1、BSI Standards PublicationLow-voltage switchgear and controlgear enclosed equipmentPart 1: Enclosed switch-disconnectors outside the scope of IEC 60947-3 to provide isolation during repair and maintenance workBS EN 62626-1:2014National forewordThis British Standard is the UK implementation of EN 6262
2、6-1:2014. It isidentical to IEC 62626-1:2014.The UK participation in its preparation was entrusted by TechnicalCommittee PEL/17, Switchgear, controlgear, and HV-LV co-ordination, toSubcommittee PEL/17/2, Low voltage switchgear and controlgear.A list of organizations represented on this committee can
3、 be obtained onrequest to its secretary.This publication does not purport to include all the necessary provisions ofa contract. Users are responsible for its correct application. The British Standards Institution 2014.Published by BSI Standards Limited 2014ISBN 978 0 580 67620 8ICS 29.120.40; 29.130
4、.20Compliance with a British Standard cannot confer immunity fromlegal obligations.This British Standard was published under the authority of theStandards Policy and Strategy Committee on 30 June 2014.Amendments/corrigenda issued since publicationAmd. No. Date Text affectedBRITISH STANDARDBS EN 6262
5、6-1:2014EUROPEAN STANDARD NORME EUROPENNE EUROPISCHE NORM EN 62626-1 May 2014 ICS 29.120.40; 29.130.20 English Version Low-voltage switchgear and controlgear enclosed equipment - Part 1: Enclosed switch-disconnectors outside the scope of IEC 60947-3 to provide isolation during repair and maintenance
6、 work (IEC 62626-1:2014) Appareillage basse tension sous enveloppe - Partie 1: Interrupteur-sectionneur en coffret, en dehors du domaine dapplication de la norme CEI 60947-3, destin garantir lisolation pendant les phases de maintenance (CEI 62626-1:2014) Gekapselte Niederspannungsschaltgerte - Teil
7、1: Gekapselte Lasttrennschalter auerhalb des Anwendungsbereiches von IEC 60947-3, zum Trennen whrend der Reparatur- und Wartungsarbeit (IEC 62626-1:2014) This European Standard was approved by CENELEC on 2014-03-21. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which
8、stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CENELEC member. This E
9、uropean Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the same status as the official versions. CENELEC
10、 members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the Netherlands
11、, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom. European Committee for Electrotechnical Standardization Comit Europen de Normalisation Electrotechnique Europisches Komitee fr Elektrotechnische Normung CEN-CENELEC Management Centre:
12、Avenue Marnix 17, B-1000 Brussels 2014 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members. Ref. No. EN 62626-1:2014 E BS EN 62626-1:2014EN 62626-1:2014 - 2 - Foreword The text of document 17B/1839A/FDIS, future edition 1 of IEC 62626-1, prepared by
13、 SC 17B “Low-voltage switchgear and controlgear“ of IEC/TC 17 “Switchgear and controlgear“ was submitted to the IEC-CENELEC parallel vote and approved by CENELEC as EN 62626-1:2014. The following dates are fixed: latest date by which the document has to be implemented at national level by publicatio
14、n of an identical national standard or by endorsement (dop) 2014-12-21 latest date by which the national standards conflicting with the document have to be withdrawn (dow) 2017-03-21 Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights.
