1、BS EN 50600-4-1:2016Information technology Data centre facilities andinfrastructuresPart 4-1: Overview of and generalrequirements for key performanceindicatorsBSI Standards PublicationWB11885_BSI_StandardCovs_2013_AW.indd 1 15/05/2013 15:06BS EN 50600-4-1:2016 BRITISH STANDARDNational forewordThis B
2、ritish Standard is the UK implementation of EN 50600-4-1:2016. The UK participation in its preparation was entrusted to Technical Committee TCT/7, Telecommunications - Installation requirements.A list of organizations represented on this committee can be obtained on request to its secretary.This pub
3、lication does not purport to include all the necessary provisions of a contract. Users are responsible for its correct application. The British Standards Institution 2017.Published by BSI Standards Limited 2017ISBN 978 0 580 93731 6 ICS 35.020; 35.110; 35.160 Compliance with a British Standard canno
4、t confer immunity from legal obligations.This British Standard was published under the authority of the Standards Policy and Strategy Committee on 31 January 2017.Amendments/corrigenda issued since publicationDate T e x t a f f e c t e dBS EN 50600-4-1:2016EUROPEAN STANDARD NORME EUROPENNE EUROPISCH
5、E NORM EN 50600-4-1 December 2016 ICS 35.020; 35.110; 35.160 English Version Information technology - Data centre facilities and infrastructures - Part 4-1: Overview of and general requirements for key performance indicators Technologie de linformation - Installation et infrastructures de centres de
6、 traitement de donnes - Partie 4-1 : Vue densemble et exigences gnrales relatives aux indicateurs-cls de performance Informationstechnik - Einrichtungen und Infrastrukturen von Rechenzentren - Teil 4-1: berblick ber und allgemeine Anforderungen an Leistungskennzahlen This European Standard was appro
7、ved by CENELEC on 2016-10-10. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such natio
8、nal standards may be obtained on application to the CEN-CENELEC Management Centre or to any CENELEC member. This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CENELEC member into its ow
9、n language and notified to the CEN-CENELEC Management Centre has the same status as the official versions. CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia
10、, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom. European Committee for Electrotechnical Standardization Comit Europen
11、de Normalisation Electrotechnique Europisches Komitee fr Elektrotechnische Normung CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels 2016 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members. Ref. No. EN 50600-4-1:2016 E BS EN 50600-4-
12、1:2016EN 50600-4-1:2016 2 Contents PageEuropean foreword . 4 Introduction . 5 1 Scope . 8 2 Normative references 8 3 Terms, definitions and abbreviations 8 3.1 Terms and definitions 8 3.2 Abbreviations . 9 4 Conformance 9 5 Key Performance Indicators (KPIs) 9 5.1 General 9 5.2 Common Objectives for
13、KPIs 10 5.3 Requirements for KPIs 10 5.3.1 General . 10 5.3.2 Scale . 10 5.3.3 Evolution 10 5.3.4 Formulae 10 5.3.5 Definition of boundaries . 10 5.3.6 Reporting . 11 5.3.7 Definition of terms 11 5.3.8 Measurement points and procedures . 11 5.3.9 Requirements 11 5.3.10 Classifications . 11 5.4 Eleme
14、nts addressed in the standards within the EN 50600-4-X series 11 5.5 Use of KPIs . 12 6 Data Centre Boundaries 12 6.1 General 12 6.2 Spatial and logical boundaries . 12 7 Data Centre spaces and equipment . 12 7.1 Data Centre spaces 12 7.2 Data centre equipment (logical boundaries) . 13 7.2.1 IT and
15、network telecommunications/infrastructure 13 7.2.2 Power distribution infrastructure 13 7.2.3 Environmental control/infrastructure . 13 7.2.4 Security and safety infrastructure . 13 Annex A (informative) KPI constraints and data centre criticality . 14 BS EN 50600-4-1:2016EN 50600-4-1:2016 3 A.1 Gen
16、eral 14 A.2 Data centre availability objectives 14 A.3 Data centre location . 14 Bibliography 15 Figures Figure 1 Schematic relationship between the EN 50600 series of documents . 6 BS EN 50600-4-1:2016EN 50600-4-1:2016 4 European foreword This document (EN 50600-4-1:2016) has been prepared by CLC/T
17、C 215 “Electrotechnical aspects of telecommunication equipment”. The following dates are fixed: Latest date by which this documenthas to be implemented at national level by publication of an identical national standard or by endorsement (dop) 2017-07-10 Latest date by which the nationalstandards con
18、flicting with this document have to be withdrawn (dow) 2019-10-10 This document has been prepared under a mandate given to CENELEC by the European Commission and the European Free Trade Association. Attention is drawn to the possibility that some of the elements of this document may be the subject o
