1、raising standards worldwideNO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAWBSI Standards PublicationDigital addressable lighting interface Part 205: Particular requirements for control gear Supply voltage controller for incandescent lamps (device type 4)BS EN 62386-205:2009Nati
2、onal forewordThis British Standard is the UK implementation of EN 62386-205:2009. It isidentical to IEC 62386-205:2009.The UK participation in its preparation was entrusted by Technical CommitteeCPL/34, Lamps and related equipment, to Subcommittee CPL/34/3, Auxiliariesfor lamps.A list of organizatio
3、ns represented on this committee can be obtained onrequest to its secretary.This publication does not purport to include all the necessary provisions of acontract. Users are responsible for its correct application. BSI 2010ISBN 978 0 580 57540 2ICS 29.140.50; 29.140.99Compliance with a British Stand
4、ard cannot confer immunity fromlegal obligations.This British Standard was published under the authority of the StandardsPolicy and Strategy Committee on 31 January 2010Amendments issued since publicationAmd. No. Date Text affectedBRITISH STANDARDBS EN 62386-205:2009EUROPEAN STANDARD EN 62386-205 NO
5、RME EUROPENNE EUROPISCHE NORM November 2009 CENELEC European Committee for Electrotechnical Standardization Comit Europen de Normalisation Electrotechnique Europisches Komitee fr Elektrotechnische Normung Central Secretariat: Avenue Marnix 17, B - 1000 Brussels 2009 CENELEC - All rights of exploitat
6、ion in any form and by any means reserved worldwide for CENELEC members. Ref. No. EN 62386-205:2009 E ICS 29.140.50; 29.140.99 English version Digital addressable lighting interface - Part 205: Particular requirements for control gear - Supply voltage controller for incandescent lamps (device type 4
7、) (IEC 62386-205:2009) Interface dclairage adressable numrique - Partie 205: Exigences particulires pour les appareillages de commande - Variateur de tension dalimentation pour les lampes incandescence (dispositifs de type 4) (CEI 62386-205:2009) Digital adressierbare Schnittstelle fr die Beleuchtun
8、g - Teil 205: Besondere Anforderungen an Betriebsgerte - Versorgungsspannungsregler fr Glhlampen (Gertetyp 4) (IEC 62386-205:2009) This European Standard was approved by CENELEC on 2009-09-01. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the condition
9、s for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the Central Secretariat or to any CENELEC member. This European Standard exists in three
10、official versions (English, French, German). A version in any other language made by translation under the responsibility of a CENELEC member into its own language and notified to the Central Secretariat has the same status as the official versions. CENELEC members are the national electrotechnical
11、committees of Austria, Belgium, Bulgaria, Cyprus, the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the
12、 United Kingdom. BS EN 62386-205:2009EN 62386-205:2009 - 2 - Foreword The text of document 34C/819/CDV, future edition 1 of IEC 62386-205, prepared by SC 34C, Auxiliaries for lamps, of IEC TC 34, Lamps and related equipment, was submitted to the IEC-CENELEC parallel vote and was approved by CENELEC
13、as EN 62386-205 on 2009-09-01. This standard is to be used in conjunction with EN 62386-101 and EN 62386-102, which contain general requirements for the relevant product type (control gear or control devices). The following dates were fixed: latest date by which the EN has to be implemented at natio
14、nal level by publication of an identical national standard or by endorsement (dop) 2010-06-01 latest date by which the national standards conflicting with the EN have to be withdrawn (dow) 2012-09-01 Annex ZA has been added by CENELEC. _ Endorsement notice The text of the International Standard IEC
15、62386-205:2009 was approved by CENELEC as a European Standard without any modification. In the official version, for Bibliography, the following notes have to be added for the standards indicated: IEC 60598-1 NOTE Harmonized as EN 60598-1:2008 (modified). IEC 60669-2-1 NOTE Harmonized as EN 60669-2-
16、1:2004 (modified). IEC 60921 NOTE Harmonized as EN 60921:2004 (not modified). IEC 60923 NOTE Harmonized as EN 60923:2005 (not modified). IEC 60925 NOTE Harmonized as EN 60925:1991 (not modified). IEC 60929 NOTE Harmonized as EN 60929:2006 (not modified). IEC 61347-1 NOTE Harmonized as EN 61347-1:200
