1、BRITISH STANDARDBS EN 60332-1-2:2004Tests on electric and optical fibre cables under fire conditions Part 1-2: Test for vertical flame propagation for a single insulated wire or cable Procedure for 1 kW pre-mixed flameICS 13.220.40; 29.060.20; 33.180.10g49g50g3g38g50g51g60g44g49g42g3g58g44g55g43g50g
2、56g55g3g37g54g44g3g51g40g53g48g44g54g54g44g50g49g3g40g59g38g40g51g55g3g36g54g3g51g40g53g48g44g55g55g40g39g3g37g60g3g38g50g51g60g53g44g42g43g55g3g47g36g58+A11:2016(IEC 60332-1-2:2004)BS EN 60332-1-2:2004+A11:2016This British Standard was published under the authority of the Standards Policy and Strat
3、egy Committee on 10 December 2004National forewordA list of organizations represented on this committee can be obtained on request to its secretary.This publication does not purport to include all the necessary provisions of a contract. Users are responsible for its correct application.Compliance wi
4、th a British Standard cannot confer immunity from legal obligations.This British Standard is the UK implementation of EN 60332-1-2:2004+A11:2016. It is derived from IEC 60332-1-2:2004, incorporating amendment 1:2015. It supersedes BS EN 60332-1-2:2004+A1:2015, which will be withdrawn on 23 May 2019.
5、The start and finish of text introduced or altered by amendment is indicated in the text by tags. Tags indicating changes to IEC text carry the number of the IEC amendment. For example, text altered by IEC amendment 1 is indicated by !“.The UK participation in its preparation was entrusted to Techni
6、cal Committee GEL/20, Electric cables.Amendments/corrigenda issued since publicationDate Comments 30 November 2015Implementation of IEC amendment 1:2015 with CENELEC endorsement A1:2015. Annex ZA updatedISBN 978 0 580 92296 1 The British Standards Institution 2016. Published by BSI Standards Limited
7、 2016by .Where a common modification has been introduced by CENELEC amendment,the tags carry the number of the amendment. For example, the commonmodifications introduced by CENELEC amendment A11 are indicatedhi31 August 2016 Implementation of CENELEC amendment A11:2016EUROPEAN STANDARD EN 60332-1-2N
8、ORME EUROPENNE EUROPISCHE NORM CENELEC European Committee for Electrotechnical Standardization Comit Europen de Normalisation Electrotechnique Europisches Komitee fr Elektrotechnische Normung Central Secretariat: rue de Stassart 35, B - 1050 Brussels 2004 CENELEC - All rights of exploitation in any
9、form and by any means reserved worldwide for CENELEC members. Ref. No. EN 60332-1-2:2004 E ICS 13.220.40; 29.020; 29.060.20 English version Tests on electric and optical fibre cables under fire conditions Part 1-2: Test for vertical flame propagation for a single insulated wire or cable - Procedure
10、for 1 kW pre-mixed flame (IEC 60332-1-2:2004) Essais des cbles lectriques et fibres optiques soumis au feu Partie 1-2: Essai de propagation verticale de la flamme sur conducteur ou cble isol - Procdure pour flamme prmlange de 1kW (CEI 60332-1-2:2004) Prfungen an Kabeln, isolierten Leitungen und Glas
11、faserkabeln im Brandfall Teil 1-2: Prfung der vertikalen Flammenausbreitung an einer Ader, einer isolierten Leitung oder einem Kabel -Prfverfahren mit 1 kW-Flamme mit Gas-/Luftgemisch (IEC 60332-1-2:2004) This European Standard was approved by CENELEC on 2004-09-01. CENELEC members are bound to comp
12、ly with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the Central Sec
13、retariat or to any CENELEC member. This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CENELEC member into its own language and notified to the Central Secretariat has the same status as
14、 the official versions. CENELEC members are the national electrotechnical committees of Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovaki
15、a, Slovenia, Spain, Sweden, Switzerland and United Kingdom. :2004+A11 August 2016 Foreword The text of document 20/697/FDIS, future edition 1 of IEC 60332-1-2, prepared by IEC TC 20, Electric cables, was submitted to the IEC-CENELEC parallel vote and was approved by CENELEC as EN 60332-1-2 on 2004-0
