1、raising standards worldwideNO COPYING WITHOUT BSI PERMISSION EXCEPT AS PERMITTED BY COPYRIGHT LAWBSI Standards PublicationField device tool (FDT) interface specification Part 303-2: Communication profile integration IEC 61784 CP 3/4, CP 3/5 and CP 3/6BS EN 62453-303-2:2009National forewordThis Briti
2、sh Standard is the UK implementation of EN 62453-303-2:2009. It isidentical to IEC 62453-303-2:2009.The UK participation in its preparation was entrusted to Technical CommitteeAMT/7, Industrial communications: process measurement and control, including fieldbus.A list of organizations represented on
3、 this committee can be obtained onrequest to its secretary.This publication does not purport to include all the necessary provisions of acontract. Users are responsible for its correct application. BSI 2010ISBN 978 0 580 62563 3ICS 25.040.40; 35.100.05; 35.110Compliance with a British Standard canno
4、t confer immunity fromlegal obligations.This British Standard was published under the authority of the StandardsPolicy and Strategy Committee on 31 January 2010Amendments issued since publicationAmd. No. Date Text affectedBRITISH STANDARDBS EN 62453-303-2:2009EUROPEAN STANDARD EN 62453-303-2 NORME E
5、UROPENNE EUROPISCHE NORM October 2009 CENELEC European Committee for Electrotechnical Standardization Comit Europen de Normalisation Electrotechnique Europisches Komitee fr Elektrotechnische Normung Central Secretariat: Avenue Marnix 17, B - 1000 Brussels 2009 CENELEC - All rights of exploitation in
6、 any form and by any means reserved worldwide for CENELEC members. Ref. No. EN 62453-303-2:2009 E ICS 25.040.40; 35.100.05; 35.110 English version Field device tool (FDT) interface specification - Part 303-2: Communication profile integration - IEC 61784 CP 3/4, CP 3/5 and CP 3/6 (IEC 62453-303-2:20
7、09) Spcification des interfaces des outils des dispositifs de terrain (FDT) - Partie 303-2: Intgration des profils de communication - CEI 61784 CP 3/4, CP 3/5 et CP 3/6 (CEI 62453-303-2:2009) Field Device Tool (FDT)-Schnittstellenspezifikation - Teil 303-2: Integration von Kommunikationsprofilen - K
8、ommunikationsprofile (CP) 3/4, 3/5 und 3/6 nach IEC 61784 (IEC 62453-303-2:2009) This European Standard was approved by CENELEC on 2009-08-01. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of
9、a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the Central Secretariat or to any CENELEC member. This European Standard exists in three official versions (English, French, German). A ver
10、sion in any other language made by translation under the responsibility of a CENELEC member into its own language and notified to the Central Secretariat has the same status as the official versions. CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Cyprus,
11、the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and the United Kingdom. BS EN 62453-303-2:2009EN 62453-30
12、3-2:2009 - 2 - Foreword The text of document 65E/128/FDIS, future edition 1 of IEC 62453-303-2, prepared by SC 65E, Devices and integration in enterprise systems, of IEC TC 65, Industrial-process measurement, control and automation, was submitted to the IEC-CENELEC parallel vote and was approved by
13、CENELEC as EN 62453-303-2 on 2009-08-01. Each part of the EN 62453-3xy series is intended to be read in conjunction with EN 62453-2. The following dates were fixed: latest date by which the EN has to be implemented at national level by publication of an identical national standard or by endorsement
14、(dop) 2010-05-01 latest date by which the national standards conflicting with the EN have to be withdrawn (dow) 2012-08-01 Annex ZA has been added by CENELEC. _ Endorsement notice The text of the International Standard IEC 62453-303-2:2009 was approved by CENELEC as a European Standard without any m
15、odification. In the official version, for Bibliography, the following note has to be added for the standard indicated: IEC 61158 NOTE Harmonized in EN 61158 series (not modified). _ BS EN 62453-303-2:2009- 3 - EN 62453-303-2:2009 Annex ZA (normative) Normative references to international publication
16、s with their corresponding European publications The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.
