1、September 2014DEUTSCHE NORM DIN/VDE-DKE Deutsche Kommission Elektrotechnik Elektronik InformationstechnikPreisgruppe 14DIN Deutsches Institut fr Normung e. V. Jede Art der Vervielfltigung, auch auszugsweise, nur mit Genehmigung des DIN Deutsches Institut fr Normung e. V., Berlin, gestattet.ICS 91.14
2、0.50; 35.240.99!%7A“2203004www.din.deDDIN EN 62056-7-6Datenkommunikation der elektrischen Energiemessung DLMS/COSEM Teil 7-6: HDLC basiertes 3-Schichten Kommunikations-Protokoll(IEC 62056-7-6:2013);Englische Fassung EN 62056-7-6:2013Electricity metering data exchange The DLMS/COSEM suite Part 7-6: T
3、he 3-layer, connection-oriented HDLC based communication profile(IEC 62056-7-6:2013);English version EN 62056-7-6:2013Echange des donnes de comptage de llectricit La suite DLMS/COSEM Partie 7-6: Profil de communication 3 couches, orient connexion et bas sur HDLC(CEI 62056-7-6:2013);Version anglaise
4、EN 62056-7-6:2013Alleinverkauf der Normen durch Beuth Verlag GmbH, 10772 BerlinTeilweiser Ersatz frDIN EN 62056-53:2007-08Siehe Anwendungsbeginnwww.beuth.deGesamtumfang 20 SeitenDIN EN 62056-7-6:2014-09 2 Anwendungsbeginn Anwendungsbeginn fr die von CENELEC am 2013-06-20 angenommene Europische Norm
5、als DIN-Norm ist 2014-09-01. Fr DIN EN 62056-53:2007-08 besteht eine bergangsfrist bis 2016-06-20. Nationales Vorwort Vorausgegangener Norm-Entwurf: E DIN EN 62056-7-6:2011-10. Fr dieses Dokument ist das nationale Arbeitsgremium K 461 Elektrizittszhler“ der DKE Deutsche Kommission Elektrotechnik Ele
6、ktronik Informationstechnik im DIN und VDE (www.dke.de) zustndig. Die enthaltene IEC-Publikation wurde vom TC 13 Equipment for electrical energy measurement and load control“ erarbeitet. Das IEC-Komitee hat entschieden, dass der Inhalt dieser Publikation bis zu dem Datum (stability date) unverndert
7、bleiben soll, das auf der IEC-Website unter http:/webstore.iec.ch“ zu dieser Publikation angegeben ist. Zu diesem Zeitpunkt wird entsprechend der Entscheidung des Komitees die Publikation besttigt, zurckgezogen, durch eine Folgeausgabe ersetzt oder gendert. Fr den Fall einer undatierten Verweisung i
8、m normativen Text (Verweisung auf eine Norm ohne Angabe des Ausgabedatums und ohne Hinweis auf eine Abschnittsnummer, eine Tabelle, ein Bild usw.) bezieht sich die Verweisung auf die jeweils neueste gltige Ausgabe der in Bezug genommenen Norm. Fr den Fall einer datierten Verweisung im normativen Tex
9、t bezieht sich die Verweisung immer auf die in Bezug genommene Ausgabe der Norm. Der Zusammenhang der zitierten Normen mit den entsprechenden Deutschen Normen ergibt sich, soweit ein Zusammenhang besteht, grundstzlich ber die Nummer der entsprechenden IEC-Publikation. Beispiel: IEC 60068 ist als EN
10、60068 als Europische Norm durch CENELEC bernommen und als DIN EN 60068 ins Deutsche Normenwerk aufgenommen. Das Prsidium des DIN hat mit Prsidialbeschluss 1/2004 festgelegt, dass DIN-Normen, deren Inhalt sich auf internationale Arbeitsergebnisse der Informationsverarbeitung grndet, unter bestimmten
11、Bedingungen allein in englischer Sprache verffentlicht werden drfen. Diese Bedingungen sind fr die vorliegende Norm erfllt. Da sich die Benutzer der vorliegenden Norm der englischen Sprache als Fachsprache bedienen, wird die Englische Fassung der EN 62056-7-6 verffentlicht. Fr viele der verwendeten
12、Begriffe existieren keine gebruchlichen deutschen Benennungen, da sich die deutschen Anwender in der Regel ebenfalls der englischen Benennungen bedienen. Diese Norm steht nicht in unmittelbarem Zusammenhang mit Rechtsvorschriften und ist nicht als Sicherheitsnorm anzusehen. Das Original-Dokument ent
13、hlt Bilder in Farbe, die in der Papierversion in einer Graustufen-Darstellung wiedergegeben werden. Elektronische Versionen dieses Dokuments enthalten die Bilder in der originalen Farbdarstellung. In IEC 62056-7-6:2013 ist folgender Hinweis enthalten: Die Internationale Elektrotechnische Kommission
14、(IEC) weist darauf hin, dass die bereinstimmung mit diesem Dokument die Verwendung von Patenten hinsichtlich Protokoll-Stack in IEC 62056-7-6 bedeuten kann. Die IEC nimmt keine Stellung zur Rechtmigkeit, zur Gltigkeit und zum Anwendungsbereich dieser Patent-rechte. DIN EN 62056-7-6:2014-09 3 Der Hal
15、ter dieser Patentrechte hat IEC zugesichert, dass er bereit ist, ber Lizenzen zu vernnftigen und nicht diskriminierenden Geschftsbedingungen mit Antragstellern in der ganzen Welt zu verhandeln. In diesem Zusammenhang ist die Erklrung des Halters dieser Patentrechte bei IEC registriert. Informationen
16、 sind erhltlich bei: DLMS User Association Zug/Schweiz www.dlms.ch nderungen Gegenber DIN EN 62056-53:2007-08 wurden folgende nderungen vorgenommen: a) Der Titel dieser Norm wurde an die Titel anderer Teile der berarbeiteten Reihe EN 62056 angepasst; b) ein Bild, das den Protokoll-Stack zeigt, wurde
