1、raising standards worldwideNO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAWBSI Standards PublicationBS EN 50181:2010Plug-in type bushings above 1kV up to 52 kV and from 250 Ato 2,50 kA for equipment otherthan liquid filled transformersBS EN 50181:2010 BRITISH STANDARDNational f
2、orewordThis British Standard is the UK implementation of EN 50181:2010. Itsupersedes BS EN 50181:1999 which is withdrawn.The UK participation in its preparation was entrusted to TechnicalCommittee PEL/36, Insulators for power systems.A list of organizations represented on this committee can beobtain
3、ed on request to its secretary.This publication does not purport to include all the necessaryprovisions of a contract. Users are responsible for its correctapplication. BSI 2010ISBN 978 0 580 69499 8ICS 29.080.20Compliance with a British Standard cannot confer immunity fromlegal obligations.This Bri
4、tish Standard was published under the authority of theStandards Policy and Strategy Committee on 31 August 2010.Amendments issued since publicationDate Text affectedBS EN 50181:2010EUROPEAN STANDARD EN 50181 NORME EUROPENNE EUROPISCHE NORM July 2010 CENELEC European Committee for Electrotechnical St
5、andardization Comit Europen de Normalisation Electrotechnique Europisches Komitee fr Elektrotechnische Normung Management Centre: Avenue Marnix 17, B - 1000 Brussels 2010 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members. Ref. No. EN 50181:2010
6、E ICS 29.080.20 Supersedes EN 50181:1997English version Plug-in type bushings above 1 kV up to 52 kV and from 250 A to 2,50 kA for equipment other than liquid filled transformers Traverses embrochables de tensions suprieures 1 kV jusqu 52 kV et de 250 A 2,50 kA pour quipements autres que transformat
7、eurs remplissage de liquide Steckbare Durchfhrungen ber 1 kV bis 52 kV und von 250 A bis 2,50 kA fr Anlagen anders als flssigkeitsgefllte Transformatoren This European Standard was approved by CENELEC on 2010-07-01. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which
8、stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the Central Secretariat or to any CENELEC member. This European St
9、andard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CENELEC member into its own language and notified to the Central Secretariat has the same status as the official versions. CENELEC members are the nat
10、ional electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Sp
11、ain, Sweden, Switzerland and the United Kingdom. BS EN 50181:2010EN 50181:2010 2 Foreword This European Standard was prepared by the Technical Committee CENELEC TC 36A, Insulated bushings. It was submitted to the Unique Acceptance Procedure and was approved by CENELEC as EN 50181 on 2010-07-01. This
12、 document supersedes EN 50181:1997. The main technical changes on the Plug-in type bushings are: Enlarge the scope of the voltage class from the plug-in bushings from 36 kV to 52 kV; Upgrading the current capacity of the existing defined bushings; Introduce a new bushing interface for 52 kV. Attenti
13、on is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN and CENELEC shall not be held responsible for identifying any or all such patent rights. The following dates were fixed: latest date by which the EN has to be implemented at national le
14、vel by publication of an identical national standard or by endorsement (dop) 2011-07-01 latest date by which the national standards conflicting with the EN have to be withdrawn (dow) 2013-07-01 _ BS EN 50181:2010 3 EN 50181:2010 Contents Introduction 41 Scope 42 Normative references 43 Definitions 4
15、4 Requirements . 54.1 Application . 54.2 Standard values of maximum voltage (Um) . 54.3 Standard values of rated current (Ir ) 54.4 Compliance . 54.5 Bushing mounting distance . 54.6 Detail dimensions of plug-in type bushings . 5Figures Figure 1 - Interface dimensions of outside cone plug-in type bu
16、shings 6 Figure 2 - Bushing details of outside cone plug-in type bushings . 7 Figure 3 - Outer dimensions of inside cone plug-in type bushings . 9 Figure 4 - Interface details of inside cone plug-in type bushings 10 Tables Table 1 - Interface dimensions 6Table 2 - Bushing dimensions . 8Table 3 - Bus
17、hing dimensions . 9Table 4 - Interface dimensions 11BS EN 50181:2010EN 50181:2010 4 Introduction The object of this European Standard is to specify the requirements to ensure interchangeability of bushings for maximum voltages above 1 kV up to 52 kV and rated currents from 250 A to 2 500 A for equip
18、ment other than insulating liquid filled transformers. 1 Scope This European Standard is applicable to insulated bushings for maximum voltages above 1 kV up to 52 kV, rated currents from 250 A up to 2 500 A and frequencies from 15 Hz up to 60 Hz for equipment other than liquid filled transformers. T
