1、BSI Standards PublicationBS EN 1366-2:2015Fire resistance tests for serviceinstallationsPart 2: Fire dampersBS EN 1366-2:2015 BRITISH STANDARDNational forewordThis British Standard is the UK implementation of EN 1366-2:2015. It supersedes BS EN 1366-2:1999 which is withdrawn. The UK participation in
2、 its preparation was entrusted to Technical Committee FSH/22/-/4, Fire resistance tests for dampers, seals and smoke extraction.A list of organizations represented on this committee can be obtained on request to its secretary.This publication does not purport to include all the necessary provisions
3、of a contract. Users are responsible for its correct application. The British Standards Institution 2015.Published by BSI Standards Limited 2015ISBN 978 0 580 86606 7 ICS 13.220.50 Compliance with a British Standard cannot confer immunity from legal obligations.This British Standard was published un
4、der the authority of the Standards Policy and Strategy Committee on 30 June 2015.Amendments/corrigenda issued since publicationDate T e x t a f f e c t e dEUROPEAN STANDARD NORME EUROPENNE EUROPISCHE NORM EN 1366-2 June 2015 ICS 13.220.50 Supersedes EN 1366-2:1999English Version Fire resistance test
5、s for service installations - Part 2: Fire dampers Essais de rsistance au feu des installations techniques - Partie 2 : Clapets rsistant au feu Feuerwiderstandsprfungen fr Installationen - Teil 2: Brandschutzklappen This European Standard was approved by CEN on 3 April 2015. CEN members are bound to
6、 comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CE
7、NELEC Management Centre or to any CEN member. This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has t
8、he same status as the official versions. CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxem
9、bourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United Kingdom. EUROPEAN COMMITTEE FOR STANDARDIZATION COMIT EUROPEN DE NORMALISATION EUROPISCHES KOMITEE FR NORMUNG CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brusse
10、ls 2015 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 1366-2:2015 EBS EN 1366-2:2015EN 1366-2:2015 (E) 2 Contents Page Foreword 4 Introduction .6 1 Scope 7 2 Normative references 7 3 Terms and definitions .7 4 Test equipment 8 4.
11、1 General 8 4.2 Connecting duct .8 4.3 Volume flow measuring station 9 4.4 Condensing unit .9 4.5 Gas temperature measuring devices .9 4.6 Exhaust fan system .9 5 Test conditions 9 6 Test specimen . 10 6.1 Size . 10 6.2 Number of tests . 10 6.2.1 General . 10 6.2.2 Supporting construction 10 6.2.3 M
12、ethod of installation in the supporting construction . 10 6.2.4 Method of installation on to the supporting construction 11 6.2.5 Method of installation away from the supporting construction. . 11 6.2.6 Blade pivot axis. 11 6.2.7 Application with no ducting on one or both sides, where additional evi
13、dence of insulation in such applications is required 11 6.3 Design 11 6.3.1 General . 11 6.3.2 Orientation to be tested . 12 6.3.3 Fire dampers installed within a wall or floor opening. 12 6.3.4 Fire dampers mounted on to the face of a wall or floor 12 6.3.5 Fire dampers mounted remote from a wall o
14、r floor 12 6.3.6 Application with no ducting on one or both sides, where additional evidence of insulation in such applications is required 12 6.3.7 Temperature sensing element . 13 7 Installation of test specimen . 13 7.1 General . 13 7.2 Supporting construction 13 7.3 Minimum separation . 14 8 Con
15、ditioning 14 8.1 General . 14 8.2 Water-based sealing materials 14 9 Application of instrumentation 14 9.1 Thermocouples . 14 9.1.1 Furnace thermocouples (plate thermometers) 14 9.1.2 Unexposed surface temperature . 14 9.2 Furnace pressure 15 BS EN 1366-2:2015EN 1366-2:2015 (E) 3 9.2.1 General 15 9.