15、 CENELEC and/or CEN shall not be held responsible for identifying any or all such patent rights. This standard covers the Principle Elements of the Safety Objectives for Electrical Equipment Designed for Use within Certain Voltage Limits (LVD - 2006/95/EC). Endorsement notice The text of the Interna
16、tional Standard IEC 62626-1:2014 was approved by CENELEC as a European Standard without any modification. In the official version, for Bibliography, the following notes have to be added for the standards indicated: IEC 60204-1 NOTE Harmonized as EN 60204-1. IEC 60364-5-51 NOTE Harmonized as HD 60364
17、-5-51. IEC 60529 NOTE Harmonized as EN 60529. IEC 60947-5-1 NOTE Harmonized as EN 60947-5-1. ISO 13850 NOTE Harmonized as EN ISO 13850. BS EN 62626-1:2014- 3 - EN 62626-1:2014 Annex ZA (normative) Normative references to international publications with their corresponding European publications The f
18、ollowing documents, in whole or in part, are normatively referenced in this document and are indispensable for its application. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. NOTE 1 When
19、an International Publication has been modified by common modifications, indicated by (mod), the relevant EN/HD applies. NOTE 2 Up-to-date information on the latest versions of the European Standards listed in this annex is available here: www.cenelec.eu Publication Year Title EN/HD Year IEC 60050 se
20、ries International Electrotechnical Vocabulary - series IEC 60947-1 A1 2007 2010 Low-voltage switchgear and controlgear - Part 1: General rules EN 60947-1 2007 IEC 60947-3 A1 2008 2012 Low-voltage switchgear and controlgear - Part 3: Switches, disconnectors, switch-disconnectors and fuse-combination
21、 units EN 60947-3 A1 2009 2012 IEC 62262 2002 Degrees of protection provided by enclosures for electrical equipment against external mechanical impacts (IK code) EN 62262 2002 BS EN 62626-1:2014 2 62626-1 IEC:2014 CONTENTS INTRODUCTION . 5 1 Scope 6 2 Normative references 6 3 Terms and definitions 7
22、 4 Classification . 7 5 Characteristics 7 6 Product information . 8 6.1 Nature of information . 8 6.2 Markings 8 Front-marking . 8 6.2.1Additional marking 8 6.2.27 Normal service, mounting and transport conditions 9 8 Constructional and performance requirements . 9 8.1 Constructional requirements 9
23、General 9 8.1.1Locking . 9 8.1.2Environmental influences 9 8.1.3Mechanical strength 9 8.1.4Degree of protection . 9 8.1.5Operation/actuation 9 8.1.68.2 Performance requirements . 9 General 9 8.2.1Switching capacity 9 8.2.29 Tests . 10 9.1 General 10 9.2 Type tests 10 Bibliography 11 Figure 1 Symbol
24、for marking according to this standard . 8 Table 1 Requirements and tests for devices . 10 BS EN 62626-1:201462626-1 IEC:2014 5 INTRODUCTION Enclosed switch-disconnectors covered by this part of IEC 62626 are intended for use in various applications, to provide isolation of electrical equipment, esp
25、ecially motor circuits, during repair, cleaning and maintenance works. Such enclosed switch-disconnectors are sometimes known as “maintenance switches”, or “safety switches”. The name “safety switch” is also used for safety related position switches, inspection switches and switches for other applic
26、ations, which are not covered by this standard. This part of IEC 62626 specifies additional requirements for enclosed switch-disconnectors according to IEC 60947-3 to provide isolation of electrical equipment during repair and maintenance work. Enclosed switch-disconnectors according to this standar
27、d are mounted close to the equipment which has to be isolated and are usually operated by instructed persons. NOTE 1 The term “safety switch” is not recognized in some countries as the same meaning given in this standard. NOTE 2 Switch-disconnectors do not necessarily meet the requirements for preve
28、ntion of unexpected start, especially if there are energy sources other than electrical. BS EN 62626-1:2014 6 62626-1 IEC:2014 LOW-VOLTAGE SWITCHGEAR AND CONTROLGEAR ENCLOSED EQUIPMENT Part 1: Enclosed switch-disconnectors outside the scope of IEC 60947-3 to provide isolation during repair and maint
29、enance work 1 Scope This part of IEC 62626 applies to enclosed switches-disconnectors with rated voltages up to 1 000 V a.c. for repair and maintenance work or cleaning work in load circuits. Devices within the scope of this standard are derived from switch-disconnectors according to IEC 60947-3. En
30、closed switch-disconnectors in this standard are suitable for isolation according to IEC 60947 series and are not supposed to be equipped with means for remote control or automatic switching to avoid unexpected or accidental start. These devices are not intended to be used for operational switching,
31、 quick start and stop or jogging. NOTE 1 However, these kind of devices can provide the possibility to switch off electrical equipment (even in a critical situation or not). Devices within the scope of this standard provide isolation of electrical equipment, especially in motor circuits, during repa
32、ir and maintenance or cleaning works. Enclosed switch-disconnectors for various applications to provide isolation of electrical equipment during repair and maintenance work, named “maintenance switches”, are designated hereafter as devices with: a) different classes; b) characteristics of each class