17、NOTE When an international publication has been modified by common modifications, indicated by (mod), the relevant EN/HD applies. Publication Year Title EN/HD Year IEC 61158-5-10 1)Industrial communication networks - Fieldbus specifications - Part 5-10: Application layer service definition - Type 10
18、 elements EN 61158-5-10 20082)IEC 61158-6-10 1)Industrial communication networks - Fieldbus specifications - Part 6-10: Application layer protocol specification - Type 10 elements EN 61158-6-10 20082)IEC 61784-2 1)Industrial communication networks - Profiles - Part 2: Additional fieldbus profiles fo
19、r real-time networks based on ISO/IEC 8802-3 EN 61784-2 20082)IEC 62453-1 2009 Field device tool (FDT) interface specification - Part 1: Overview and guidance EN 62453-1 2009 IEC 62453-2 2009 Field device tool (FDT) interface specification - Part 2: Concepts and detailed description EN 62453-2 2009
20、1)Undated reference. 2)Valid edition at date of issue. BS EN 62453-303-2:2009 2 62453-303-2 IEC:2009(E) CONTENTS INTRODUCTION.6 1 Scope.7 2 Normative references .7 3 Terms, definitions, symbols, abbreviated terms and conventions 7 3.1 Terms and definitions 7 3.2 Abbreviated terms .8 3.3 Conventions
21、8 3.3.1 Data type names and references to data types 8 3.3.2 Vocabulary for requirements8 3.3.3 Use of UML .8 4 Bus category 8 5 Access instance and device data9 5.1 Process Channel objects provided by DTM9 5.2 DTM services to access instance and device data .9 6 Protocol specific behavior.9 7 Proto
22、col specific usage of general data types.9 8 Protocol specific common data types11 9 Network management data types11 9.1 General .11 9.2 Parameter access data types 11 10 Communication data types .17 11 Channel parameter data types20 12 Device identification .23 12.1 Protocol specific handling of da
23、ta type STRING 23 12.2 Device type identification data types .23 12.3 Topology scan data types26 12.4 Scan identification data types27 12.5 Device type identification data types .29 Bibliography32 Figure 1 Part 303-2 of the IEC 62453 series 6 Table 1 Protocol identifier 8 Table 2 Physical layer iden
24、tifier .8 Table 3 Protocol specific usage of general data types9 Table 4 Simple parameter access data types .11 Table 5 Structured parameter access data types14 Table 6 Simple communication data types .17 Table 7 Structured communication data types18 Table 8 Simple channel parameter data types21 Tab
25、le 9 Structured channel parameter data types 22 Table 10 Identification data types for PROFINET with pure DCP24 BS EN 62453-303-2:200962453-303-2 IEC:2009(E) 3 Table 11 Identification data types for PROFINET with I NetworkManagementInfoWrite service. 9.2 Parameter access data types The data types de
26、scribe the parameter information of an IEC 61784 CP 3/4, CP 3/5 and CP 3/6 device (see Table 4 and Table 5) Table 4 Simple parameter access data types Data type Definition Description arType UINT ARType according to the PROFINET specification Shall only be set by Parent arProperties UDINT ARProperti
27、es according to the PROFINET specification Shall only be set by Parent arUUID UUID ARUUID according to the PROFINET specification Shall only be set by Parent alarmCRType UINT AlarmCRType according to the PROFINET specification Shall only be set by Parent alarmCRProperties UDINT AlarmCRProperties acc
28、ording to the PROFINET specification Shall only be set by Parent rtaTimeoutFactor UINT RTATimeoutFactor according to the PROFINET specification Shall only be set by Parent rtaRetries UINT RTARetries according to the PROFINET specification Shall only be set by Parent localAlarmReference UINT LocalAla
29、rmReference according to the PROFINET specification Shall only be set by Parent maxAlarmDataLength UINT MaxAlarmDataLength according to the PROFINET specification Shall only be set by Parent infoText STRING Additional textual information Shall only be set by DTM localIndex UINT The attribute used wi
30、thin Device/Identification to address the device instance. Shall only be set by DTM BS EN 62453-303-2:2009 12 62453-303-2 IEC:2009(E) Data type Definition Description nameOfStation STRING The station name is the primary address. The default value is the DNS_CompatibleName of the GSDML. The Parent sh
31、all configure the station name according to the rules defined by the DNS_CompatibleName. Shall only be set by Parent apart of the default value, which shall be set by DTM (during InitNew) dynIpAddress BOOL The attribute indicates whether the IP address is dynamically assigned to the device. Shall on
32、ly be set by Parent extAddrSupported BOOL Extended address assignment (e.g. by DHCP, BootP) is supported by the Profinet IO Device. Shall only be set by DTM ipAddress STRING The attribute contains the IP address that is assigned to the device. The IP address is a secondary address. The default value
33、 is “0.0.0.0”. Shall only be set by Parent ipSubnetMask STRING The attribute contains the subnet mask. The default value is “255.255.255.255”. Shall only be set by Parent ipDefaultGateway STRING The attribute contains the default gateway address. The default value is an empty string. Shall only be s
