1、BRITISH STANDARDConduit systems for cable management Part 23: Particular requirements Flexible conduit systemsICS 29.120.10 g49g50g3g38g50g51g60g44g49g42g3g58g44g55g43g50g56g55g3g37g54g44g3g51g40g53g48g44g54g54g44g50g49g3g40g59g38g40g51g55g3g36g54g3g51g40g53g48g44g55g55g40g39g3g37g60g3g38g50g51g60g5
2、3g44g42g43g55g3g47g36g58BS EN 61386-23:2004 +A 1:20101National forewordThis British Standard is the UK implementation of EN 61386-23:2004+A11:2010. It is identical to IEC 61386-23:2002. It supersedes BS EN 61386-23:2004, which is withdrawn.The UK participation in its preparation was entrusted to Tec
3、hnical Committee PEL/213, Cable management.A list of organizations represented on this committee can be obtained on request to its secretary.This publication does not purport to include all the necessary provisions of a contract. Users are responsible for its correct application. Compliance with a B
4、ritish Standard cannot confer immunity from legal obligations. BS EN 61386-23:2004+A11:2010This British Standard was published under the authority of the Standards Policy and Strategy Committee on 26 May 2004 BSI 2011Amendments/corrigenda issued since publicationDate Comments 30 June 2011 Implementa
5、tion of CENELEC amendment A11:2010, modification of CENELEC foreword.ISBN 978 0 580 71474 0EUROPEAN STANDARD EN 61386-23:2004+A11+A11 NORME EUROPENNE EUROPISCHE NORM December 2010 CENELEC European Committee for Electrotechnical Standardization Comit Europen de Normalisation Electrotechnique Europisc
6、hes Komitee fr Elektrotechnische Normung Central Secretariat: Avenue Marnix 17, B - 1000 Brussels 2010 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members. Ref. No. EN 61386-23:2004 E ICS 29.120.10 Supersedes EN 50086-2-3:1995 + A11:1998English ve
7、rsion Conduit systems for cable management Part 23: Particular requirements Flexible conduit systems (IEC 61386-23:2002) Systmes de conduits pour installations lectriques Partie 23: Rgles particulires Systmes de conduits souples (CEI 61386-23:2002) Elektroinstallationsrohrsysteme fr elektrische Ener
8、gie und fr Informationen Teil 23: Besondere Anforderungen fr flexible Elektroinstallationsrohrsysteme (IEC 61386-23:2002) This European Standard was approved by CENELEC on 2003-09-23. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giv
9、ing this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the Central Secretariat or to any CENELEC member. This European Standard exists in three official
10、versions (English, French, German). A version in any other language made by translation under the responsibility of a CENELEC member into its own language and notified to the Central Secretariat has the same status as the official versions. CENELEC members are the national electrotechnical committee
11、s of Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom. Incorporates Corrigendu
12、m April 2004 Foreword The text of the International Standard IEC 61386-23:2002, prepared by SC 23A, Cable management systems, of IEC TC 23, Electrical accessories, was submitted to the Unique Acceptance Procedure and was approved by CENELEC as EN 61386-23 on 2003-09-23. This European Standard supers
13、edes EN 50086-2-3:1995 + corrigendum February 2001 + A11:1998 + A11:1998/corrigendum February 2001. The following dates were fixed: latest date by which the EN has to be implemented at national level by publication of an identical national standard or by endorsement (dop) 2004-10-01 latest date by w
14、hich the national standards conflicting with the EN have to be withdrawn (dow) 2008-06-30 This part 23 supplements or modifies the corresponding clauses of EN 61386-1. Where a particular clause or subclause of part 1 is not mentioned in this part 23, that clause or subclause applies as far as is rea
15、sonable. Where this part 23 states “addition“, “modification“ or “replacement“, the relevant text of part 1 is to be adapted accordingly. Subclauses, tables and figures which are in addition to those in part 1 are numbered starting with 101. Additional annexes are lettered AA, BB, etc. A conduit sys
16、tem which complies with this standard is deemed safe for use when installed in accordance with national wiring regulations, whilst applying the manufacturers installation instructions and conduit classification. In this standard, the following print types are used: - requirements: in roman type; - t
17、est specifications: in italic type; - notes: in smaller roman type. Annexes ZAA and ZBB have been added by CENELEC. _ Endorsement notice The text of the International Standard IEC 61386-23:2002 was approved by CENELEC as a European Standard without any modification. _ Page 2This part 23, which speci
