1、INCH-POUNDA-A-59248June 16, 1998SUPERSEDINGGG-M-2742June 26, 1991COMMERCIAL ITEM DESCRIPTIONMETER, VOLUMETRIC, POSITIVE DISPLACEMENT, LIQUID, FUEL, 600 GPMThe General Services Administration has authorized the use of this commercialit em description for all Federal agencies.1. SCOPE. This commercial
2、 item description (CID) covers 600 gallon per minute (gpm)(2 271 litre per minute (L/m) diesel fuel, automotive gasoline, jet fuel and aviation gasolinevolumetric, positive displacement meters.2. SALIENT CHARACTERISTICS.2.1 Description . The positive displacement meter, herein after referred to as m
3、eter, shall be usedto meter fuel pumped into tanker trucks. The meter shall be capable of handling fuels at a flowrate of 600 gpm (2 271 L/m). The meter shall have a digital readout register that indicates thegallonage throughput. The fuels most generally metered shall be diesel fuel and automotiveg
4、asoline, however, under some circumstances it shall be used for metering of jet fuel and aviationgasoline. All fuels shall pass through a strainer prior to reaching the meter.2.2 Standard commercial product . The meter shall, as a minimum, be in accordance with therequirements of this CID and shall
5、be the manufacturers standard commercial product.Additional or better features which are not specifically prohibited by this CID, but which are apart of the manufacturers standard commercial product, shall be included in the meter beingfurnished. A standard commercial product is a product which is b
6、eing sold or is being currentlyoffered for sale on the commercial market through advertisements or manufacturers catalogs orbrochures, and represents the latest production model.Beneficial comments, recommendations, additions, deletions, clarifications, etc. and any datawhich may improve this docume
7、nt should be sent to: Officer in Charge (Code 15E2), SeabeeLogistics Center, 4111 San Pedro St., Port Hueneme, CA 93043-4410, by using theStandardization Document Improvement Proposal (DD Form 1426) appearing at the end of thisdocument or by letter.AMSC N/A FSC 6680Provided by IHSNot for ResaleNo re
8、production or networking permitted without license from IHS-,-,-A-A-5924822.3 Performance .2.3.1 Static pressure. The meter shall be capable of operating at a working pressure of275 pounds force per square inch (psi) (1 896 kilopascal (kPa).2.3.2 Flow pressure drop. The maximum pressure drop between
9、 inlet and outlet shall be notgreater than 5 psi (34.5 kPa) when operating at rated capacity.2.3.4 Meter error. The meter repeatability error shall be not greater than 0.1 percent for any onepredetermined flow rate and accuracy setting.2.3.5 Overload protection. The meter shall be capable of 125 per
10、cent of maximum rated capacitywithout damage to the mechanism.2.4 Environmental conditions . Unless otherwise specified (see 6.2), the meter shall be capable ofmeeting all performance requirements specified herein at ambient temperatures ranging from- 20 to 126 F (- 29 to 52 C). The maximum pressure
11、 drop at - 65 F (- 54 C) shall be notgreater than 4 psi (27.6 kPa). The meter shall meet all performance requirements under highhumidity, salt fog, sand and dust conditions.2.5 Design and construction .2.5.1 Interchangeability. All units of the same classification furnished with similar options unde
12、ra specific contract shall be identical to the extent necessary to ensure interchangeability ofcomponent parts, assemblies, accessories, and spare parts.2.5.2 Adjustment mechanism. The meter shall be equipped with an accuracy adjustmentmechanism that will operate without change during the life of th
13、e meter, except by manualadjustment. The accuracy adjustment mechanism shall be so designed as to be direct-reading andpermit ready adjustment without disassembly of the mechanism. The accuracy adjustment shallhave a range of not less than 5 percent.2.5.3 Inlet and outlet. Unless otherwise specified
14、 (see 6.2), the meter shall be designed forstraight-through flow. Unless otherwise specified (see 6.2), the meter shall be provided with4-inch 300 class raised face flanges in accordance with ANSI B16.24, and as specified herein.2.5.4 Meter register. The meter register shall be capable of recording
15、a volume of 99,999,999gallons (378 499 996 L) of fuel, and shall have a 8-digit totalizer unit. The meter register drivemechanism shall have a positive counter drive with no friction devices or a adjustable drivingmechanism capable of transmitting without slippage, a torque not less than 4 ounce-inc
16、hes (oz-in)(0.028 Newton metre (N m).2.5.5 Strainer. When specified (see 6.2), each meter shall be protected from pipe scale or foreignobjects by a strainer placed in the inlet piping to the meter.Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-A-A-5
17、924832.5.6 Indexing. Unless otherwise specified (see 6.2), the registers shall be of a type that can beindexed throughout a full revolution in increments of 30 degrees or less, to permit positioning ofthe register in any direction with relation to the meter housing. The meter register face shall hav
18、ea transparent, colorless face of sufficient size to provide a full view of all digits.2.5.7 Torque limitation. The breakaway torque required to rotate the input shaft of the registershall be not greater than 4 oz-in (0.028 N m) at - 65 F (- 54 C).2.6 Workmanship . All operations and processes invol
19、ved in accomplishing the requirements ofthis CID shall be in accordance with the highest grade practices associated with this type of work.3. REGULATORY REQUIREMENTS.3.1 Materials . The offeror/contractor is encouraged to use recovered materials to the maximumextent practicable, in accordance with p
