1、January 2009DEUTSCHE NORM English price group 10No part of this standard may be reproduced without prior permission ofDIN Deutsches Institut fr Normung e. V., Berlin. Beuth Verlag GmbH, 10772 Berlin, Germany,has the exclusive right of sale for German Standards (DIN-Normen).ICS 23.060.99!$UKY“1504054
2、www.din.deDDIN EN ISO 11117Gas cylinders Valve protection caps and valve guards Design, construction and tests (ISO 11117:2008)English version of DIN EN ISO 11117:2009-01Gasflaschen Ventilschutzkappen und Ventilschutzkrbe Auslegung, Bau und Prfungen (ISO 11117:2008)Englische Fassung DIN EN ISO 11117
3、:2009-01SupersedesDIN EN 962:2000-11www.beuth.deDocument comprises 16 pagesDIN EN ISO 11117:2009-01 2 National foreword This document has been prepared by Technical Committee ISO/TC 58 “Gas cylinders” in collaboration with Technical Committee CEN/TC 23 “Transportable gas cylinders” (Secretariat: BSI
4、, United Kingdom). The responsible German body involved in its preparation was the Normenausschuss Druckgasanlagen (Pressurized Gas Installations Standards Committee), Technical Committee NA 016-00-03 AA Druckgas-flaschen und Ausrstung. Amendments This standard differs from DIN EN 962:2000-11 as fol
5、lows: a) Valve protection devices for breathing apparatus cylinders have been excluded from the scope. b) The drop test has been extended to include low temperatures (20 C). c) The contents of the cylinders used for the drop test has been limited depending on the permitted mass. d) Clause 7 “Marking
6、” has been extended to include the date of manufacture for non-metallic caps and guards. e) EN 962 and ISO 11117 have been combined in one document. Previous editions DIN 4661-6: 1968-09 DIN 4664: 1989-08 DIN 4664-1: 1969-06 DIN 4665: 1934-12, 1940-10 DIN 4667: 1934-12 DIN 4667-1: 1944-01 DIN 4668:
7、1934-12, 1968-09 DIN 4668-1: 1944-02 DIN 4668-2: 1944x-01 DIN 4669: 1934-12, 1944-01 DIN 4671: 1934-12, 1954-09 DIN EN 962: 1996-09, 2000-04, 2000-11 DIN 4666: 1934-12, 1940-09 EUROPEAN STANDARDNORME EUROPENNEEUROPISCHE NORMEN ISO 11117September 2008ICS 11.040.10; 23.020.30 Supersedes EN 962:1996 En
8、glish VersionGas cylinders - Valve protection caps and valve guards -Design, construction and tests (ISO 11117:2008)Bouteilles gaz - Chapeaux ferms et chapeaux ouvertsde protection des robinets - Conception, construction etessais (ISO 11117:2008)Gasflaschen - Ventilschutzkappen und Ventilschutzkrbe
9、-Auslegung, Bau und Prfungen (ISO 11117:2008)This European Standard was approved by CEN on 7 February 2008.CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this EuropeanStandard the status of a national standard without any alteratio
10、n. Up-to-date lists and bibliographical references concerning such nationalstandards may be obtained on application to the CEN Management Centre or to any CEN member.This European Standard exists in three official versions (English, French, German). A version in any other language made by translatio
11、nunder the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as theofficial versions.CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland,France, Germany, Greece
12、, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.EUROPEAN COMMITTEE FOR STANDARDIZATIONCOMIT EUROPEN DE NORMALISATIONEUROPISCHES KOMITEE FR NORMUNGManagement Cent
13、re: rue de Stassart, 36 B-1050 Brussels 2008 CEN All rights of exploitation in any form and by any means reservedworldwide for CEN national Members.Ref. No. EN ISO 11117:2008: E2 DIN EN ISO 11117:2009-01 EN ISO 11117:2008 (E) Contents Page Foreword .3 Introduction.4 1 Scope5 2 Normative references5
14、3 Terms and definitions .5 4 General requirements .6 4.1 Cap6 4.2 Guard 6 4.3 Testing6 5 Materials .11 6 Type testing .11 6.1 General .11 6.2 Documentation 11 6.3 Number of test samples11 6.4 Preliminary check11 6.5 Torque test (one test)11 6.6 Axial test (one test) .12 6.7 Drop test.12 7 Marking.13
15、 8 Test report13 Annex A (normative) Marking of caps 14 Foreword 3 EN ISO 11117:2008 (E) DIN EN ISO 11117:2009-01 This document (EN ISO 11117:2008) has been prepared by Technical Committee ISO/TC 58 “Gas cylinders“ in collaboration with Technical Committee CEN/TC 23 “Transportable gas cylinders”, th
16、e secretariat of which is held by BSI. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by March 2009, and conflicting national standards shall be withdrawn at the latest by March 2009. Attention is d
17、rawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN and/or CENELEC shall not be held responsible for identifying any or all such patent rights. This document supersedes EN 962:1996. According to the CEN/CENELEC Internal Regulations, the nationa
18、l standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Pol