17、 in Abschnitt 5 hinzugefgt; c) EN 62056-53:2007 enthlt die Spezifikationen der DLMS/COSEM-Kommunikationsprofile, whrend die neue EN 62056-5-3:2013, die EN 62056-53:2007 ersetzt, diese nicht enthlt. Frhere Ausgaben DIN EN 62056-53: 2003-01, 2007-08 DIN EN 62056-53 Berichtigung 1: 2003-04 DIN EN 62056
18、-7-6:2014-09 4 Leerseite EUROPEAN STANDARD EN 62056-7-6 NORME EUROPENNE EUROPISCHE NORM September 2013 CENELEC European Committee for Electrotechnical Standardization Comit Europen de Normalisation Electrotechnique Europisches Komitee fr Elektrotechnische Normung CEN-CENELEC Management Centre: Avenu
19、e Marnix 17, B - 1000 Brussels 2013 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members. Ref. No. EN 62056-7-6:2013 E ICS 17.220; 35.110; 91.140.50 Supersedes EN 62056-53:2007 (partially)English version Electricity metering data exchange - The DLM
20、S/COSEM suite - Part 7-6: The 3-layer, connection-oriented HDLC based communication profile (IEC 62056-7-6:2013) Echange des donnes de comptage de llectricit - La suite DLMS/COSEM - Partie 7-6: Profil de communication 3 couches, orient connexion et bas sur HDLC (CEI 62056-7-6:2013) Datenkommunikatio
21、n der elektrischen Energiemessung - DLMS/COSEM - Teil 7-6: HDLC basiertes 3-Schichten Kommunikations-Protokoll (IEC 62056-7-6:2013) This European Standard was approved by CENELEC on 2013-06-20. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditio
22、ns for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CENELEC member. This European Standard exist
23、s in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the same status as the official versions. CENELEC members are the natio
24、nal electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Port
25、ugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom. DIN EN 62056-7-6:2014-09 EN 62056-7-6:2013 Foreword The text of document 13/1527/FDIS, future edition 1 of IEC 62056-7-6, prepared by IEC/TC 13 “Electrical energy measurement, tariff- and load control“ was
26、submitted to the IEC-CENELEC parallel vote and approved by CENELEC as EN 62056-7-6:2013. The following dates are fixed: latest date by which the document has to be implemented at national level by publication of an identical national standard or by endorsement (dop) 2014-03-20 latest date by which t
27、he national standards conflicting with the document have to be withdrawn (dow) 2016-06-20 EN 62056-7-6:2013 supersedes partially EN 62056-53:2007. It is based on EN 62056-53:2007, Electricity metering Data exchange for meter reading, tariff and load control Part 53: COSEM application layer, Annex B.
28、2 The 3-layer, connection-oriented, HDLC based communication profile and introduces the following significant technical changes: NOTE EN 62056-53:2007 contains the specification of the DMS/COSEM communication profiles whereas the new edition, EN 62056-5-3:2013, which replaces it, does not. The title
29、 of the standard has been aligned with the title of other parts of the revised EN 62056 series; A Figure showing the protocol stack has been added to Clause 5. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CENELEC and/or CEN sha
30、ll not be held responsible for identifying any or all such patent rights. Endorsement notice The text of the International Standard IEC 62056-7-6:2013 was approved by CENELEC as a European Standard without any modification. 2 DIN EN 62056-7-6:2014-09 EN 62056-7-6:2013 CONTENTS 1 Scope 4 2 Normative
31、references .4 3 Terms, definitions and abbreviations .4 4 Targeted communication environments .5 5 Structure of the profile 5 6 Identification and addressing scheme6 7 Supporting layer services and service mapping .7 8 Communication profile specific service parameters of the DLMS/COSEM AL services8
32、9 Specific considerations / constraints .8 9.1 Confirmed and unconfirmed AAs and data transfer service invocations, frame types used8 9.2 Correspondence between AAs and data link layer connections, releasing AAs 9 9.3 Service parameters of the COSEM-OPEN / -RELEASE / -ABORT services .9 9.4 EventNoti
33、fication service and protocol10 9.5 Transporting long messages 12 9.6 Supporting multi-drop configurations 12 Bibliography .14 Index15 Annex ZA (normative) Normative references to international publications with their corresponding European publications .16 Figure 1 The DLMS/COSEM 3-layer, connectio
34、n oriented, HDLC based communication profile.6 Figure 2 Identification/addressing scheme in the 3-layer, CO, HDLC-based communication profile .7 Figure 3 Summary of data link layer services8 Figure 4 Example: EventNotificaton triggered by the client11 Figure 5 Multi-drop configuration and its model.