20、aragraph 23.403 of the Federal Acquisition Regulation(FAR). Unless otherwise specified herein, all equipment, material, and articles incorporated in thework covered by this commercial item description are to be new and fabricated using materialsproduced from recovered materials to the maximum extent
21、 possible without jeopardizing theintended use. The term “recovered materials” means materials which have been collected orrecovered from solid waste and reprocessed to become a source of raw materials, as opposed tovirgin raw materials. Unless otherwise specified, none of the above shall be interpr
22、eted to meanthat the use of used or rebuilt products are allowed under this commercial item description.3.2 Metric products . Products manufactured to metric dimensions will be considered on an equalbasis with those manufactured using inch-pound units, provided they fall within specifiedtolerances u
23、sing conversion tables contained in the latest version of ASTM SI-10(IEEE/ASTM SI-10), and all other requirements of this commercial item description includingform, fit, and function are met. If a product is manufactured to metric dimensions and thesedimensions exceed the tolerances specified in the
24、 inch-pound units, a request should be made tothe contracting officer to determine if the product is acceptable. The contracting officer has theoption of accepting or rejecting the product.4. QUALITY ASSURANCE PROVISIONS.4.1 Product conformance . The products provided shall meet the salient characte
25、ristics of thiscommercial item description, conform to the producers own drawings, specifications, standards,and quality assurance practices, and be the same product offered for sale in the commercialmarket. The government reserves the right to require proof of such conformance.5. PACKAGING. The pre
26、servation, packing, and marking shall be as specified in the contract ororder.Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-A-A-5924846. NOTES.6.1 Source of documents .6.1.1 The Federal Acquisition Regulation (FAR) may be obtained from the Superint
27、endent ofDocuments, U.S. Government Printing Office, Washington, DC 20402.6.1.2 ANSI Standard is available from the American National Standards Institute, Inc.,11 West 42 nd Street, New York, NY 10036.6.1.3 ASTM Standard is available from the American Society for Testing and Materials,100 Barr Harbo
28、r Drive, West Conshohocken, PA 19428-2959.6.1.4 IEEE Standard is available from the Institute of Electrical and Electronics Engineers,IEEE Service Center, 445 Hoes Lane, P.O. Box 1331, Piscataway, NJ 08855-1331.6.2 Ordering data . Acquisition documents should specify the following:a. Title, number,
29、and date of this CID.b. When performance requirements are other than as specified (see 2.4).c. When the m eter and flanges are designed other than as specified (see 2.5.3).d. When pipe strainers are required (see 2.5.5).e. When register indexing is other than as specified (see 2.5.6).6.3 Supersessio
30、n data . This CID replaces Federal Specification GG-M-2742, datedJune 26, 1991.6.4 Metric units . The values stated in either inch-pound units or SI units are to be regardedseparately as standard. Within the text, the SI units are shown in brackets. The values stated ineach system are not exact equi
31、valents; therefore, each system should be used independently of theother. Combining values from the two systems may result in non-conformance with the standard.6.5 Subject term (key word) listing .AutomotiveAviationProvided by IHSNot for ResaleNo reproduction or networking permitted without license
32、from IHS-,-,-A-A-592485MILITARY INTERESTS: CIVIL AGENCY COORDINATING ACTIVITY:Custodians : GSA-FSSArmy - AVNavy - YD1 Preparing Activity :Air Force - 99 Navy - YD1Review Activities : (Project 6680-0258)Navy - AS, CGAir Force - 82DLA - GSProvided by IHSNot for ResaleNo reproduction or networking perm
33、itted without license from IHS-,-,-STANDARDIZATION DOCUMENT IMPROVEMENT PROPOSALINSTRUCTIONS1. The preparing activity must complete blocks 1, 2, 3, and 8. In block 1, both the document number and revision letter should begiven.2. The submitter of this form must complete blocks 4, 5, 6, and 7.3. The
34、preparing activity must provide a reply within 30 days from receipt of the form.NOTE: This form may not be used to request copies of documents, nor to request waivers, or clarification of requirements on currentcontracts. Comments submitted on this form do not constitute or imply authorization to wa
35、ive any portion of the referenceddocument(s) or to amend contractual requirements.I RECOMMEND A CHANGE: 1. DOCUMENT NUMBERA-A-59248 2. DOCUMENT DATE (YYMMDD) 9806163. DOCUMENT TITLEMETER, VOLUMETRIC, POSITIVE DISPLACEMENT, LIQUID, FUEL, 600 GPM4. NATURE OF CHANGE (Identify paragraph number and inclu
36、de proposed rewrite, if possible. Attach extra sheets as needed.)5. REASON FOR RECOMMENDATION6. SUBMITTERa. NAME (Last, First, Middle Initial) b. ORGANIZATIONc. ADDRESS (Include Zip Code) d. TELEPHONE (Include Area Code)(1) Commercial(2) AUTOVON(if applicable)7.DATE SUBMITTED(YYMMDD)8. PREPARING ACT
37、IVITYa. NAMERUSSELL REYNOLDSb. TELEPHONE Include Area Code)(1) Commercial (2) AUTOVON805-982-5946 551-5946c. ADDRESS (Include Zip Code)OFFICER IN CHARGE, SEABEE LOGISTICS CENTER(CODE 15E2), 4111 SAN PEDRO STREETPORT HUENEME, CA 93043-4410IF YOU DO NOT RECEIVE A REPLY WITHIN 45 DAYS, CONTACT:DEFENSE QUALITY AND STANDARDIZATION OFFICE5203 Leesburg Pike, Suite 1403, Falls Church, VA 22401-3466Telephone (703) 756-2340 AUTOVON 289-2340DD Form 1426, OCT 89 Previous editions are obsolete. 198/290Provided by IHSNot for ResaleNo reproduction or networking permitted without license from IHS-,-,-