16、9-01. This European Standard supersedes EN 50265-2-1:1998. The following dates were fixed: latest date by which the EN has to be implemented at national level by publication of an identical national standard or by endorsement (dop) 2005-06-01 latest date by which the national standards conflicting w
17、ith the EN have to be withdrawn (dow) 2007-09-01 Annex ZA has been added by CENELEC _ Endorsement notice The text of the International Standard IEC 60332-1-2:2004 was approved by CENELEC as a European Standard without any modification. In the official version, for Bibliography, the following notes h
18、ave to be added for the standards indicated: IEC 60332-1-3 NOTE Harmonized as EN 60332-1-3:2004 (not modified). IEC 60332-2-2 NOTE Harmonized as EN 60332-2-2:2004 (not modified). _ Page 2The text of document 20/1591/FDIS, future IEC 60332-1-2:2004/A1, prepared by IEC/TC 20 “Electric cables“ was subm
19、itted to the IEC-CENELEC parallel vote and approved by CENELEC as EN 60332-1-2:2004/A1:2015. The following dates are fixed: latest date by which the document has to be implemented at national level by publication of an identical national standard or by endorsement (dop) 2016-06-01 latest date by whi
20、ch the national standards conflicting with the document have to be withdrawn (dow) 2018-09-01 Foreword to amendment A1 BS EN 60332-1-2:2004+A11:2016EN 60332-1-2:2004+A11:20162 Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CENELE
21、C and/or CEN shall not be held responsible for identifying any or all such patent rights. This standard covers the Principle Elements of the Safety Objectives for Electrical Equipment Designed for Use within Certain Voltage Limits (LVD - 2006/95/EC). Endorsement notice The text of the International
22、Standard IEC 60332-1-2:2004/A1:2015 was approved by CENELEC as a European Standard without any modification. In the Bibliography of EN 60332-1-2:2004, the following note has to be added for the standard indicated: ISO 13943 NOTE Harmonized as EN ISO 13943. Page 3BS EN 60332-1-2:2004+A11:2016EN 60332
23、-1-2:2004+A11:2016Foreword to amendment A11 This document EN 60332-1-2:2004/A11:2016 has been prepared by CLC/TC 20 “Electric cables“. The following dates are fixed: latest date by which this document has to be implemented at national level by publication of an identical national standard or by endo
24、rsement (dop) 2017-05-23 latest date by which the national standards conflicting with this document have to be withdrawn (dow) 2019-05-23 This document has been prepared under a mandate given to CENELEC by the European Commission and the European Free Trade Association. Attention is drawn to the pos
25、sibility that some of the elements of this document may be the subject of patent rights. CENELEC and/or CEN shall not be held responsible for identifying any or all such patent rights. Annex ZA (normative) Normative references to international publications with their corresponding European publicati
26、ons The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. Publication Year Title EN/HD Year IEC 60332-1
27、-1 - 1)Tests on electric and optical fibre cables under fire conditions Part 1-1: Test for vertical flame propagation for a single insulated wire or cable Apparatus EN 60332-1-1 2004 2)IEC 60695-4 - 1)Fire hazard testing Part 4: Terminology concerning fire tests EN 60695-4 1995 2)IEC Guide 104 - 1)T
28、he preparation of safety publications and the use of basic safety publications and group safety publications - - 1)Undated reference. 2)Valid edition at date of issue. IEC 60811-203 - Electric and optical fibre cables - Test methods for non-metallic materials - Part 203: General tests - Measurement
29、of overall dimensions EN 60811-203 - NOTE 1 When an International Publication has been modified by common modifications, indicated by (mod), the relevant EN/HD applies. NOTE 2 Up-to-date information on the latest versions of the European Standards listed in this annex is available here: www.cenelec.