19、and, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom. Endorsement notice The text of ISO 11117:2008 has been approved by CEN as EN ISO 11117:2008 without any modification. Introduction This International Standard covers devices intended for the protection of
20、gas cylinder valves, where such protection is required, for example, where the valve is unable to meet the impact test requirements of the relevant valve standard to allow safe transport, handling and storage without such protection. This International Standard specifies the principal dimensions, re
21、quirements for fitment and drop test procedure, to confirm the provision of adequate valve protection, in the event of the occurrence of a cylinder toppling from its base. 4 DIN EN ISO 11117:2009-01 EN ISO 11117:2008 (E) 1 Scope This International Standard specifies the requirements for valve protec
22、tion caps and guards for gas cylinders. This International Standard defines tests for checking the mechanical strength and physical properties of the valve protection cap or valve guard. This International Standard applies to protection devices for valves used on cylinders for liquefied, dissolved o
23、r compressed gases. This International Standard excludes protection devices for cylinders with a water capacity of 5 l or less and cylinders whereby the protection device is fixed by means of lugs welded or brazed to the cylinder, or is welded or brazed directly to the cylinder. This International S
24、tandard does not cover valve protection for breathing apparatus cylinders. This International Standard does not specify all the requirements that may be necessary to enable the valve protection device to be used for lifting the cylinder. 2 Normative references The following referenced documents are
25、indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. ISO 10297, Transportable gas cylinders Cylinder valves Specification and type testing IS
26、O 14245, Gas cylinders Specifications and testing of LPG cylinder valves Self-closing ISO 15995, Gas cylinders Specifications and testing of LPG cylinder valves Manually operated 3 Terms and definitions For the purposes of this document, the following terms and definitions apply. 3.1 valve protectio
27、n cap cap device securely fixed over the valve during handling, transportation and storage and which is removed for access to the valve 3.2 valve guard guard device protecting the valve during handling, transportation, storage NOTE The guard need not be removed to provide access to the valve. 5 EN I
28、SO 11117:2008 (E) DIN EN ISO 11117:2009-01 3.3 permitted mass mass of the cylinder, together with its permanent attachments and test substance contents, as used during the drop test See 6.7. 3.4 test valve gas filling and/or dispensing device used to verify the guard or protection cap approval in ac
29、cordance with this International Standard and which represents the valve of equal or lesser dimensions for which approved guards or protection caps provide suitable protection 4 General requirements 4.1 Cap The cap shall be of adequate strength to protect the valve during handling and transportation
30、. It shall be capable of being securely fixed to the cylinder, either by screwed thread or other suitable means. Provision should be made for assisted fitting or removal of the cap, for example, a hexagonal section. Unless otherwise specified, the cap shall be provided with vent hole(s), e.g. by dia
31、metrically opposed vent holes of 10 mm diameter. Two diametrically opposite vent holes shall be provided, each of them having a minimum diameter of 10 mm. (When the cap has no vent hole, the valve outlet passage of the cylinder shall be plugged to prevent leakage and subsequent pressure build up in
32、the cap.) Caps designed for use with valve dimensions in accordance with ISO 10297, as applicable, shall conform to dimensions given in Figure 1 and preferably Figure 4 where a threaded fixing connection is used. Caps designed for use with valves with dimensions other than those given in ISO 10297 s
33、hall be tested with the intended largest valve. The cap shall be of such dimensions as not to contact any part of the valve. See Tables 1 and 2. 4.2 Guard The guard shall be of adequate strength to protect the valve during handling and transportation. It shall be fixed so as to prevent easy removal
34、by the end user or dismantling under normal service conditions. The design shall permit ready access for valve operation and assembly of operational equipment. When the guard is of a rotating type, it shall be capable of manual orientation. The clearance dimensions of the guard given in Figure 2 are
35、 typical for valves designed in accordance with ISO 10297. The centre of the opening in the guard shall be within 10 mm of the valve outlet axis. The opening shall not extend below the reference plane. Where a threaded fixing connection is used, the preferred thread dimensions are given in Figure 4.
