1、BS EN 378-3:2016Refrigerating systems and heat pumps Safety and environmental requirementsPart 3: Installation site and personal protectionBSI Standards PublicationWB11885_BSI_StandardCovs_2013_AW.indd 1 15/05/2013 15:06BS EN 378-3:2016 BRITISH STANDARDNational forewordThis British Standard is the U
2、K implementation of EN 378-3:2016.It supersedes BS EN 378-3:2008+A1:2012 which is withdrawn.The UK participation in its preparation was entrusted to Technical Committee RHE/18, Refrigeration safety.A list of organizations represented on this committee can be obtained on request to its secretary.This
3、 publication does not purport to include all the necessary provisions of a contract. Users are responsible for its correct application. The British Standards Institution 2016.Published by BSI Standards Limited 2016ISBN 978 0 580 84662 5 ICS 27.080; 27.200 Compliance with a British Standard cannot co
4、nfer immunity from legal obligations.This British Standard was published under the authority of the Standards Policy and Strategy Committee on 31 December 2016.Amendments/corrigenda issued since publicationDate T e x t a f f e c t e dBS EN 378-3:2016EUROPEAN STANDARD NORME EUROPENNE EUROPISCHE NORM
5、EN 378-3 November 2016 ICS 27.080; 27.200 Supersedes EN 378-3:2008+A1:2012English Version Refrigerating systems and heat pumps - Safety and environmental requirements - Part 3: Installation site and personal protection Systmes frigorifiques et pompes chaleur - Exigences de scurit et denvironnement -
6、 Partie 3: Installation in situ et protection des personnes Klteanlagen und Wrmepumpen - Sicherheitstechnische und umweltrelevante Anforderungen - Teil 3: Aufstellungsort und Schutz von Personen This European Standard was approved by CEN on 3 September 2016. CEN members are bound to comply with the
7、CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC Management
8、Centre or to any CEN member. This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same status as
9、 the official versions. CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Net
10、herlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey andUnited Kingdom. EUROPEAN COMMITTEE FOR STANDARDIZATION COMIT EUROPEN DE NORMALISATION EUROPISCHES KOMITEE FR NORMUNG CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels 2016 CEN All ri
11、ghts of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 378-3:2016 EBS EN 378-3:2016EN 378-3:2016 (E) 2 Contents Page European foreword . 5 Introduction 6 1 Scope 7 2 Normative references 7 3 Terms, definitions and abbreviated terms 8 4 Location of
12、refrigerating equipment 8 4.1 General 8 4.2 Refrigerating equipment located in the open air 8 4.3 Refrigerating equipment located in a machinery room 9 4.4 Refrigerating equipment located in the occupied space 9 4.5 Refrigerating equipment located in an unoccupied space not designated a machinery ro
13、om 9 4.6 Refrigerating equipment located in a ventilated enclosure within an occupied space 10 4.7 Piping duct or shaft . 10 5 Machinery rooms . 10 5.1 Access to machinery rooms 10 5.2 Venting from or through the machinery room 10 5.3 Combustion equipment and air compressors 10 5.4 Open flame 10 5.5
14、 Storage . 10 5.6 Remote emergency switch 11 5.7 Exterior openings of the machinery room 11 5.8 Piping and ducting . 11 5.9 Normal lighting . 11 5.10 Emergency lighting 11 5.11 Dimensions and accessibility . 11 5.12 Doors, walls and ducts 12 5.12.1 Doors and openings . 12 5.12.2 Emergency 12 5.12.3
15、Walls, floor and ceiling . 12 5.12.4 Service ducts 12 5.12.5 Ventilation ducts 12 5.13 Ventilation 12 5.13.1 General . 12 5.13.2 Ventilation for normal operating conditions or when machinery room is occupied 13 5.13.3 Emergency mechanical ventilation . 13 5.13.4 Required airflow for emergency mechan
16、ical ventilation 13 5.13.5 Mechanical ventilation openings 13 5.14 Machinery rooms for groups A2L, A2, A3, B2L, B2 and B3 refrigerants . 13 5.14.1 General . 13 5.14.2 Location . 13 5.14.3 Additional requirements for R-717 . 14 5.14.4 Maximum surface temperature 15 5.14.5 Doors and openings . 15 BS E
17、N 378-3:2016EN 378-3:2016 (E) 3 6 Requirements for alternative provisions 15 6.1 General . 15 6.2 Occupied space 15 6.3 Ventilation . 15 6.3.1 General . 15 6.3.2 Dilution transfer openings (air transfer openings for dilution) for natural convection . 15 6.3.3 Mechanical ventilation . 16 6.4 Safety s
18、hut off valves . 17 6.4.1 General . 17 6.4.2 Location 17 6.4.3 Design . 17 7 Electrical installations 17 7.1 General requirements . 17 7.2 Main power supply . 18 7.3 Electrical equipment in machinery rooms with refrigerating systems containing flammable refrigerants 18 8 Safety alarms 18 8.1 General