30、eu. Page 4BS EN 60332-1-2:2004+A11:2016EN 60332-1-2:2004+A11:2016CONTENTS 1 Scope.2 Normative references.6 3 Terms and definitions.7 4 Test apparatus . 5 Procedure 7 5.1 Sample7 5.2 Conditioning7 5.3 Positioning of test piece7 5.4 Flame application8 6 Evaluation of test results9 Annex A (informative
31、) Recommended performance requirements11 Bibliography12 Page 5BS EN 60332-1-2:2004+A11:2016IEC 60332-1-2:2004+A11:20166 7TESTS ON ELECTRIC AND OPTICAL FIBRE CABLES UNDER FIRE CONDITIONS Part 1-2: Test for vertical flame propagation for a single insulated wire or cable Procedure for 1 kW pre-mixed fl
32、ame 1 Scope This part of IEC 60332 specifies the procedure for testing the resistance to vertical flame propagation for a single vertical electrical insulated conductor or cable, or optical fibre cable, under fire conditions. The apparatus is given in IEC 60332-1-1. NOTE 1 Testing to IEC 60332-1-2 m
33、ay be performed simultaneously with that to IEC 60332-1-3 if required. Recommended requirements for performance are given in Annex A. IEC 60332-1-2 specifies the use of a 1 kW pre-mixed flame and is for general use, except that the procedure specified may not be suitable for the testing of small sin
34、gle insulated conductors or cables of less than 0,5 mm total cross-section because the conductor melts before the test is completed, or for the testing of small optical fibre cables because the cable is broken before the test is completed. In these cases, the procedure given in IEC 60332-2-2 is reco
35、mmended. NOTE 2 Since the use of insulated conductor or cable which retards flame propagation and complies with the recommended requirements of this standard is not sufficient by itself to prevent propagation of fire under all conditions of installation, it is recommended that wherever the risk of p
36、ropagation is high, for example in long vertical runs of bunches of cables, special installation precautions should also be taken. It cannot be assumed that because the sample of cable complies with the performance requirements recommended in this standard, that a bunch of cables will behave in a si
37、milar manner. (See IEC 60332-3 series.) 2 Normative references The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendme
38、nts) applies. IEC 60332-1-1, Tests on electric and optical fibre cables under fire conditions Part 1-1: Test for vertical flame propagation for a single insulated wire or cable Apparatus IEC 60695-4, Fire hazard testing Part 4: Terminology concerning fire tests IEC Guide 104, The preparation of safe
39、ty publications and the use of basic safety publications and group safety publications IEC 60811-203, Electric and optical fibre cables Test methods for non-metallic materials Part 203: General tests Measurement of overall dimensions!“Page 6BS EN 60332-1-2:2004+A11:2016IEC 60332-1-2:2004+A11:20163 T
40、erms and definitions For the purposes of this document, the following terms and definitions apply. The definitions are taken from IEC 60695-4. 3.1 ignition source source of energy that initiates combustion 3.2 char carbonaceous residue resulting from pyrolysis or incomplete combustion 4 Test apparat
41、us The apparatus specified in IEC 60332-1-1 shall be used. 5 Procedure 5.1 Sample 5.2 Conditioning Before testing, all test pieces shall be conditioned at (23 5) C for not less than 16 h at a relative humidity of (50 20) %. In the case of a single insulated conductor or cable with a finish of paint
42、or lacquer, this conditioning shall follow an initial period where the test piece shall be kept at a temperature of (60 2) C for 4 h. 5.3 Positioning of test piece ! “! “!“!“SOURCE: ISO 13943:2008, 1.489 SOURCE: ISO 13943:2008, 4.38 The test piece shall be straightened and secured to two horizontal
43、supports by means of a suitable size of copper wire, in a vertical position in the centre of the metal enclosure, as described in IEC 60332-1-1, so that the distance between the bottom of the upper support and the top of the lower support is (550 5) mm. In addition, the test piece shall be positione
44、d so that the bottom of the specimen is approximately 50 mm from the base of the enclosure (see Figure 1). The vertical axis of the test piece shall be arranged centrally within the enclosure (i.e. 150 mm from each side and 225 mm from the rear). The test sample shall be a piece of single insulated
45、conductor or cable (600 25) mm long. The test sample diameter shall be measured using the method given in IEC 60811-203. The measurement shall be made at each of three places, separated by at least 100 mm. The average of the three values obtained shall be rounded to obtain the overall diameter. If t
46、he calculation gives 5 or more for the second decimal figure, raise the first to the next number; thus, for example, 5,75 is rounded to 5,8. If the calculation gives 4 or less for the second decimal figure, maintain the first number; thus, for example, 5,74 is rounded to 5,7. The overall diameter ob
47、tained shall be used for the selection of the time for flame application. Page 7BS EN 60332-1-2:2004+A11:2016IEC 60332-1-2:2004+A11:20165.4 Flame application Safety warning Precautions shall be taken to safeguard personnel against the following when conducting tests: a) the risk of fire or explosion
48、; b) the inhalation of smoke and/or noxious products, particularly when halogenated materials are burned; c) harmful residues. 5.4.1 Positioning of flame 5.4.2 Test duration The flame shall be applied continuously for the period of time corresponding to the diameter shown in Table 1. Table 1 Time fo
49、r flame application Overall diameter of test piece a mm Time for flame application s D 25 25 75 60 2 120 2 240 2 480 2 a b At the end of the specified flame application time, the burner shall be removed and the flame of the burner extinguished. !“A burner, as described in IEC 60332-1-1, shall be ignited and the flow rates of gas and air adjusted to the specified values. The burner shall be positioned so that the tip of the blue cone impinges on the surface of the test piece at a dista