1、BS EN 200:2008ICS 91.140.70NO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAWBRITISH STANDARDSanitary tapware Single taps andcombination taps forwater supply systemsof type 1 and type 2 General technicalspecificationIncorporating Corrigendum January and March 20092009 This Britis
2、h Standardwas published underthe authority of theStandards Policy andStrategy Committee on 31 BSI 2009ISBN 978 0 580 67357 3 Amendments/corrigenda issued since publicationDate CommentsBS EN 200:2008National forewordThis British Standard is the UK implementation of EN 200:2008. Itsupersedes BS EN 200
3、:1992 and BS 5412:1996, which is declared In the opinion of the UK Committee the text of this standard containserrors and these were recorded by the UK Committee at the time of theFormal Vote. Most of these errors are of an editorial nature and they donot have any technical implications. However, th
4、e omission of values forthe radius of the supply pipe before the fitting under test in Figures 13and 14 could impact upon the reproducibility of test results. In each casethe UK Committee would considers a radius of 4 times the diameter ofthe pipe to be satisfactory.The UK participation in its prepa
5、ration was entrusted to TechnicalCommittee B/504/8, Sanitary tapware.A list of organizations represented on this committee can be obtained onrequest to its secretary.This publication does not purport to include all the necessary provisionsof a contract. Users are responsible for its correct applicat
6、ion.Compliance with a British Standard cannot confer immunityfrom legal obligations.obsolescent.January 2009 31 January 2009 Correction to low resolution images31 March 2009 Correction to poor quality figures BS EN 200:2008EUROPEAN STANDARDNORME EUROPENNEEUROPISCHE NORMEN 200July 2008ICS 91.140.70 S
7、upersedes EN 200:2004 English VersionSanitary tapware - Single taps and combination taps for watersupply systems of type 1 and type 2 - General technicalspecificationRobinetterie sanitaire - Robinets simples et mlangeurspour les systmes dalimentation type 1 et type 2 -Spcifications techniques gnrale
8、sSanitrarmaturen - Auslaufventile und Mischbatterien frWasserversorgungssysteme vom Typ 1 und Typ 2 -Allgemeine technische SpezifikationThis European Standard was approved by CEN on 15 June 2008.CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions
9、for giving this EuropeanStandard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such nationalstandards may be obtained on application to the CEN Management Centre or to any CEN member.This European Standard exists in three officia
10、l versions (English, French, German). A version in any other language made by translationunder the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as theofficial versions.CEN members are the national standards bodies of Austria, Belg
11、ium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland,France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal,Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.EUROPEAN COMMITTEE FOR ST
12、ANDARDIZATIONCOMIT EUROPEN DE NORMALISATIONEUROPISCHES KOMITEE FR NORMUNGManagement Centre: rue de Stassart, 36 B-1050 Brussels 2008 CEN All rights of exploitation in any form and by any means reservedworldwide for CEN national Members.Ref. No. EN 200:2008: EBS EN 200:2008EN 200:2008 (E) 2 Contents
13、Page Foreword5 Introduction .6 1 Scope 7 2 Normative references 11 3 Designation 11 4 Marking and identification 12 5 Materials .13 6 Dimensional characteristics .14 7 Sequence of testing.24 8 Leaktightness characteristics 25 9 Pressure resistance characteristics - mechanical performance under press
14、ure.31 10 Hydraulic characteristics 33 11 Mechanical strength characteristics - torsion test for operating mechanism 36 12 Mechanical endurance characteristics37 13 Backflow protection.45 14 Acoustic characteristics .45 Annex A (informative) Pressure take-off tee.47 Bibliography 51 BS EN 200:2008EN
15、200:2008 (E) 3 Figure . Page Figure 1 - Supply system of Type 1 with a pressure range of (0,05 to 1,0) MPa (0,5 to 10) bar.9 Figure 2 - Supply system of Type 2 with a pressure range of (0,01 to 1,0) MPa (0,1 to 10) bar.10 Figure 3 - Bib taps and - Single-hole taps 16 Figure 4 - Multi-hole combinatio
16、n taps.17 Figure 5 - Supply connections for taps and remote outlets.17 Figure 6 - Pillar and bib taps20 Figure 7 - Remote outlet.21 Figure 8 - Single hole combination tap 21 Figure 9 - Bath/shower combination tap21 Figure 10 - Single hole combination tap 23 Figure 11 - Two hole combination tap (fixe
17、d centres) 23 Figure 12 - Three hole combination tap (adjustable centres) 24 Figure 13 - Apparatus for testing the leaktightness of automatic diverters for taps for supply system of Type 2 .31 Figure 14 - Flow rate test apparatus for taps for Type 2 supply systems 35 Figure 15 - Life test closing to
