、d units 10 6.2.6 Under floor mounted 10 6.3 Ducted units 10 6.3.1 General . 10 6.3.2 Discharge or inlet sides . 11 6.3.3 Sound level radiated by the casing . 17 7 Acoustic measurement 18 7.1 Frequency range . 18 7.2 Acoustic standard. 18 7.3 Diffuse field . 18 7.4 Free field 19 7.5 In-duct measureme
14、nt . 19 8 Uncertainty 19 9 Test report . 20 9.1 General information 20 9.2 Additional information . 20 9.3 Test results 20 10 Data to be recorded 21 11 Manufacturers data 21 Bibliography . 22 DIN EN 16583:2015-10 EN 16583:2015 (E) 3 European foreword This document (EN 16583:2015) has been prepared b
15、y Technical Committee CEN/TC 113 “Heat pumps and air conditioning units”, the secretariat of which is held by AENOR. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by February 2016, and conflicting
16、national standards shall be withdrawn at the latest by February 2016. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN and/or CENELEC shall not be held responsible for identifying any or all such patent rights. According to the
17、 CEN/CENELEC Internal Regulations, the national standards organisations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hu
18、ngary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom. DIN EN 16583:2015-10 EN 16583:2015 (E) 4 1 Scope This European Standard applies to hydronic fan coil un
19、its (FCU) as factory-made single assemblies which provide the functions of cooling and/or heating but do not include the source of cooling or heating. The standard covers both air free delivery and air ducted units with a maximum external static pressure due to duct resistance of 120 Pa max. This Eu
20、ropean Standard provides methods for the determination of the acoustical performance of fan coil units, defining standard working condition and installation. It is not the purpose of this standard to specify the tests used for production or field testing. NOTE For the purpose of remaining clauses, t
21、he term “unit” is used to mean “fan coil unit” as defined in 3.1 of EN 1397:2015. 2 Normative references The following documents, in whole or in part, are normatively referenced in this document and are indispensable for its application. For dated references, only the edition cited applies. For unda
22、ted references, the latest edition of the referenced document (including any amendments) applies. EN 1397:2015, Heat exchangers - Hydronic room fan coil units - Test procedures for establishing the performance EN ISO 3741, Acoustics - Determination of sound power levels and sound energy levels of no
23、ise sources using sound pressure - Precision methods for reverberation test rooms (ISO 3741) EN ISO 3743-1, Acoustics - Determination of sound power levels and sound energy levels of noise sources using sound pressure - Engineering methods for small movable sources in reverberant fields - Part 1: Co
24、mparison method for a hard-walled test room (ISO 3743-1) EN ISO 3743-2, Acoustics - Determination of sound power levels of noise sources using sound pressure - Engineering methods for small, movable sources in reverberant fields - Part 2: Methods for special reverberation test rooms (ISO 3743-2) EN
25、ISO 3744, Acoustics - Determination of sound power levels and sound energy levels of noise sources using sound pressure - Engineering methods for an essentially free field over a reflecting plane (ISO 3744) EN ISO 3745, Acoustics - Determination of sound power levels and sound energy levels of noise
26、 sources using sound pressure - Precision methods for anechoic rooms and hemi-anechoic rooms (ISO 3745) EN ISO 9614-1, Acoustics - Determination of sound power levels of noise sources using sound intensity - Part 1: Measurement at discrete points (ISO 9614-1) EN ISO 9614-2, Acoustics - Determination
27、 of sound power levels of noise sources using sound intensity - Part 2: Measurement by scanning (ISO 9614-2) EN ISO 9614-3, Acoustics - Determination of sound power levels of noise sources using sound intensity - Part 3: Precision method for measurement by scanning (ISO 9614-3) EN ISO 80000-8:2007,
28、Quantities and units - Part 8: Acoustics (ISO 80000-8:2007, corrected 2007-08-15) DIN EN 16583:2015-10 EN 16583:2015 (E) 5 3 Terms and definitions For the purposes of this document, the following terms and definitions apply. 3.1 hydronic fan-coil unit factory-made single assembly which provides one
29、or more of the functions of forced circulation of air, heating, cooling, dehumidification and filtering of air, but which does not include the source of heating or cooling Note 1 to entry: This device includes at least a liquid-to-air heat exchanger and a fan, and may be designed for free or ducted
30、intake air and/or for free or ducted delivery of supply air. 3.2 total electric power input total electric power absorbed by the unit, including fan(s) and auxiliary devices but excluding any electrical resistance heater 3.3 standard fan speed fan speed setting declared by the manufacturer and used
31、for setting the air flow rate conditions of ducted units Note 1 to entry: The fan speed setting can be declared by the manufacturer as a certain wiring, a switch position or a steering voltage. 3.4 external static pressure positive pressure difference measured between the air outlet and inlet sectio
32、ns of the unit 3.5 acoustics for acoustic quantities, the definitions of EN ISO 80000-8:2007 apply 4 Measuring instruments The acoustic instruments shall fulfil the requirements of the acoustic standard used for the test. Other measurements can be necessary for the tests: Electrical: voltage (V), cu