19、f patent rights. CENELEC shall not be held responsible for identifying any or all such patent rights. Regarding the various parts in the EN 50600 series, see the Introduction. BS EN 50600-4-1:2016EN 50600-4-1:2016 5 Introduction The unrestricted access to internet-based information demanded by the i
20、nformation society has led to an exponential growth of both internet traffic and the volume of stored/retrieved data. Data centres are housing and supporting the information technology and network telecommunications equipment for data processing, data storage and data transport. They are required bo
21、th by network operators (delivering those services to customer premises) and by enterprises within those customer premises. Data centres need to provide modular, scalable and flexible facilities and infrastructures to easily accommodate the rapidly changing requirements of the market. In addition, e
22、nergy consumption of data centres has become critical both from an environmental point of view (reduction of carbon footprint) and with respect to economic considerations (cost of energy) for the data centre operator. The implementation of data centres varies in terms of: a) purpose (enterprise, co-
23、location, co-hosting, or network operator facilities);b) security level;c) physical size;d) accommodation (mobile, temporary and permanent constructions).The needs of data centres also vary in terms of availability of service, the provision of security and the objectives for energy efficiency. These
24、 needs and objectives influence the design of data centres in terms of building construction, power distribution, environmental control and physical security. Effective management and operational information is required to monitor achievement of the defined needs and objectives. This series of Europ
25、ean Standards specifies requirements and recommendations to support the various parties involved in the design, planning, procurement, integration, installation, operation and maintenance of facilities and infrastructures within data centres. These parties include: 1) owners, facility managers, ICT
26、managers, project managers, main contractors;2) architects, consultants, building designers and builders, system and installation designers;3) facility and infrastructure integrators, suppliers of equipment;4) installers, maintainers.At the time of publication of this European Standard, the EN 50600
27、 series will comprise the following standards and documents: EN 50600-1, Information technology Data centre facilities and infrastructures Part 1: General concepts; EN 50600-2-1, Information technology Data centre facilities and infrastructures Part 2-1: Building construction; EN 50600-2-2, Informat
28、ion technology Data centre facilities and infrastructures Part 2-2: Power distribution; EN 50600-2-3, Information technology Data centre facilities and infrastructures Part 2-3: Environmental control; EN 50600-2-4, Information technology Data centre facilities and infrastructures Part 2-4: Telecommu
29、nications cabling infrastructure; BS EN 50600-4-1:2016EN 50600-4-1:2016 6 EN 50600-2-5, Information technology Data centre facilities and infrastructures Part 2-5: Security systems; EN 50600-3-1, Information technology Data centre facilities and infrastructures Part 3-1: Management and operational i
30、nformation; EN 50600-4-1, Information technology Data centre facilities and infrastructures Part 4-1: Overview of and general requirements for key performance indicators; EN 50600-4-2, Information technology Data centre facilities and infrastructures Part 4-2: Power Usage Effectiveness; EN 50600-4-3
31、, Information technology Data centre facilities and infrastructures Part 4-3: Renewable Energy Factor; CLC/TR 50600-99-1, Information technology Data centre facilities and infrastructures Part 99-1: Recommended practices for energy management. The inter-relationship of the standards within the EN 50
32、600 series is shown in Figure 1. Figure 1 Schematic relationship between the EN 50600 series of documents EN 50600-2-X standards specify requirements and recommendations for particular facilities and infrastructures to support the relevant classification for “availability”, “physical security” and “
33、energy efficiency enablement” selected from EN 50600-1. EN 50600-3-X documents specify requirements and recommendations for data centre operations, processes and management. EN 50600-4-X documents specify requirements and recommendations for key performance indicators (KPIs) used to assess and impro
34、ve the resource usage efficiency and effectiveness, respectively, of a data centre. In todays digital society data centre growth, and power consumption in particular, is an inevitable consequence and that growth will demand increasing power consumption despite the most stringent energy efficiency st