18、rque vs time .40 Figure 16 - Endurance test rig for divided-outlet swivel spout45 Figure A.1 - Pressure take-off tee (test rig Type 1 taps).47 Figure A.2 - Schematic examples of pressure take-off tees (test rig Type 1 taps)49 BS EN 200:2008EN 200:2008 (E) 4 Table. Page Table 1 - Conditions of use/Cl
19、assifications .8 Table 2 - Performance characteristics to be noted if used outside the recommended operating range 8 Table 3 - Designation12 Table 4 - Inlet dimensions (Pillar water supply systems of Type 2 (see Figure 2 and Table 1) with a pressure range of 0,01 MPa (0,1 bar) to 1,0 MPa (10 bar) wh
20、ich combines mains-fed and cistern-fed water supply systems. According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Cyprus, Czech Republic, Denmark, Estonia, Finland
21、, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom. BS EN 200:2008EN 200:2008 (E) 6 Introduction In respect of potential adverse effec
22、ts on the quality of water intended for human consumption, caused by the product covered by this European Standard. This European Standard provides no information as to whether the product can be used without restriction in any of the Member States of the EU or EFTA. It should be noted that, while a
23、waiting the adoption of verifiable European criteria, existing national regulations concerning the use and/or the characteristics of these products remain in force. This document identifies characteristics and technical requirements for single and combination taps. BS EN 200:2008EN 200:2008 (E) 7 1
24、Scope This European Standard specifies: a) the field of application for pillar taps, bib taps, single and multi-hole combination taps for use in: 1) a supply system of Type 1 (see Figure 1); 2) a supply system of Type 2 (see Figure 2); b) the dimensional, leaktightness, pressure resistance, hydrauli
25、c performance, mechanical strength, endurance and acoustic characteristics of nominal size and single taps and combination taps; c) test methods to verify the characteristics. The tests described in this European Standard are type tests (laboratory tests) and not quality control tests carried out du
26、ring manufacture. This European Standard applies to draw-off taps (single taps and combination taps) for use with sanitary appliances installed in rooms used for bodily hygiene (cloakrooms, bathrooms etc.) and in kitchens, i.e. for use with baths, wash basins, bidets, showers and sinks. Figure 1 sho
27、ws a supply system of Type 1 with a pressure range of (0,05 to 1,0) Mpa (0,5 to 10) bar. Figure 2 shows a supply system of Type 2 with a pressure range of (0,01 to 1,0) Mpa (0,1 to 10) bar. This European Standard applies to sanitary draw-off taps of nominal size and (PN 10). The conditions of use an
28、d classifications are given in Table 1. The Table 2 gives the performance characteristics to be noted if the tap is used outside the recommended operating range. BS EN 200:2008EN 200:2008 (E) 8 Table 1 Conditions of use/Classifications Operating range of taps Flow rate classes Acoustics Marking Wate
29、r supply system Limits Recommended See Table 13 See 14 See 4 Type 1 see Figure 1 Dynamic Pressure 0,05 Mpa (0,5 bar) Static Pressure 1,0 Mpa (10,0 bar) Dynamic Pressure (0,1 to 0,5) Mpa (1.0 to 5,0) bar see note b)Z 0,15 l/s A 0,25 l/s S 0,33 l/s B 0,42 l/s C 0,50 l/s D 0,63 l/s Group I - Group II u
30、nclassified for example IA IIC/B I /- a)II /- a)See Table 10 Type 2 see Figure 2 Dynamic Pressure 0,01 Mpa (0,1 bar) Static Pressure 1,0 Mpa (10,0 bar) Dynamic Pressure (0,02 to 0,1) MPa (0,2 to 1,0) bar see note b)X 0,125 l/s Y 0,250 l/s R d) 0,125 l/s Hot and 0,070 l/s Cold see note c)(unclassifie
31、d)X Y R Temperature 90 C25 mm or a backflow prevention device is provided in accordance with EN 1717; the D1 dimension shall be coordinated with the appropriate sanitary appliance. The manufacturers literature including the installation instructions supplied with the tapware shall indicate clearly t
32、hat the tapware is for special applications. 6.6 Flexible hoses for shower outlets Requirements for flexible hoses for shower outlets shall be as specified in EN 1113. 6.7 Shower outlets Requirements for Shower outlets shall be as specified in EN 1112. 7 Sequence of testing The samples shall be subj
33、ected to the test sequence shown in Table 7. BS EN 200:2008EN 200:2008 (E) 25 Table 7 - Test Sequence Sequence Sample 1 Sample 2 1 Dimensions (see 6) 2 Leaktightness (see 8) Flow rate (see 10) 3 Endurance (see 12) Mechanical strength (see 11) 4 Leaktightness (see 8) Leaktightness (see 8) 5 Pressure
34、resistance (see 9) NOTE Acoustic testing will require three samples which may be different from the two mentioned above. 8 Leaktightness characteristics 8.1 General This clause describes the test methods that shall be carried out to verify the leaktightness of the complete tap and specifies the corr