19、 . 18 8.2 Alarm system power 18 8.3 Alarm system warning 18 8.4 Additional alarm system requirements for R-717 systems with charges above 3 000 kg 18 9 Detectors 19 9.1 General . 19 9.2 Location of detectors . 19 9.3 Type and performance of detectors . 19 9.3.1 General . 19 9.3.2 Refrigerant detecto
20、rs for A2, A2L, B2L (except for R-717), B2, A3 and B3 refrigerants 19 9.3.3 R-717 detectors . 20 9.4 Installation 20 10 Instruction manuals, notices and inspections 20 10.1 Instruction manual. 20 10.2 Warning notice 21 10.3 Visual inspection of the site 21 10.4 Maintenance of the site . 21 11 Heat s
21、ources and temporary high temperatures at the site . 21 Anhang A (informative) Personal protective equipment 23 A.1 General requirements . 23 A.1.1 Type of protective equipment 23 A.1.2 Accessibility 23 A.1.3 Location 23 A.1.4 Check and maintenance . 23 A.1.5 Temperature 23 A.1.6 Respirators 23 A.2
22、Normal use 24 BS EN 378-3:2016EN 378-3:2016 (E) 4 A.3 Emergency use 24 A.3.1 General . 24 A.3.2 Respiratory protective devices . 24 A.3.3 First aid equipment . 24 Bibliography . 25 BS EN 378-3:2016EN 378-3:2016 (E) 5 European foreword This document (EN 378-3:2016) has been prepared by Technical Comm
23、ittee CEN/TC 182 “Refrigerating systems, safety and environmental requirements”, the secretariat of which is held by DIN. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by May 2017, and conflicting
24、national standards shall be withdrawn at the latest by May 2017. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN and/or CENELEC shall not be held responsible for identifying any or all such patent rights. This document superse
25、des EN 378-3:2008+A1:2012. EN 378 consists of the following parts under the general title “Refrigerating systems and heat pumps Safety and environmental requirements”: Part 1: Basic requirements, definitions, classification and selection criteria; Part 2: Design, construction, testing, marking and d
26、ocumentation; Part 3: Installation site and personal protection; Part 4: Operation, maintenance, repair and recovery. The main changes in part 3 with respect to the previous edition are listed below: harmonisation as far as possible with ISO 5149:2014 and ISO 817:2014; clarification of when to use o
27、f special machinery room, and modify to “separate refrigeration machinery room”; consideration of requirements for 2L refrigerants; inclusion of Clause 6 additional measures to support EN 378-1:2016, C.3; modification of requirements for sprinkler systems. According to the CEN/CENELEC Internal Regul
28、ations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, It
29、aly, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom. BS EN 378-3:2016EN 378-3:2016 (E) 6 Introduction The introduction of EN 378-1 is applicable. BS EN 378-3:2016EN 378-3:2016 (E) 7 1
30、 Scope This European Standard specifies the requirements for the safety of persons and property, provides guidance for the protection of the environment and establishes procedures for the operation, maintenance and repair of refrigerating systems and the recovery of refrigerants. The term “refrigera
31、ting system” used in this European Standard includes heat pumps. This Part 3 of the European Standard is applicable to the installation site (plant space and services). It specifies requirements on the site for safety, which may be needed because of, but not directly connected with, the refrigeratin
32、g system and its ancillary components. This standard applies: a) to refrigerating systems, stationary or mobile, of all sizes except to vehicle air conditioning systems covered by a specific product standard e.g. ISO 13043; b) to secondary cooling or heating systems; c) to the location of the refrig
33、erating systems; d) to replaced parts and added components after adoption of this standard if they are not identical in function and in the capacity. Systems using refrigerants other than those listed in of EN 378-1:2016, Annex E are not covered by this standard. This standard does not apply to good
34、s in storage. This standard is not applicable to refrigerating systems which were manufactured before the date of its publication as a European Standard except for extensions and modifications to the system which were implemented after publication. This standard is applicable to new refrigerating sy
35、stems, extensions or modifications of already existing systems, and for existing stationary systems, being transferred to and operated on another site. This standard also applies in the case of the conversion of a system for another refrigerant type, in which case conformity with the relevant clause