18、fies particular requirements for flexible conduit systems, is to be used in conjunction with EN 61386-1:2008; it may also be used in conjunction with EN 61386-1:2004 until EN 61386-1:2004 is withdrawn, the date of the withdrawal being no later than 2011-06-01. BS EN 61386-23:2004+A11:2010EN 61386-23
19、:2004+A11:2010 (E)This amendment (affecting only the foreword) has been issued to allow the use of EN 61386-23:2004 in conjunction with EN 61386-1:2008. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN and CENELEC shall not be
20、held responsible for identifying any or all such patent rights. The following dates were fixed: latest date by which the amendment has to be implemented at national level by publication of an identical national standard or by endorsement (dop) 2011-12-01 dwhsrofngwith the amendment have to be withdr
21、awn (dow) 2013-12-01 _ Page 3BS EN 61386-23:2004+A11:2010EN 61386-23:2004+A11:2010 (E)Foreword to amendment 1This amendment to the European Standard EN 61386-23:2004 was prepared by the Technical Committee CENELEC TC 213, Cable management systems. It was submitted to the Unique Acceptance Procedure
22、and was accepted by CENELEC as amendment A11 to EN 61386-23:2004 on 2010-12-01.CONTENTS 1 Scope 5 2 Normative references .5 3 Definitions5 4 General requirements.5 5 General conditions for tests5 6 Classification5 7 Marking and documentation5 8 Dimensions 6 9 Construction.6 10 Mechanical properties
23、6 11 Electrical properties7 12 Thermal properties .8 13 Fire effects.8 14 External influences.8 15 Electromagnetic compatibility .8 Annex ZA (normative) Normative references to international publications with their corresponding European publications.13Figure 101 Flexing test apparatus 9 Figure 102
24、Gauge for checking the minimum inside diameter of the conduit system after impact and resistance to heat tests . 10Figure 103 Assembly of conduit and terminating conduit fitting for bonding test 11Page 4BS EN 61386-23:2004+A11:2010EN 61386-23:2004+A11:2010 (E)6831632- CEI : 2002 4 CONDUIT SYSTEMS FO
25、R CABLE MANAGEMENT Part 23: Particular requirements Flexible conduit systems 1 Scope This clause of part 1 is applicable, except as follows: Addition: This part of IEC 61386 specifies the requirements for flexible conduit systems. 2 Normative references This clause of part 1 is applicable. 3 Definit
26、ions This clause of part 1 is applicable. 4 General requirements This clause of part 1 is applicable. 5 General conditions for tests This clause of part 1 is applicable. 6 Classification This clause of part 1 is applicable, except as follows: Subclauses 6.1.3 1, 6.1.3 2 and 6.1.3 3 are not applicabl
27、e. NOTE Flexible conduit systems according to 6.1.1 1, 6.1.1 2, 6.1.2 1, 6.1.2 2 and classification 1X from 6.2.1, table 1 are not allowed in France. 7 Marking and documentation This clause of part 1 is applicable, except as follows: Addition: 7.1.101 The conduit shall be marked in accordance with 7
28、.1 along its entire length at regular intervals of preferably 1 m but not longer than 3 m. Where this is technically impractical, the mark shall be on a label attached to the product at each end, or on the packaging. Page 5BS EN 61386-23:2004+A11:2010EN 61386-23:2004+A11:2010 (E)6831632- CEI : 2002
29、5 Compliance is checked by inspection. 7.1.102 The manufacturer shall document or add to the packaging for the system the minimum inside diameter, the minimum bend radius and the classification in accordance with clause 6. Compliance is checked by inspection. 8 Dimensions Replacement: 8.1 Threads sh
30、all comply with IEC 60423. Compliance is checked by means of the gauges specified in IEC 60423. 8.2 The minimum inside diameter of the conduit system shall be as declared by the manufacturer. Compliance is checked by measurement. 9 Construction This clause of part 1 is applicable. 10 Mechanical prop
31、erties This clause of part 1 is applicable, except as follows: 10.1 Mechanical strength 10.1.1 Addition: NOTE Very light flexible conduits should not be considered as providing adequate mechanical protection and should not be used within the construction of buildings. 10.4 Bending test This subclaus
32、e of part 1 is not applicable. 10.5 Flexing test 10.5.101 An assembly consisting of a conduit with a terminating conduit fitting, assembled in accordance with the manufacturers instructions, shall be subjected to a flexing test by means of the apparatus shown in figure 101. 10.5.102 The test shall b
33、e made on six samples of conduit of an appropriate length. Three of the samples shall be tested at the minimum declared transport, application and installation temperature as given in table 1 with a tolerance of 2 C. The other three samples shall be tested at the maximum declared application and ins
34、tallation temperature as given in table 2 with a tolerance of 2 C. Page 6BS EN 61386-23:2004+A11:2010EN 61386-23:2004+A11:2010 (E)6831632- CEI : 2002 6 A manufacturer may declare that a flexible conduit is suitable for transport and installation according to table 1 but may only be suitable for flex