16、2.2 Pressure differential measurement, furnace and connecting duct 15 10 Test procedure . 15 10.1 Determination of leakage of connecting duct and measuring station . 15 10.2 Opening and closing test 15 10.3 Determination of leakage at ambient temperature . 16 10.4 Fire test procedure 16 11 Performan
17、ce criteria 17 12 Test report 18 13 Field of direct application of test results 19 13.1 Size of fire damper . 19 13.2 Fire dampers installed within structural openings 19 13.3 Fire dampers installed onto the face of a wall or a floor . 19 13.4 Fire dampers remote from a wall or floor 19 13.5 Fire fr
18、om above 20 13.6 Separation between fire dampers and between fire dampers and construction elements . 20 13.7 Supporting constructions . 20 13.8 Blade pivot axis . 20 Bibliography 34 BS EN 1366-2:2015EN 1366-2:2015 (E) 4 Foreword This document (EN 1366-2:2015) has been prepared by Technical Committe
19、e CEN/TC 127 “Fire safety in buildings”, the secretariat of which is held by BSI. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by December 2015, and conflicting national standards shall be withdra
20、wn at the latest by December 2015. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN and/or CENELEC shall not be held responsible for identifying any or all such patent rights. This document supersedes EN 1366-2:1999. This docum
21、ent has been prepared under a mandate given to CEN by the European Commission and the European Free Trade Association. EN 1366, Fire resistance tests for service installations consists of the following parts: Part 1: Ventilation ducts; Part 2: Fire dampers (the present document); Part 3: Penetration
22、 seals; Part 4: Linear joint seals; Part 5: Service ducts and shafts; Part 6: Raised access and hollow core floors; Part 7: Conveyor systems and their closures; Part 8: Smoke extraction ducts; Part 9: Single compartment smoke extraction ducts; Part 10: Smoke control dampers; Part 11: Fire protective
23、 systems for cable systems and associated components (currently at Enquiry stage); Part 12: Non-mechanical fire barrier for ventilation ductwork. This standard underwent a formal review process during 2009-2011. Various comments were considered and these were only considered when they added clarity
24、to the procedure. No changes have been made that make historical data redundant. This was deliberately avoided where it was thought to be occurring. If there are some issues with this, consideration should be given to the spirit of the original test combined with the better clarity now given. The fo
25、llowing technical changes were made in this new edition: Changes include the fact that symmetry as a concept has been removed. This does not negate original tests, but may now mean that some additional tests are needed. The figures have been clarified to show some more detail. Testing away from a wa
26、ll or floor now has an equal distance between damper and the supporting construction. In this instance, historical data is not negated but any testing done after the publication of this standard needs to be done to the new dimensions. BS EN 1366-2:2015EN 1366-2:2015 (E) 5 Further information is give
27、n on thermocouple placement and the concepts of T3, T4, etc. have been added to make it clear which thermocouples should be considered and when. The description of details on additional thermocouples around discontinuities has been added for clarification. Additional information has been added to sh
28、ow the details for testing fire dampers to demonstrate insulation characteristics where a fire damper is to be used un-ducted, ducted on one side or ducted on both sides. According to the CEN-CENELEC Internal Regulations, the national standards organizations of the following countries are bound to i
29、mplement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Roma
30、nia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom. BS EN 1366-2:2015EN 1366-2:2015 (E) 6 Introduction The purpose of the test is to evaluate the ability of a fire damper to prevent fire and smoke spreading from one fire compartment to another through the air ductwork
31、 system which may penetrate fire separating walls and floors. The fire damper is attached (directly or remotely via a section of ducting), to a fire separating element in a manner representative of practice. Tests are performed starting with the fire damper in the open position to expose the tempera
32、ture sensing element of the fire damper to furnace conditions. Temperature and integrity measurements are carried out in various parts of the test construction during the test. The leakage of the fire damper system is measured (continuously during the test) by direct flow measurements whilst maintai
33、ning a constant pressure differential across the closed fire damper of 300 Pa. The leakage of the fire damper in the closed position is also measured at ambient temperature, when a reduced leakage classification needs to be achieved. An additional test to prove insulation characteristics may be need