36、s of parts 1 to 4 of the standard shall be assessed. 2 Normative references The following documents, in whole or in part, are normatively referenced in this document and are indispensable for its application. For dated references, only the edition cited applies. For undated references, the latest ed
37、ition of the referenced document (including any amendments) applies. EN 378-1:2016, Refrigerating systems and heat pumps Safety and environmental requirements Part 1: Basic requirements, definitions, classification and selection criteria EN 378-2:2016, Refrigerating systems and heat pumps Safety and
38、 environmental requirements Part 2: Design, construction, testing, marking and documentation EN 1363 (all parts), Fire resistance tests EN 1364 (all parts), Fire resistance tests for non-load bearing elements EN 1365 (all parts), Fire resistance tests for load bearing elements EN 1366-1, Fire resist
39、ance tests for service installations Part 1: Ventilation ducts BS EN 378-3:2016EN 378-3:2016 (E) 8 EN 1366-2, Fire resistance tests for service installations Part 2: Fire dampers EN 1507, Ventilation for buildings Sheet metal air ducts with rectangular section Requirements for strength and leakage E
40、N 1634 (all parts), Fire resistance and smoke control tests for door and shutter assemblies, openable windows and elements of building hardware EN 12236, Ventilation for buildings Ductwork hangers and supports Requirements for strength EN 12845, Fixed firefighting systems Automatic sprinkler systems
41、 Design, installation and maintenance EN 14624, Performance of portable leak detectors and of room monitors for halogenated refrigerants EN 60079-10-1, Explosive atmospheres Part 10-1: Classification of areas Explosive gas atmospheres (IEC 60079-10-1) EN 60204-1:2006, Safety of machinery Electrical
42、equipment of machines Part 1: General requirements (IEC 60204-1:2005) EN 60529, Degrees of protection provided by enclosures (IP Code) (IEC 60529) EN ISO 13850, Safety of machinery Emergency stop function Principles for design (ISO 13850) EN ISO 14122-2, Safety of machinery Permanent means of access
43、 to machinery Part 2: Working platforms and walkways (ISO 14122-2) ISO 13043, Road vehicles Refrigerant systems used in mobile air conditioning systems (MAC) Safety requirements ISO 817, Refrigerants Designation and safety classification IEC 60364, Low-voltage electrical installations 3 Terms, defin
44、itions and abbreviated terms For the purposes of this document, the terms, definitions and abbreviated terms given in EN 378-1:2016 apply. 4 Location of refrigerating equipment 4.1 General Refrigerating equipment may be sited outside the building in the open air or in a machinery room or in occupied
45、 areas or in unoccupied areas not designated as a machinery room. NOTE The refrigerating equipment can be contained in a ventilated enclosure provided by the manufacturer. Requirements for this enclosure are given in EN 3782:2016, 6.2.15. 4.2 Refrigerating equipment located in the open air Refrigera
46、ting systems sited in the open air shall be positioned to avoid leaked refrigerant flowing into a building or otherwise endangering people and property. The refrigerant shall not be able to flow into any ventilation fresh air opening, doorway, trap door or similar opening in the event of a leak. Whe
47、re a BS EN 378-3:2016EN 378-3:2016 (E) 9 shelter is provided for refrigerating equipment sited in the open air it shall have natural or forced ventilation. A room, where at least one of the longer walls is open to the outside air by means of louvres with 75 % free area and covering at least 80 % of
48、the wall area (or the equivalent if more than one wall is to outside), is considered as being in the open air. For refrigeration systems installed outside in a location where a release of refrigerant can stagnate e.g. below ground, then the installation shall comply with the requirements for gas det
49、ection and ventilation of machinery rooms (see 5.13, Clauses 8 and 9). For refrigerants of class 2L, 2 and 3 requirements regarding ignition sources in EN 378-2:2016, 6.2.14 shall apply where appropriate. 4.3 Refrigerating equipment located in a machinery room When a machinery room is chosen for the location of the refrigerating equipment it shall meet the requirements specified in 5.1 to 5.14. A risk analysis based on the safety concept for the refrigerating system (as determined by the manufacturer an