19、his European Standard establishes essential dimensions, to ensure adequate mounting and interchangeability of mating plug-in separable connectors of equivalent ratings. 2 Normative references The following referenced documents are indispensable for the application of this document. For dated referen
20、ces, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 60137, Insulated bushings for alternating voltages above 1 000 V IEC Guide 109 and Cenelec TC 111X document 1), Environmental aspects Inclusion in electro
21、technical product standards NOTE It is highly recommended to minimize the impact of bushings on the environment during all phases of their life (including manufacturing, operation during service life, dismantling after their end of life and disposal or recycling). IEC Guide109 and document by CENELE
22、C TC 111X, Environmental standardization for electrical and electronic products and systems after finalization can be used as helpful reference. 3 Terms and definitions For the purposes of this document, the following terms and definitions apply. 3.1 plug in type bushing bushing one end of which is
23、immersed in an insulating medium which has customized dimensions according to insulation requirements for the specific application and the other end designed to receive a separable insulated cable connector without which the bushing cannot function 3.2 separable connector fully insulated termination
24、 permitting the connection and disconnection of the cable to and from the mating plug-in type bushing 3.3 interface type bushing dimensions that insure mechanical and electrical interchangeability of bushing and separable connector of similar rating and type NOTE Each interface type is designed by a
25、 letter or a number. 3.4 bail holder fixture which facilitates anchoring of an externally mounted device (called the bail) designed to prevent undesirable separation of a separable connector and a bushing 1)Under development. BS EN 50181:2010 5 EN 50181:2010 NOTE A bail holder may or may not be an i
26、ntegral part of a bushing and is an optional feature. 4 Requirements 4.1 Application Bushings covered by this European Standard shall be suitable for operation with one end connected to a separable connector and the other end having customized dimensions according to the insulation requirements for
27、the specific application. 4.2 Standard values of maximum voltage (Um) The value of Umof a bushing shall be chosen from the standard values of the highest voltage for equipment, defined in IEC 60038 as given below in kilovolt: 12 24 36 52 4.3 Standard values of rated current (Ir) The value Ir of a bu
28、shing shall be chosen from the standard values given below in ampere: 250 - 400 - 630 - 800 - 1 250 - 1 600 - 2 000 - 2 500 4.4 Compliance Bushings which are supplied separately shall meet the requirements of EN 60137. Customized bushings which are integrated directly in the equipment shall comply w
29、ith the test requirements specified in the standard(s) relevant to that type of equipment. 4.5 Bushing mounting distance The minimum distance between bushings shall take into account the outer dimensions of separable connectors and the optional bail holders. 4.6 Detail dimensions of plug-in type bus
30、hings 4.6.1 General The dimensions necessary to ensure adequate mounting and interchangeability of mating plug-in separable connectors shall be as specified in the following Figures and Tables. 4.6.2 Outside cone type The dimensions necessary for outside cone plug-in type bushings are specified in F
31、igures 1 and 2 and in Tables 1 and 2. BS EN 50181:2010EN 50181:2010 6 Figure 1 - Interface dimensions of outside cone plug-in type bushings Table 1 - Interface dimensions UmIrd1d2o-2d3o-2d4max./1 max. /2/3 min.Contact type Interfacetype FigurekV A mm mm mm mm mm mm mm 12-24 250 31 +0.1 - 0.3 32,5 48
32、,5 132 205 48 0-0,29 Sliding A 1a) 12-24-36 250 - 400 46 0.2 56 70 137 205 90 0.2 11 Sliding B 1a) 12-24-36 630-1 250 46 0.2 56 70 137 205 90 0.2 11 Bolted C 1a) 12-24 800-1 250 39,9 0.2 52,1 76,2 137 205 81 0.2 14,8 Bolted D 1a) 36 39,9 0.2 61,5 76,2 165 240 103,7 0.2 21 Bolted E 1a) 12-24-36 630-1
33、 250 2 500 64 0.2 86,8 165 240 110,5 0.2 Bolted F 1b) 12-24-36-52 630-1 250 NOTE The envelope /1x d4represents the section of the plug-in type bushing inside the equipment. When bushings are an integral functional part of an equipment, the values /1and d4may differ from the table and shall be define