35、12 Figure 6 Master/ Slave operation on the multi-drop bus.12 Table 1 Application associations and data exchange in the 3-layer, CO, HDLC-based profile.9 3 DIN EN 62056-7-6:2014-09 EN 62056-7-6:2013 ELECTRICITY METERING DATA EXCHANGE THE DLMS/COSEM SUITE Part 7-6: The 3-layer, connection-oriented HDL
36、C based communication profile 1 Scope This part of IEC 62056 specifies the DLMS/COSEM 3-layer, connection-oriented HDLC based communication profile. 2 Normative references The following documents, in whole or in part, are normatively referenced in this document and are indispensable for its applicat
37、ion. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. IEC 62056-21:2002, Electricity metering Data exchange for meter reading, tariff and load control Part 21: Direct local data exchange IE
38、C 62056-42:2002, Electricity metering Data exchange for meter reading, tariff and load control Part 42: Physical layer services and procedures for connection-oriented asynchronous data exchange IEC 62056-46:2002, Electricity metering Data exchange for meter reading, tariff and load control Part 46:
39、Data link layer using HDLC protocol Amendment 1:2006 IEC 62056-5-3:, Electricity metering data exchange The DLMS/COSEM suite Part 5-3: DLMS/COSEM application layer NOTE See also the Bibliography. 3 Terms, definitions and abbreviations AA Application Association AARQ A-Associate Request an APDU of th
40、e ACSE ACSE Association Control Service Element AL Application Layer APDU Application Layer Protocol Data Unit ASO Application Service Object Client A station, asking for services. In the case of the 3-layer, CO HDLC based profile it is the master station .cnf confirm service primitive CO Connection
41、-oriented COSEM Companion Specification for Energy Metering DLMS Device Language Message Specification DLMS UA DLMS User Association GSM Global System for Mobile Communications HDLC High-level Data Link Control 4 DIN EN 62056-7-6:2014-09 EN 62056-7-6:2013 HHU Hand Held Unit I Information frame (a HD
42、LC frame type) .ind .indication service primitive LLC Logical Link Control (Sublayer) MAC Medium Access Control (sublayer) MAC Message Authentication Code (cryptography) master Central station station which takes the initiative and controls the data flow NRM Normal Response Mode OSI Open System Inte
43、rconnection PDU Protocol Data Unit P/F Poll/Final PhL Physical Layer PSTN Public Switched Telephone Network .req .request service primitive .res .response service primitive RNR Receive Not Ready (a HDLC frame type) RR Receive Ready (a HDLC frame type) SAP Service Access Point SNRM Set Normal Respons
44、e Mode (a HDLC frame type) Server A station, delivering services. The tariff device (meter) is normally the server, delivering the requested values or executing the requested tasks. Slave Station responding to requests of a master station. The tariff device (meter) is normally a slave station. UA Un
45、numbered Acknowledge (a HDLC frame type) UI Unnumbered Information (a HDLC frame type) 4 Targeted communication environments The 3-layer, CO, HDLC-based profile is suitable for local data exchange with metering equipment via direct connection, or remote data exchange via the PSTN or GSM networks wit
46、h appropriate modems. 5 Structure of the profile This profile is based on a three-layer (collapsed) OSI protocol architecture: the DLMS/COSEM AL, specified in IEC 62056-5-3; the data link layer based on the HDLC standard, specified in IEC 62056-46; the physical layer; specified in IEC 62056-42. This
47、 three-layer architecture is shown in Figure 1. The use of the PhL for the purposes of direct local data exchange using an optical port or a current loop physical interface is specified in IEC 62056-21:2002, Annex E. 5 DIN EN 62056-7-6:2014-09 EN 62056-7-6:2013 COSEM Application ProcessIEC 62056-6-1
48、, IEC 62056-6-2DLMS/COSEM Application layerACSE and xDLMS ASEData security ASEIEC 62056-5-3Physical connection managerPhysical layerIEC 62056-42Data link layer using HDLC protocolIEC 62056-46PH-DATAservicesPH-CONNECTPH-ABORTPH-DATAservicesPH-ABORTindicationDL-DATA servicesDL-CONNECTDL-DISCONNECTserv
49、icesCOSEM-OPENCOSEM-RELEASECOSEM-ABORTservicesxDLMSservicesIEC 1143/13 Figure 1 The DLMS/COSEM 3-layer, connection oriented, HDLC based communication profile 6 Identification and addressing scheme The HDLC-based data link layer provides services to the DLMS/COSEM AL at Data Link SAP-s, also called as the Data Link- or HDLC addresses. On the client side, only the client AP needs to be identified. The addressing of the physical devic