33、; c) minimum test requirements; d) information to be marked on the equipment or made available by the manufacturer, for example in the catalogue. NOTE 2 This standard does not specify additional requirements that are necessary for the application of these switches, for example, in explosive atmosphe
34、res (e.g. ATEX in Europe). 2 Normative references The following documents, in whole or in part, are normatively referenced in this document and are indispensable for its application. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced do
35、cument (including any amendments) applies. IEC 60050 (all parts), International electrotechnical vocabulary. Available from: IEC 60947-1:2007, Low-voltage switchgear and controlgear Part 1: General rules Amendment 1:2010 IEC 60947-3:2008, Low-voltage switchgear and controlgear Part 3: Switches, disc
36、onnector, switch-disconnector and fuse-combination units Amendment 1:2012 IEC 62262:2002, Degrees of protection provided by enclosures for electrical equipment against external mechanical impacts (IK code) BS EN 62626-1:201462626-1 IEC:2014 7 3 Terms and definitions For the purposes of this document
37、, the terms and definitions given in IEC 60050-441, IEC 60947-1, IEC 60947-3, as well as the following apply. 3.1 (mechanical) switch mechanical switching device capable of making, carrying and breaking currents under normal circuit conditions which may include specified operating overload condition
38、s and also carrying for a specified time currents under specified abnormal circuit conditions such as those of short-circuit Note 1 to entry: A switch may be capable of making, but not breaking, short-circuit currents. SOURCE: IEC 60050-441:1984, 441-14-10 3.2 disconnector mechanical switching devic
39、e which, in the open position, complies with the requirements specified for the isolating function Note 1 to entry: A disconnector is capable of opening and closing a circuit when either a negligible current is broken or made, or when no significant change in the voltage across the terminals of each
40、 of the poles of the disconnector occurs. It is also capable of carrying currents under normal circuit conditions and carrying for a specified time currents under abnormal conditions such as those of short circuit. SOURCE: IEC 60050-441:1984, 441-14-05, modified Reference has been made to the isolat
41、ing function instead of the isolating distance. 3.3 switch-disconnector switch which, in the open position, satisfies the isolating requirements specified for a disconnector SOURCE: IEC 60050-441:1984, 441-14-12 3.4 enclosed switch switch with a dedicated enclosure, providing a specified degree of p
42、rotection against certain external influences 4 Classification Devices according to this standard are classified into two classes, class 0 and class 1. Class 0 is the minimum requirement level, as class 1 is this required by harsh and rough/heavy duty conditions, for example for chemical industries.
43、 Both are specified in Table 1. 5 Characteristics Clause 4 of IEC 60947-3:2008, Amendment 1:2012 applies. BS EN 62626-1:2014 8 62626-1 IEC:2014 6 Product information 6.1 Nature of information Subclause 5.1 of IEC 60947-1:2007, Amendment 1:2010 applies with the following additional dashed item under
44、list of “Characteristics”: corresponding class of this standard. 6.2 Markings Front-marking 6.2.1Each device shall be marked in a durable and legible manner with the following data. The markings for a), b) and c) below shall be on the equipment itself or on a name-plate or name-plates attached to th
45、e device, and shall be located at a place such that they are legible from the front after mounting the equipment in accordance with the manufacturers instructions. a) Indication of the open and closed position. The open and closed position shall be respectively indicated by the graphical symbols (IE
46、C 60417-5008 (2002-10) and (IEC 60417-5007 (2002-10), see 7.1.6.1 of IEC 60947-1:2007. b) Symbol for marking according to this standard, see Figure 1. Figure 1 Symbol for marking according to this standard c) A corrosion-resistant label or plate marked with the text “maintenance switch” or translate
47、d in national language. The label or plate shall be colored according to national practice. The height of the text shall be at least 5 mm. The text “maintenance switch” shall be marked in a durable and legible manner and the color of the text shall be different from the color of the label or plate.
48、NOTE The translations of the terms “maintenance switch” on the label into different languages can be for example “interrupteur de maintenance”, “Sicherheitschalter”, or equivalent translations in other languages. Additional marking 6.2.2The following information shall be marked on the equipment, but
49、 does not need to be visible from the front when the device is mounted: a) manufacturers name or trade mark; b) type designation or serial number; IEC 0547/14 BS EN 62626-1:201462626-1 IEC:2014 9 c) rated operational current (or rated power) at the rated operational voltage; d) value (or range) of the rated frequency; e) number of this standard (IEC 62626-1) including class (see Clause 4), if the manufacturer claims compliance with this standard. 7 Normal service, mounting and transport con