35、ing at ambient temperature as a minimum. In this case the test shall be carried out at (20 2) C and the 3rd digit of the classification code shall be X. The manufacturer shall clearly declare in his literature both the minimum transport and installation temperature in accordance with table 1, the mi
36、nimum application temperature which is ambient and the maximum installation and application temperature in accordance with table 2. 10.5.103 The sample shall be fixed to the oscillating member by means of the terminating conduit fitting as shown in figure 101, so that when the conduit is at the midd
37、le of its travel, the axis of the conduit is vertical and passes through the axis of the oscillation. The apparatus with the sample shall be conditioned for 2 h or until the sample has attained the declared temperature, whichever period is the longer. 10.5.104 The oscillating member shall be moved b
38、ackwards and forwards through a total angle of (180 5) divided equally about the vertical axis. The assembly shall be subjected to 5 000 flexings at a rate of (40 5) flexings per minute. A flexing constitutes, starting from the vertical position, one continuous cycle of movement of essentially sinus
39、oidal forms. 10.5.105 After the test, the sample shall show no sign of disintegration, nor shall there be any cracks visible to normal or corrected vision without magnification. 10.6 Collapse test This subclause of part 1 is not applicable. 10.7 Tensile strength This subclause of part 1 is applicabl
40、e, except as follows: 10.7.3 Replacement: For conduit systems where tensile strength is not declared, the tensile strength of the joint shall comply with classification 1 in table 6. 11 Electrical properties This clause of part 1 is applicable, except as follows: 11.2 Bonding test Replacement: A sam
41、ple of a conduit and terminating conduit fitting shall be assembled in accordance with the manufacturers instructions and mounted as shown in figure 103. A current of 25 A, having a frequency of 50 Hz to 60 Hz, derived from an a.c. source having a no-load voltage not exceeding 12 V, shall be passed
42、through the assembly for (5060+) s. Then the voltage drop shall be measured between the points shown in figure 103 and the resistance calculated from the current and this voltage drop. The resistance shall not exceed 0,05 . Page 7BS EN 61386-23:2004+A11:2010EN 61386-23:2004+A11:2010 (E)6831632- CEI
43、: 2002 7 Where special devices are required for the coupling of conduit and conduit fittings, they shall be sufficient to remove the protective coating from the conduit, or the protective finish shall be removed in accordance with the manufacturers instructions. 12 Thermal properties This clause of
44、part 1 is applicable, except as follows: 12.2.4 Replacement: The load is then removed and immediately after its removal it shall be possible to pass the appropriate gauge, in accordance with figure 102, through the conduit under its own weight and without any initial speed, with the sample in the ve
45、rtical position. 13 Fire effects This clause of part 1 is applicable. 14 External influences This clause of part 1 is applicable. 15 Electromagnetic compatibility This clause of part 1 is applicable. Page 8BS EN 61386-23:2004+A11:2010EN 61386-23:2004+A11:2010 (E)6831632- CEI : 2002 8 dn32dsR1R2dsY2Z
46、BA90901Key A Conduit B Terminating fitting dsOutside diameter of conduit (A) dnInside diameter of support block: 1,1 dsR1Radius of support block: 0,5 d, R2Radius of support block: 0,25 dsY Minimum bend radius, declared by the manufacturer Z 1,5 Y 1 Oscillating member 2 Guide support block 3 Plan vie
47、w of guide support block NOTE This drawing is not intended to govern design except as regards the dimensions shown. Figure 101 Flexing test apparatus IEC 505/02 Page 9BS EN 61386-23:2004+A11:2010EN 61386-23:2004+A11:2010 (E)6831632- CEI : 2002 10 D 80 % of the manufacturers declared minimum inside d
48、iameter of the conduit system Material Steel, hardened and polished, edges slightly rounded Manufacturing tolerance mm05,00+Tolerance and axial dimension 0,2 mm Admissible wear 0,01 mm NOTE This drawing is not intended to govern design except as regards the dimensions shown. Figure 102 Gauge for che
49、cking the minimum inside diameter of the conduit system after impact and resistance to heat tests IEC 475/02 Page 10BS EN 61386-23:2004+A11:2010EN 61386-23:2004+A11:2010 (E)6831632- CEI : 2002 12 321VXX4A25A 50/60 HzKey X 12 mm 2 mm 1 3 mm steel plate 2 Optional locknut 3 Terminating conduit fitting secured to plate by tapped hole or by locknut on fitting thread 4 Conduit NOTE This drawing is not intended to govern design except as regards the dimensions sh