34、d by the equipment manufacturer. a) b) BS EN 50181:2010 7 EN 50181:2010 Interface type: A to E Interface type: F Figure 2 - Bushing details of outside cone plug-in type bushings BS EN 50181:2010EN 50181:2010 8 Table 2 - Bushing dimensions UmIrBushing contact RadiusBail holder Type 1 or 2 Interfacean
35、d bushing type Type Materiala d5 nominal d6Thread l4l5l6r1r2Locationd 7 0,5 Required number d8 Type 2 l7 2 l8l16 1 kV A min. min. max. max max. min. min. mm mm mm mm mm mm mm mm mm mm mm 12-24 250 Sliding Cu - +0,02 7,9 -0,05 - 32 30 54 1 2x 45 90 2 M6 3,5 8 2 A1 12-24-36 250 Sliding Cu - +0 14 -0,0
36、4 - 40 38 97 3 3 102 2 M8 5,5 10 2 B1 12-24-36 400 Sliding Cu - +0 14 -0,04 - 40 38 97 3 3 102 2 M8 5,5 10 2 B2 12-24-36 630 Bolted Cu 22 min. - M 16 29 - 97 3 3 b 102 b2 bM8 - 10 - C1 12-24-36 1 250 Bolted Cu 32 - M 16 29 - 97 3 3 b102 b2 bM8 - 10 - C2 12-24 800 Bolted Cu or Al 32 - M 16 29 88 3 3
37、b102 b2 bM8 - 10 - D1 36 111 E1 12-24 1 250 Bolted Cu 32 - M 16 29 - 88 3 3 b123 b2 bM8 - 10 - D2 36 111E2 12-24-36 2 500 Bolted Cu 50 - M 16 29 - 94 3 - - - - - - - F1 12-24-36-52 630 Bolted Cu 22 min. - M 16 29 - 94 3 - - - - - - - F2 12-24-36-52 1 250 Bolted Cu 32 - M 16 29 - 94 3 - - - - - - - F
38、3 aIn the connection of separable connectors to bushings, care must be taken in the matching of the materials of the cable conductors, the cable lugs and the bushing conductors. Where dissimilar metals are joined, appropriate precautions shall be taken. Where aluminium bushing conductors are used an
39、d screw threads are required, a suitable grade of aluminium or aluminium alloy shall be used. b Bail holder is optional. BS EN 50181:2010 9 EN 50181:2010 4.6.3 Inside cone type The dimensions necessary for inside cone plug-in type bushings are specified in Figures 3 and 4 and in Tables 3 and 4. Figu
40、re 3 - Outer dimensions of inside cone plug-in type bushings Table 3 - Bushing dimensions UmkV Ir A d4 max. l1 max. Interface type mm mm 12-24 250 132 205 0 12-24-36 400 - 630 137 205 1 12-24-36 800 137 205 2 12-24-36-52 1 250 185 240 3 NOTE The envelope l1x d4represents the section of the plug-in t
41、ype bushing inside the equipment. When bushings are an integral functional part of an equipment, the values l1and d4may differ from the table and shall be defined by the equipment manufacturer. BS EN 50181:2010EN 50181:2010 10 Figure 4 - Interface details of inside cone plug-in type bushings BS EN 5
42、0181:2010 11 EN 50181:2010 Table 4 - Interface dimensions UmIrd10d11d12 0,4 d13 0,4 d14 + 0,10 d15d16d17l10 1,3l11 l12 0,2l13l14 + 2 - 1 l15 + 5 0 l17Contacttype InterfaceType kV A max. min. min. mm mm mm mm mm mm mm mm mm mm mm mm mm mm mm 12-24 250 min 69 max 62 53,2 47,5 a88 108 59,5 83 44 59+ 12
43、0 014 23 + 1 1 -0,5 Sliding 0 12-24-36 400 630 min 79 max 72 59,8 54 36 95 115 63,5 83 46,5 59+ 120 014 23 0 Sliding 1 12-24-36 800 min 86 max 79 65,8 60 39 102 122 69,5 83 46,5 59+ 120 014 23 0 Sliding 2 12-24-36-52 1 250 0 115 -18 0 95 -187,8 79,7 55 130 150 92,5 110 82 81+1,524 019 32 0 Sliding 3
44、 aThe female part has to be designed according to the requirements of the separable connector contact pin detail. This page deliberately left blankThis page deliberately left blankBSI is the independent national body responsible for preparing British Standardsand other standards-related publications
45、, information and services. It presents the UK view on standards in Europe and at the international level. It is incorporated by Royal Charter.British Standards Institution (BSI)raising standards worldwideBSI Group Headquarters389 Chiswick High Road London W4 4AL UKTel +44 (0)20 8996 9001Fax +44 (0)
46、20 8996 Standards are updated by amendment or revision. Users of British Stan-dards should make sure that they possess the latest amendments or editions.It is the constant aim of BSI to improve the quality of our products and serv-ices. We would be grateful if anyone finding an inaccuracy or ambigu
47、ity whileusing this British Standard would inform the Secretary of the technical com-mittee responsible, the identity of which can be found on the inside frontcover.Tel: +44 (0)20 8996 9001 Fax: +44 (0)20 8996 7001BSI offers Members an individual updating service called PLUS which ensuresthat subscr
48、ibers automatically receive the latest editions of standards.Tel: +44 (0)20 8996 7669 Fax: +44 (0)20 8996 7001Email: Buying standardsYou may buy PDF and hard copy versions of standards directly using acredit card from the BSI Shop on the website addition all orders for BSI, international and foreign standards publicationscan be addressed to BSI Customer Services.Tel: +44 (0)20 8996 9001 Fax: +44 (0)20 8996 7001Email: In response to orders for international standards, it is BSI policy tosupply the BSI implementation of those that have been publishedas British Standards, unless otherwise