17、8 (modified). IEC 61347-2-3 NOTE Harmonized as EN 61347-2-3:2001 (not modified). IEC 61547 NOTE Harmonized as EN 61547:1995 (not modified). CISPR 15 NOTE Harmonized as EN 55015:2006 (not modified). _ BS EN 62386-205:2009- 3 - EN 62386-205:2009 Annex ZA (normative) Normative references to internation
18、al publications with their corresponding European publications The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendme
19、nts) applies. NOTE When an international publication has been modified by common modifications, indicated by (mod), the relevant EN/HD applies. Publication Year Title EN/HD Year IEC 62386-101 2009 Digital addressable lighting interface - Part 101: General requirements - System EN 62386-101 2009 IEC
20、62386-102 2009 Digital addressable lighting interface - Part 102: General requirements - Control gearEN 62386-102 2009 BS EN 62386-205:2009 2 62386-205 IEC:2009 CONTENTS INTRODUCTION.5 1 Scope.6 2 Normative references .6 3 Terms and definitions .6 4 General description 7 5 Electrical specifications
21、7 6 Interface power supply .7 7 Transmission protocol structure7 8 Timing 7 9 Method of operation .7 10 Declaration of variables8 11 Definition of commands 9 12 Test procedures .16 Bibliography27 Figure 1 Application extended configuration command sequence example.10 Figure 2 Test sequence QUERY DIM
22、MER STATUS and QUERY FEATURES .17 Figure 3 Test sequence QUERY FAILURE STATUS.18 Figure 4 Test sequence COMMANDS 242 to 248 .20 Figure 5 Test sequence SELECT DIMMING CURVE, QUERY DIMMING CURVE and QUERY DIMMER STATUS .21 Figure 6 Test sequence REFERENCE SYSTEM POWER .22 Figure 7 Test sequence REFERE
23、NCE SYSTEM POWER .23 Figure 8 Test sequence QUERY REFERENCE MEASUREMENT FAILED 24 Figure 9 Test sequence QUERY EXTENDED VERSION NUMBER .25 Figure 10 Test sequence RESERVED APPLICATION EXTENDED COMMANDS26 Table 1 Declaration of variables.8 Table 2 Dimming method bits.12 Table 3 Summary of the applica
24、tion extended command set 15 Table 4 Command 241 QUERY FAILURE STATUS test conditions.19 Table 5 Query commands 242 to 248 test table .20 BS EN 62386-205:200962386-205 IEC:2009 5 INTRODUCTION This first edition of IEC 62386-205 is published in conjunction with IEC 62386-101 and IEC 62386-102. The di
25、vision of IEC 62386 into separately published parts provides for ease of future amendments and revisions. Additional requirements will be added as and when a need for them is recognized. This International Standard, and the other parts that make up the IEC 62386-200 series, in referring to any of th
26、e clauses of IEC 62386-101 or IEC 62386-102, specify the extent to which such a clause is applicable and the order in which the tests are to be performed. The parts also include additional requirements, as necessary. All parts that make up the IEC 62386-200 series are self-contained and therefore do
27、 not include references to each other. Where the requirements of any of the clauses of IEC 62386-101 or IEC 62386-102 are referred to in this International Standard by the sentence “The requirements of IEC 62386-1XX, clause n apply”, this sentence is to be interpreted as meaning that all requirement
28、s of the clause in question of Part 101 or Part 102 apply, except any which are inapplicable to the specific type of lamp control gear covered by Part 205. All numbers used in this International Standard are decimal numbers unless otherwise noted. Hexadecimal numbers are given in the format 0xVV, wh
29、ere VV is the value. Binary numbers are given in the format XXXXXXXXb or in the format XXXX XXXX, where X is 0 or 1; “x“ in binary numbers means “dont care“. BS EN 62386-205:2009 6 62386-205 IEC:2009 DIGITAL ADDRESSABLE LIGHTING INTERFACE Part 205: Particular requirements for control gear Supply vol
30、tage controller for incandescent lamps (device type 4) 1 Scope This International Standard specifies a protocol and test procedures for the control by digital signals of electronic control gear associated with incandescent lamps. 2 Normative references The following referenced documents are indispen
31、sable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. IEC 62386-101:2009, Digital addressable lighting interface Part 101: General requirements System
32、 IEC 62386-102:2009, Digital addressable lighting interface Part 102: General requirements Control gear 3 Terms and definitions For the purposes of this document, the terms and definitions given in Clause 3 of IEC 62386-101:2009 and Clause 3 of IEC 62386-102:2009 apply, together with the following.