35、rategies. This makes the need for key performance indicators that cover the effective use of resources (including but not limited to energy) and the reduction of CO2emissions essential. BS EN 50600-4-1:2016EN 50600-4-1:2016 7 NOTE Within the EN 506004 series, the term “resource usage effectiveness”
36、is more generally used for KPIs in preference to “resource usage efficiency”, which is restricted to situations where the input and output parameters used to define the KPI have the same units. In order to enable the optimum resource effectiveness of data centres a suite of effective KPIs is needed
37、to measure and report on resources consumed in order to develop an improvement roadmap. These standards are intended to accelerate the provision of operational infrastructures with improved resource usage effectiveness. This European Standard provides an overview of and defines general requirements
38、for key performance indicators specified in the EN 50600-4 series. The common objective of the KPIs is the effective or efficient use of resources, for example: the minimization of energy and other resource (e.g. water) consumption; task effectiveness of the IT load (data processing, storage and tra
39、nsport) within the data centre,maximizing the IT output with the minimum energy consumption; energy reuse in the form of waste heat, if possible; the use of renewable energy, both generated on site and off site.Additional standards in the EN 50600-4 series will be developed, each describing a specif
40、ic KPI for resource usage effectiveness or efficiency. The EN 50600-4 series does not specify limits or targets for any KPI and does not describe or imply, unless specifically stated, any form of aggregation of individual KPIs into a combined nor an overall KPI for data centre resource usage effecti
41、veness or efficiency. This European Standard is intended for use by and collaboration between data centre managers, facility managers, ICT managers and main contractors. This series of European Standards does not address the selection of information technology and network telecommunications equipmen
42、t, software and associated configuration issues. BS EN 50600-4-1:2016EN 50600-4-1:2016 8 1 Scope This European Standard specifies the following for the other standards in the EN 50600-4-X series: a) a common structure,b) definitions, terminology and boundary conditions for KPIs of data centre resour
43、ce usage effectivenessand efficiency,c) common requirements for KPIs of data centre resource usage effectiveness and efficiency,d) common objectives for KPIs of the data centre resource effectiveness and efficiency,e) general information regarding the use of KPIs of data centre resource usage effect
44、iveness andefficiency.2 Normative references The following documents, in whole or in part, are normatively referenced in this document and are indispensable for its application. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced documen
45、t (including any amendments) applies. EN 50600-1, Information technology Data centre facilities and infrastructures Part 1: General concepts 3 Terms, definitions and abbreviations 3.1 Terms and definitions For the purposes of this document, the terms and definitions given in EN 50600-1 and the follo
46、wing apply. 3.1.1 information technology equipment equipment providing data storage, processing and transport services including telecommunications network equipment dedicated to providing direct connection to core and/or access networks 3.1.2 key performance indicator number representing the resour
47、ce usage effectiveness or efficiency of a given system 3.1.3 resource usage effectiveness ratio of resulting output to a resource consumed to produce that output when the input and output units are not the same Note 1 to entry: The term is used generically to describe the conversion of a resource to
48、 an output or outcome, such as litres of water per kWh. BS EN 50600-4-1:2016EN 50600-4-1:2016 9 3.1.4 resource usage efficiency ratio of output to the resource used by the device or system when the input and output units are the same 3.2 Abbreviations For the purposes of this document, the abbreviat
49、ions given in EN 50600-1 and the following apply: AC Alternating Current DC Direct Current IT Information Technology KPI Key Performance Indicator SLA Service Level Agreement UPS Uninterruptible Power Supply 4 Conformance In order for a KPI of data centre resource usage effectiveness or efficiency to be included in the EN 50600-4 series it shall: a) meet the common objectives outlined in 5.2;b) meet the requirements of 5.3;c) meet the structure requirements of 5.4;d) meet the use requ