36、 Figure 3 gives examples of guards. 4.3 Testing Type testing of the protection devices shall be performed in accordance with the procedure described in Clause 6. 6 DIN EN ISO 11117:2009-01 EN ISO 11117:2008 (E) Dimensions in millimetres Key 1 cap with open top 5 cylinder neck ring 2 closed cap 6 ref
37、erence plane 3 cylinder axis 7 example A 4 vent W 10 mm 8 example B a 80 2,309 Whitworth. NOTE 1 The outlines and dimensions given are typical for caps in common use. Any other shape or dimension can be used, provided they give appropriate clearance around the valve. NOTE 2 The preferred 80 mm fixin
38、g connection is shown. Alternative sizes, e.g. 78 mm, can be used. Caps for such cylinders should have the appropriate dimensions. NOTE 3 For open tops, water drainage should be considered. Figure 1 Basic dimensions of valve protection caps and neck rings 7 EN ISO 11117:2008 (E) DIN EN ISO 11117:200
39、9-01 Dimensions in millimetres Key H height of the guard (at least 1 mm greater than the projection of the fully open valve above the reference plane) r maximum radius of handwheel 1 axis of the valve outlet 2 reference plane aMeasured at the lowest position of the handwheel. b 80 2,309 Whitworth. N
40、OTE 1 The outlines and dimensions given are typical for guards in common use. Any other shape or dimensions can be used, providing they give appropriate clearance around the valve. NOTE 2 The preferred 80 mm fixing connection is shown. Alternative sizes, e.g. 78 mm can be used. Guards for such cylin
41、ders should have the appropriate dimensions. NOTE 3 For valve details see ISO 10297, ISO 14245 and ISO 15995. NOTE 4 Provisions for water drainage should be considered. Figure 2 Basic dimensions of valve guard 8 DIN EN ISO 11117:2009-01 EN ISO 11117:2008 (E) a) b)c) d) e)f) g) Figure 3 Examples of v
42、alve guards 9 EN ISO 11117:2008 (E) DIN EN ISO 11117:2009-01 25,4p= zr = 0,137 329 p H = 0,960 491 p H1= 0,640 327 p Key 1 cap or guard thread profile 2 cylinder neck ring thread profile NOTE Other recognized thread forms are permitted, provided that all test requirements of this International Stand
43、ard are met. Figure 4 Thread Table 1 Dimensions of the thread Dimensions in millimetres Nominal diameter Major diameter Pitch diameter Minor diameter Pitch Number of threads per inch Thread height Radius d = D D2= D2D1= D1p z H1r W 80 80 78,521 77,042 2,309 11 1,479 0,317 Table 2 Tolerances of the t
44、hread Dimensions in millimetres Cylinder neck ring Cap or guard Nominal diameter Major diameter d Pitch diameter d2Minor diameterd1Major diameterD Pitch diameter D2Minor diameterD10,055 0 0 a +0,280 +0,630 W 80 0,530 0,280 0,450 0 0 +0,155 aNo maximum tolerance is specified but satisfactory operatio
45、n shall be ensured. 10 DIN EN ISO 11117:2009-01 EN ISO 11117:2008 (E) 5 Materials The cap or guard shall withstand impacts and falls throughout the whole range of operating temperatures from 20 C to +20 C. The relationship between material properties and operating temperature shall be taken into acc
46、ount. The cap or guard shall be designed to withstand local temperature conditions outside this range if specified. The cap or guard material shall be adequately resistant to atmospheric conditions and the transported product, including solvents e.g. acetone, dimethylformamide (D.M.F). 6 Type testin
47、g 6.1 General These tests qualify the protection device for use, only with valves of maximum dimensions equal to, or less than, that of the test valve, and with cylinders plus contents (gross mass) equal to or less than the permitted weight (see 3.3). 6.2 Documentation The following documents shall
48、be available: a description of the protection device and the method by which it is fixed to the cylinder; a complete set of drawings, identifying all dimensions and material specifications of the protection device; details of the intended service conditions, the intended valves and the intended cyli
49、nders; limitations on use, due to material incompatibility with the cylinder contents. 6.3 Number of test samples Thirteen samples shall be submitted for type testing: sample 1 for the torque test (if applicable); sample 2 for the axial test; samples 3 to 8 for the room temperature drop test; samples 9 and 10 for additional drop tests (see 6.7.5); samples 11 and 12 for extreme temperature tests; sample 13 for any additional test which may be required. 6.4 Preliminary check The design of the protection