1、Industrial-process control systems Instruments with analogue inputs and two- ormulti-state outputsPart 2: Guidance for inspection and routine testingBS EN 61003-2:2009National forewordThis British Standard is the UK implementation of EN 61003-2:2009. It isidentical to IEC 61003-2:2009.The UK partici
2、pation in its preparation was entrusted by Technical CommitteeGEL/65, Measurement and control, to Subcommittee GEL/65/2, Elements ofsystems.A list of organizations represented on this committee can be obtained onrequest to its secretary.This publication does not purport to include all the necessary
3、provisions of acontract. Users are responsible for its correct application. BSI 2010ISBN 978 0 580 61815 4ICS 25.040.40Compliance with a British Standard cannot confer immunity fromlegal obligations.This British Standard was published under the authority of the StandardsPolicy and Strategy Committee
4、 on 31 May 2010.Amendments issued since publicationAmd. No. Date Text affectedBRITISH STANDARDBS EN 61003-2:2009EUROPEAN STANDARD EN 61003-2 NORME EUROPENNE EUROPISCHE NORM October 2009 CENELEC European Committee for Electrotechnical Standardization Comit Europen de Normalisation Electrotechnique Eu
5、ropisches Komitee fr Elektrotechnische Normung Central Secretariat: Avenue Marnix 17, B - 1000 Brussels 2009 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members. Ref. No. EN 61003-2:2009 E ICS 25.040.40 English version Industrial-process control s
6、ystems - Instruments with analogue inputs and two- or multi-state outputs - Part 2: Guidance for inspection and routine testing (IEC 61003-2:2009) Processus industriels - Instruments avec entres analogiques et sorties deux ou plusieurs tats - Partie 2: Guide pour les inspections et les essais indivi
7、duels de srie (CEI 61003-2:2009) Systeme der industriellen Prozessleittechnik - Gerte mit analogen Eingngen und Zwei- oder Mehrpunktverhalten - Teil 2: Leitfaden fr Funktionskontrolle und Serienprfung (IEC 61003-2:2009) This European Standard was approved by CENELEC on 2009-09-01. CENELEC members ar
8、e bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to
9、the Central Secretariat or to any CENELEC member. This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CENELEC member into its own language and notified to the Central Secretariat has the
10、 same status as the official versions. CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Cyprus, the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands,
11、Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom. BS EN 61003-2:2009EN 61003-2:2009 - 2 - Foreword The text of document 65B/703/CDV, future edition 1 of IEC 61003-2, prepared by SC 65B, Devices Relative humidity from 45 % to 75 %; Atmospheric p
12、ressure from 86 kPa to 106 kPa; BS EN 61003-2:200961003-2 IEC:2009 7 Electromagnetic field value to be stated if relevant. The maximum rate of change of ambient temperature permissible during any test shall be 1 C in 10 min and less than 3 C/h. 5.2.2 Supply conditions Electrical supply: Rated voltag
13、e 1 %; Rated frequency 1 %; Harmonic distortion (a.c. supply) less than 5 %; Ripple (d.c. supply) less than 0,1 %. Pneumatic supply: Rated pressure 3 %; Supply air temperature ambient temperature 2 C; Supply air humidity dew point at least 10 C below devices body temperature; Oil and dust content oi
14、l: less than 1 106by weight; dust: absence of particles greater than 3 m. 5.3 Tests under reference conditions 5.3.1 General All tests given in 6.1 and 6.3 of IEC 61003-1 should be carried out. Multi-state instruments should supplement the tests given in Clause 7 of IEC 61003-1. The detailed test pr
15、ocedures are given in IEC 61298-2. 5.3.2 Set point 5.3.2.1 Set point adjustable and measurable or indicated The set point shall be tested at value of 10 %, 50 % and 90 % at least, the 50 % value being taken last. The measurement or indication accuracy shall be determined at five points approximately
16、 evenly spaced over the range. 5.3.2.2 Set point adjustable but not indicated The set point shall be tested for at least three values, approximately evenly spaced over the effective range of adjustment. 5.3.2.3 Set point not adjustable The set point shall be tested directly. 5.3.2.4 Multi-state inst