33、rrent (A), total electric power input (W); Pressure (Pa); Rotation speed (min-1). Measurements for the ambient conditions: Relative humidity (%); Air Temperature (C); Atmospheric pressure (kPa). Table 1 gives the uncertainties allowed for these measurement values. DIN EN 16583:2015-10 EN 16583:2015
34、(E) 6 Table 1 Uncertainties of measurement for indicated values Measured quantity Unit Uncertainty of measurement Air static pressure difference Pa 3 Pa (P 100 Pa) 3% (P 100 Pa) Electrical quantities Voltage V 0,5 % Current A 0,5 % Power W 1 % or minimum 1 W Rotation speed min-1 1 % Relative humidit
35、y HR 5 % Atmospheric pressure kPa 1 % Temperature C 0,5 K 5 Operation of the unit The testing conditions are given in EN 1397:2015 except the following: The acoustic test shall be performed without connection to water supply, without water staying in the water circuit, with dry coil surface and an i
36、nlet air temperatures between 15 C and 25 C. The control of the relative humidity is not required. If the unit includes flaps, they shall be adjusted in a fixed position according to the manufacturer instructions. If this information is not available, their position shall correspond to the maximum m
37、echanical open position. NOTE 1 This maximum mechanical open position might differ from the minimum airflow resistance. For testing, the unit shall include an air filter but no any other accessory for air inlet or diffusion or others. Dampers for fresh air intake shall be closed. NOTE 2 No modificat
38、ion such as sealing is made on the unit before testing. For ducted units, an external static pressure difference of 50 Pa ( 1 Pa) shall be applied to the unit for the standard fan speed declared by the manufacturer. If other speeds are tested, the same network curve resistance shall be used. See Fig
39、ure 1. If the resistance is obtained by using an auxiliary fan, preliminary tests shall be done to determine the external static difference for each additional speed. DIN EN 16583:2015-10 EN 16583:2015 (E) 7 Key 1 ductwork load curve 2 reference standard speed 3 other speeds X external static pressu
40、re difference Y flow rate Figure 1 Setup external static pressure difference of ducted units for other speeds 6 Installation 6.1 General The typical types of units are presented in the annex of EN 1397:2015. Tests shall be made in suitable acoustic test chambers. 6.2 Non ducted units 6.2.1 General T
41、he target is the sound power level radiated by the whole unit, without distinction of inlet or discharge sides nor casing radiation. 6.2.2 Floor mounted unit The unit shall be installed on the hard floor at a minimum of 1 500 mm away from any wall out of any symmetry axis. The feet provided by the m
42、anufacturer shall be used. For aerodynamic purpose, the space between the feet shall be closed in the rear part to simulate the wall, with a rigid and reflective plate, with the same width of the unit and not exceeding its height. See Figure 2. DIN EN 16583:2015-10 EN 16583:2015 (E) 8 This plate sha
43、ll be in chipboard or equivalent, density 600 kg/m to 700 kg/m, and thickness 19 mm to 22 mm. Key 1 fan coil unit 2 feet 3 plate to close the space between the feet on the rear side 4 front side of the fan coil unit 5 rear side of the fan coil unit Figure 2 Floor mounted unit with a closing plate be
44、tween the feet 6.2.3 Wall mounted unit For low-wall mounting units, the distance to the floor given by the manufacturer shall be respected. Without information from the manufacturer, this distance shall be 150 mm. For aerodynamic purpose, the space between the unit and the floor shall be closed in t
45、he rear part to simulate the wall, with a rigid and reflective plane, with the same width of the unit and not exceeding its height. See Figure 3. The characteristics of the frame shall be such that any impact on the acoustic measurement by the frame radiation may be avoided. This plate shall be in c
46、hipboard or equivalent, density 600 kg/m to 700 kg/m, and thickness 19 mm to 22 mm. DIN EN 16583:2015-10 EN 16583:2015 (E) 9 Key 1 fan coil unit 2 supporting frame 3 plate to close the space between the unit and the floor, at the rear side Figure 3 Example of installation low wall unit mounted on a
47、frame, with the back plate 6.2.4 High wall mounted unit The unit shall be installed on a frame at a minimum of 1 500 mm away from any wall, out of any symmetry axis. For high-wall units, the height shall be at a minimum of 1 500 mm from the floor. See Figure 4. The characteristics of the frame shall
48、 be such that any impact on the acoustic measurement by the frame radiation may be avoided. Key 1 fan coil unit 2 supporting frame Figure 4 Example of installation of high wall unit mounted on a frame DIN EN 16583:2015-10 EN 16583:2015 (E) 10 6.2.5 Cassette and under ceiling mounted units The unit s
49、hall be hung on a frame, using elastic connection (elastic strap or uncoupled rigid stinger) to avoid vibration transmission, linked to the unit according to the manufacturer instructions. No additional plate is allowed on the top of unit to simulate the ceiling. The distance between the bottom of the unit and the floor shall be at a minimum of 1 500 mm, see Figure 5. The distance between the top of the unit and the ceiling of the testing room shall be at least 1 500 mm. Figure 5 Example of