34、et by Parent macAddress STRING The attribute contains the MAC address of the device. The MAC address is a secondary address. The macAddress attribute is of type string and shall be used with format shown in the example: Example: 00:A0:45:01:02:03 Shall only be set by Parent slotNumber UINT The slot
35、address that is used by the module Shall be set by DTM during configuration. Can be set by Parent during topology scan moduleIdentNumber UDINT The ModuleIdentNumber according to the PROFINET specification Shall be set by DTM during configuration. Can be set by Parent during topology scan modulePrope
36、rties UINT This attribute is reserved for future use according to the PROFINET specification subSlotNumber UINT The subslot address that is used by the submodule. Shall be set by DTM during configuration. Can be set by Parent during topology scan subModuleIdentNumber UDINT The SubmoduleIdentNumber a
37、ccording to the PROFINET specification. Shall be set by DTM during configuration. Can be set by Parent during topology scan ioType enumeration (Input | Output | InputAndOutput ) Allowed values are: Input, Output, InputAndOutput. Values and meaning according to the PROFINET specification - SubmoduleP
38、roperties.Type. Shall be set by DTM during configuration. Can be set by Parent during topology scan sharedInput enumeration (IOController | IOControllerShare ) Allowed values are: IOController, IOControllerShare. Values and meaning according to the PROFINET specification - SubmoduleProperties.Shared
39、Input. Shall be set by DTM during configuration. Can be set by Parent during topology scan BS EN 62453-303-2:200962453-303-2 IEC:2009(E) 13 Data type Definition Description reduceInputSubmodule DataLength enumeration (Expected | Zero ) Allowed values are: Expected, Zero. Values and meaning according
40、 to the PROFINET specification - SubmoduleProperties.ReduceInputSubmoduleDataLength. Shall be set by DTM during configuration. Can be set by Parent during topology scan reduceOutputSubmodule DataLength enumeration (Expected | Zero ) Allowed values are: Expected, Zero. Values and meaning according PR
41、OFINET specification - SubmoduleProperties.ReduceOutputSubmoduleDataLength. Shall be set by DTM during configuration. Can be set by Parent during topology scan discardIOXS enumeration (Expected | Zero ) Allowed values are: Expected, Zero. Values and meaning according PROFINET specification -Submodul
42、eProperties.DiscardIOXS. Shall be set by DTM during configuration. Can be set by Parent during topology scan api UDINT The API according to the PROFINET specification. Shall be set by DTM during configuration. Can be set by Parent during topology scan index UINT The address of the desired record dat
43、a object. Shall only be set by DTM recordData ARRAY OF USINT The binary data that will be written to the submodule during startup or connect. The record data implicitly contain the record data length. Shall only be set by DTM consistency enumeration (itemConsistency | allItemsConsistency ) The consi
44、stency of the input data. Shall only be set by DTM during configuration sendClockFactor UINT SendClockFactor according to the PROFINET specification. Shall only be set by Parent, if the attribute belongs to the element SubModule. Shall only be set by DTM, if the attribute belongs to the element Send
45、ClockFactor reductionRatio UINT ReductionRatio according to the PROFINET specification. Shall only be set by Parent, if the attribute belongs to the element SubModule. Shall only be set by DTM, if the attribute belongs to the element ReductionRatio watchdogFactor UINT WatchdogFactor according to the
46、 PROFINET specification. Shall only be set by Parent dataHoldFactor UINT DataHoldFactor according to the PROFINET specification. Shall only be set by Parent BS EN 62453-303-2:2009 14 62453-303-2 IEC:2009(E) Table 5 Structured parameter access data types Definition Data type Elementary data types Usa
47、geMultiplicity Description STRUCT Record data that will be written to the submodule during startup or connect index M 11 recordData M 11 RecordParamData fdt:name O 01 STRUCT List of records that will be written to the submodule during startup or connect collection of M 11 RecordParamDataList RecordP
48、aramData 1* STRUCT List of output data provided by a submodule. The list refers to the corresponding FDT-Channel objects consistency O 01 OutputDataList fdt:ChannelReferences M 11 STRUCT List of input data provided by a submodule. The list refers to the corresponding FDT-Channel objects consistency
49、O 01 InputDataList fdt:ChannelReferences M 11 STRUCT The identification and configuration of a submodule subSlotNumber M 11 fdt:name M 11 fdt:descriptor O 01 subModuleIdentNumber M 11 api M 11 sendClockFactor M 11 reductionRatio M 11 watchdogFactor M 11 dataHoldFactor M 11 InputDataList O 01 OutputDataList O 01 RecordParamDataList O 01 SubModule SubModuleProperties O 01 BS EN 62453-303-2:200962453-303-2 IEC:2009(E) 15 Defini