33、3.1 reference measurement measurement of the actual lamp load NOTE Control gear determines the actual lamp load with internal procedures and measurements, not specified by this standard. 3.2 detection of load decrease recognition that the actual lamp load is significantly below the load measured dur
34、ing a successful reference measurement NOTE The criteria for regarding a load increase or decrease as significant can only be defined by the manufacturer, and these criteria should be described in the manual. 3.3 detection of load increase recognition that the actual lamp load is significantly above
35、 the load measured during a successful reference measurement NOTE The criteria for regarding a load increase or decrease as significant can only be defined by the manufacturer, and these criteria should be described in the manual. 3.4 thermal overload the maximum permissible gear temperature is exce
36、eded BS EN 62386-205:200962386-205 IEC:2009 7 3.5 thermal shut down gear switches off the lamp because automatic reduction of output level failed to prevent a persistent thermal overload 3.6 light level reduction due to thermal overload light level reduction with the objective of decreasing gear tem
37、perature. 3.7 load over-current shutdown gear switches off the lamp because automatic reduction of output level failed to prevent a persistent over-current condition. 4 General description The requirements of Clause 4 of IEC 62386-101:2009 and Clause 4 of IEC 62386-102:2009 shall apply. 5 Electrical
38、 specifications The requirements of Clause 5 of IEC 62386-101:2009 and Clause 5 of IEC 62386-102:2009 shall apply. 6 Interface power supply The requirements of Clause 6 of IEC 62386-101:2009 and Clause 6 of IEC 62386-102:2009 shall apply if a power supply is integrated with the control gear. 7 Trans
39、mission protocol structure The requirements of Clause 7 of IEC 62386-101:2009 and Clause 7 of IEC 62386-102:2009 shall apply. 8 Timing The requirements of Clause 8 of IEC 62386-101:2009 and Clause 8 of IEC 62386-102:2009 shall apply. 9 Method of operation 9.1 General The requirements of Clause 9 of
40、IEC 62386-101:2009 and Clause 9 of IEC 62386-102:2009 shall apply with the following additions and adaptations: The dimming curve, whether logarithmic or linear, shall apply for a lamp type and rating suitable for the use by the control gear. The dimming mode in the case of a fixed-mode universal di
41、mmer shall only be changeable by the means of a switch or other physical controls on the dimmer, and not from the interface. NOTE This eliminates the danger of unintentional changes during system programming. BS EN 62386-205:2009 8 62386-205 IEC:2009 9.2 Detection of load decrease If the actual lamp
42、 load is significantly below the load measured during a successful reference measurement, the control gear might switch off the lamp if this is necessary for its safe operation and the flag bit load decrease shall be set. 9.3 Detection of load increase If the actual lamp load is significantly above
43、the load measured during a successful reference measurement, the control gear might switch off if this is necessary for its safe operation and the flag bit load increase shall be set. 9.4 Lamp replacement on control gear with load increase/decrease feature If a lamp is replaced with one of a differe
44、nt power, the control gear may falsely detect load decrease or load increase. In this case, correct detection of load decrease or load increase shall require a successful REFERENCE SYSTEM POWER measurement. NOTE In some cases, replacement of a lamp with one of the same power may require a new REFERE
45、NCE SYSTEM MEASUREMENT for correct detection of load decrease or load increase. 10 Declaration of variables The requirements of Clause 10 of IEC 62386-101:2009 and Clause 10 of IEC 62386-102:2009 shall apply, with the following additional variables for this device type, indicated in Table 1. Table 1
46、 Declaration of variables Variable Default value Reset value Range of validity Memory a“DIMMING CURVE” 0 No change 0 1; (2 255 reserved) 1 byte “DIMMER STATUS” 0000 00UU bNo change except bit 4 is reset to 0 0 - 255 1 byte RAM c“DIMMER FEATURES” Factory burn-in No change 0 - 255 each byte 3 bytes RO
47、M “FAILURE STATUS BYTE 1” UUU0 UUUU bNo change 0 - 255 1 byte RAM c“FAILURE STATUS BYTE 2” 000U UUUU bNo change 0 - 255 1 byte RAM “DIMMER TEMPERATURE” UUUU UUUU bNo change 0 254, 255 (Mask) 1 byte RAM “RMS SUPPLY VOLTAGE” UUUU UUUU bNo change 0 254, 255 (Mask) 1 byte RAM “SUPPLY FREQUENCY” UUUU UUU
48、U bNo change 0 254, 255 (Mask) 1 byte RAM “RMS LOAD VOLTAGE” UUUU UUUU bNo change 0 254, 255 (Mask) 1 byte RAM “RMS LOAD CURRENT” UUUU UUUU bNo change 0 254, 255 (Mask) 1 byte RAM “REAL LOAD POWER” UUUU UUUU bNo change 0 65534, 65535 (Mask) 2 bytes RAM “LOAD RATING” Factory burn-in No change 0 254,
49、255 (Mask) 1 byte ROM “DEVICE TYPE” 4 No change 0 - 254 1 byte ROM “EXTENDED VERSION NUMBER” 1 No change 0 - 255 1 byte ROM U = undefined aPersistent memory (storage time indefinite) if not stated otherwise bPower up value, except bit 7 of “FAILURE STATUS BYTE 1” and bit 4 of “DIMMER STATUS” c Bit 7 of “FAILURE STATUS BYTE 1” and Bit 4 of “DIMMER STATUS” shall be stored in