34、ed if the damper needs to be used un-ducted on one side or on both sides. This test is not needed where such evidence is not required, or if insulation is not a requirement of performance, in the specific application. Caution The attention of all persons concerned with managing and carrying out this
35、 fire resistance test is drawn to the fact that fire testing may be hazardous and that there is a possibility that toxic and/or harmful smoke and gases may be evolved during the test. Mechanical and operational hazards may also arise during the construction of the test elements or structures, their
36、testing and disposal of test residues. An assessment of all potential hazards and risks to health should be made and safety precautions should be identified and provided. Written safety instructions should be issued. Appropriate training should be given to relevant personnel. Laboratory personnel sh
37、ould ensure that they follow written safety instructions at all times. BS EN 1366-2:2015EN 1366-2:2015 (E) 7 1 Scope This European Standard specifies a method for determining the fire resistance of fire dampers installed in fire separating elements designed to withstand heat and the passage of fire,
38、 smoke and gases at high temperature. This European Standard is used in conjunction with EN 1363-1. This standard is not suitable for testing fire dampers in suspended ceilings. This standard is not suitable for testing non-mechanical fire dampers (see EN 1366-12). 2 Normative references The followi
39、ng documents, in whole or in part, are normatively referenced in this document and are indispensable for its application. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 1363-1:2012, Fi
40、re resistance tests Part 1: General Requirements EN 1363-2, Fire resistance tests Part 2: Alternative and additional procedures EN 13501-3, Fire classification of construction products and building elements Part 3: Classification using data from fire resistance tests on products and elements used in
41、 building service installations: fire resisting ducts and fire dampers EN ISO 5167-1, Measurement of fluid flow by means of pressure differential devices inserted in circular cross-section conduits running full Part 1: General principles and requirements (ISO 5167-1) EN ISO 13943, Fire safety Vocabu
42、lary (ISO 13943) ISO 5221, Air distribution and air diffusion Rules to methods of measuring air flow rate in an air handling duct 3 Terms and definitions For the purposes of this document, the terms and definitions given in EN 1363-1:2012 and EN ISO 13943 and the following apply. 3.1 fire damper dev
43、ice for use in heating, ventilation and air-conditioning (HVAC) systems at fire boundaries to maintain compartmentation and protect means of escape in case of fire Note 1 to entry: It may have reduced smoke leakage characteristics. 3.2 insulated fire damper fire damper which satisfies both the integ
44、rity and insulation criteria for the anticipated fire resistance period 3.3 uninsulated fire damper fire damper which satisfies the integrity criteria for the anticipated fire resistance period, but which does not provide a long enough insulation period to gain an EI classification BS EN 1366-2:2015
45、EN 1366-2:2015 (E) 8 3.4 cone valve fire damper fire damper consisting of a cone which closes into a profiled ring in case of fire and which normally has only one duct connection 3.5 fire damper actuating mechanism mechanism, integral or directly associated with the fire damper which, when initiated
46、 causes the damper to change from the “open“ to the “closed“ position 3.6 temperature sensing element device that senses temperature, that causes the thermal release mechanism to activate at a defined elevated temperature. 3.7 test specimen fire damper, connecting frame and (if applicable) the perim
47、eter penetration sealing system 3.8 thermal release mechanism mechanism, containing/linked to the sensing element, that causes the open damper to release and close in response to elevated temperature 3.9 connecting duct duct section between the fire damper or supporting construction and the measurin
48、g station 3.10 test construction complete assembly of the test specimen, the connecting duct and the supporting construction 3.11 measuring station equipment installed between the connecting duct and the exhaust equipment to determine the volume flow rate of gases passing through the fire damper und
49、er test 3.12 exhaust equipment equipment consisting of a fan and balancing or dilution dampers (if any), to apply and maintain the underpressure in the connecting duct 4 Test equipment 4.1 General In addition to the test equipment specified in EN 1363-1, and if applicable, EN 1363-2, the following is required. Examples of test configurations are shown in Figures 1 and 2. 4.2 Connecting duct The connecting duct shall be of all welded construction fabricated from (1,5 0,1) mm thick steel of the same size (width x height or diameter) as
copyright@ 2008-2019 麦多课文库(www.mydoc123.com)网站版权所有