35、esponding requirements (see Table 8). 8.2 Test methods 8.2.1 Principle The principle of the test consists of checking under cold water pressure the leaktightness of: the obturator (see 8.3); the complete tap (see 8.4); the bath/shower diverter (either manual or with automatic return) (see 8.5, 8.6 a
36、nd 8.7). In the case of a diverter with automatic return being considered to provide backflow prevention, it shall comply with the requirements of EN 14506 8.2.2 Apparatus A hydraulic test circuit, capable of supplying the required pressures and of maintaining them throughout the duration of the tes
37、ts. A hydraulic test circuit, capable of supplying gradually the required static and dynamic pressures and of maintaining them throughout the duration of the test. 8.3 Leaktightness of the obturator and of the tap upstream of the obturator(s) with the obturator in the closed position 8.3.1 Procedure
38、 a) Connect the tap to the test circuit; b) with the outlet orifice open, and generally turned downwards, close the obturator(s) using a torque of (1,5 0,15) Nm for nominal size and (2,5 0,25) Nm for nominal size ; if a stuffing box is used to ensure leaktightness of the headwork, the packing gland
39、shall be loosened before application of the closing torque; c) apply to the inlet of the tap a water pressure of (1,6 0,05) MPa (16,0 0,5) bar and maintain it for (60 5) s. BS EN 200:2008EN 200:2008 (E) 26 8.3.2 Requirements Verification of leaktightness upstream of the obturator: throughout the dur
40、ation of the test there shall be no leakage or seepage through the walls. Verification of leaktightness of the obturator: throughout the duration of the test there shall be no leakage of the obturator, i.e. at the outlet. 8.4 Leaktightness of the tap downstream of the obturator(s) with the obturator
41、 open 8.4.1 General Not applicable when the outlet cannot be closed. 8.4.2 Procedure a) Connect the tap to the test circuit; b) if a stuffing box is used to ensure leaktightness of the headwork, ensure that the packing gland is tightened in accordance with the manufacturers instructions; c) with the
42、 outlet orifice(s) artificially closed, and generally turned downwards open the obturator(s); d) apply to the inlet of the tap a water pressure of (0,4 0,02) MPa (4,0 0,2) bar and maintain it for (60 5) s; e) gradually reduce the pressure to (0,02 0,002) MPa (0,2 0,02) bar and maintain it for (60 5)
43、 s. 8.4.3 Requirement Throughout the duration of the test there shall be no leakage, or seepage through the walls. 8.5 Leaktightness of manually operated diverter 8.5.1 Procedure: flow to bath a) Connect the tap, in its normal position of use, to the test circuit; b) put the diverter in the flow-to-
44、bath mode, the outlet to bath being artificially closed and the outlet to shower open; c) apply a static water pressure of (0,4 0,02) Mpa (4,0 0,2) bar and maintain it for (60 5) s; d) gradually reduce the pressure to (0,02 0,002) Mpa (0,2 0,02) bar and maintain it for (60 5) s; e) check for leakage
45、 at the outlet to shower. 8.5.2 Requirement: flow to bath There shall be no leakage at the outlet to shower. 8.5.3 Procedure: flow to shower a) Put the diverter in the flow-to-shower mode, the outlet to shower being artificially closed and the outlet to bath open; BS EN 200:2008EN 200:2008 (E) 27 b)
46、 apply a static water pressure of (0,4 0,02) Mpa (4,0 0,2) bar and maintain it for (60 5) s; c) gradually reduce the pressure to (0,02 0,002) Mpa (0,2 0,02) bar and maintain it for (60 5) s; d) check for leakage at the outlet to bath. 8.5.4 Requirement: flow to shower There shall be no leakage at th
47、e outlet to bath. 8.6 Leaktightness and operation of diverter with automatic return: Taps for supply system of Type 1 8.6.1 Procedure: flow to bath a) Connect the tap, in its normal position of use, to the test circuit; b) connect the hydraulic resistance corresponding to the flow rate class marking
48、 see EN ISO 3822-4 to the shower outlet (for example: for marking A, class A resistance will be used during testing); c) put the diverter in the flow-to-bath mode with the outlets to bath and shower open; d) apply a dynamic pressure of (0,4 0,02) Mpa (4,0 0,2) bar and maintain it for (60 5) s; e) ch
49、eck for leakage at the outlet to shower. 8.6.2 Requirement: flow to bath There shall be no leakage at the outlet to shower. 8.6.3 Procedure: flow to shower a) Put the diverter in the flow-to-shower mode with the outlets to bath and shower open; b) apply a dynamic pressure of (0,4 0,02) Mpa (4,0 0,2) bar and maintain it for (60 5) s; c) check for leakage at the outlet to bath; d) gradually reduce the pressure