17、rument set point Each state should be tested in accordance with 5.3.2.1, 5.3.2.2 and 5.3.2.3. Subclause 7.2.2 of IEC 61003-1 gives the test method of mutual influence of pairs of switching points. BS EN 61003-2:2009 8 61003-2 IEC:2009 5.4 Tests for the effects of influence quantities 5.4.1 General W
18、hen testing the effects of influence quantities, the set point shall be not less than one. For measurable or indicated instruments, indication of the measured value should be tested also. For set point adjustable instruments, the value of 50 % should be included. The effects on switching points of i
19、nfluence quantities should be tested in accordance with 6.2 of IEC 61003-1 and with IEC 61298-3. 5.4.2 Supply voltage variations This test shall be performed on instruments with electrical power supply for internal operations. For two-wire instruments, fix the load resistance at nominal value or a c
20、onvenient value, and record this value. Test the instruments with the power voltage set at the nominal value, maximum value and minimum value successively. 5.4.3 Supply pressure variations This test shall be performed on instruments with pressure supply. The testing supply pressure should be nominal
21、 value, +10 % of the nominal value or the manufacturers limit, 15 % of the nominal value or the manufacturers limit. 6 Test report and documentation 6.1 General A test report of the evaluation shall be prepared in accordance with IEC 61298-4 after completing all tests. All the original documentation
22、, related to the tests, shall be stored by the test laboratory for at least two years, after the report is issued. 6.2 Test report and general observations Table 2 gives an example of a summary of the test results information to be reported. BS EN 61003-2:200961003-2 IEC:2009 9 Table 2 Test report a
23、nd general observations No. Designation Reference Unit Information to be reported 1. Inaccuracy of switching points IEC 61298-2, 4.1.7 % Values of points x1and x2and their average shall be reported. The switching differential (x1x2) shall be noted for each cycle. The greatest positive and negative d
24、eviations of any measured value of x1and x2, of any cycle, from the set point w for increasing and decreasing inputs shall be reported as switching point inaccuracy. 2. Inaccuracy of switching differential IEC 61298-2, 4.1.7.1 % The difference between the average value of x1and the average value of
25、x2, shall be reported as Xsd. The greatest positive and negative deviations of any measured value of the switching differentials calculated in each of the five cycles from the Xsdvalue, shall be reported as switching differential inaccuracy. 3. Set point adjustable and measurable or indicated IEC 61
26、298-2, 4.1.7.1 and 4.1.7.6 % The greatest positive and negative deviations of any measured value of xmfrom the ideal set-point value for each cycle and for each set point shall be reported as inaccuracy of set point setting. 4. Set point adjustable but not indicated IEC 61298-2, 4.1.7.1 and 4.1.7.6
27、% Values of x1, x2and Xsd, and their accuracy-related factors and values of xm, shall be reported. 5. Set point not adjustable IEC 61298-2, 4.1.7.1 and 4.1.7.6 % Values of x1, x2and Xsd, and their accuracy-related factors and values of xm, shall be reported. 6. Indication of the measured value % The
28、 changes in measured value indicated shall be recorded 7. Isolation test IEC 61010-1, 6.8 aand Annex F Report any appreciable transient overvoltage that occurs during tests. 8. Characteristics of the multi-state instrument % Each state shall report xi1, xi2, xmi, xsdi, xi1- xi2, xsriand an appropria
29、te, xmi w, (see IEC 61003-1, Figure 4) 9. Supply voltage variations IEC 61298-3, 12.1 % The effect on switching points, measured during test, (and measured value) shall be reported. 10. Supply pressure variations b IEC 61298-3, 12.8 % The effect on switching points shall be reported b. aIEC 61010-1
30、6.8 procedure for dielectric strength tests combines with IEC 61003-1 6.3.4 isolation test, and describe the test method. bIf the manufacturers specified limits are less than the preferred test values, this fact shall be reported with the test result. _ BS EN 61003-2:2009This page deliberately left blank